Plan Review Details - Permit 22070014
Plan Review Stops For Permit 22070014
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 08:20 Rev Time 0.00
Received By pvalenti Date 2022-10-03 Time 07:51 Sent To  
Notes
2022-10-03 08:21:503RD REVIEW BUILDING REVIEW DENIED:
  
 1.) CITY OF WPB AMENDMENTS TO FBC B 107.2.1, FBC B
 107.2.1.2, PLEASE PROVIDE MORE INFORMATION AS THIS
 PROJECT DOES NOT APPEAR TO BE PORTABLE DUE TO THE 18"
 DIAMETER BY 4' DEEP FOOTINGS AND THE 12' DIAMETER OF
 THE TIKI HUT ROOF.
  
 THE TIKI BAR INFORMATION PACKAGE THAT DESCRIBES THE
 PARADISE GRILLS PORTABLE PRODUCTS INDICATES THAT THERE
 IS AN EXCEPTION TO THE PRODUCTS BEING PORTABLE. THAT IS
 FOR THE "MONACO PERGOLA" WHICH APPARENTLY IS PERMANENT
 AND COMES WITH A SET OF ENGINEERED DRAWINGS INCLUDING
 FOUNDATION CONNECTION. THIS MAY BE AN OPTION FOR THE
 TIKI HUT IF APPLICABLE.
  
 PLEASE PROVIDE ENGINEERED DRAWINGS FOR THIS TIKI HUT
 PROJECT THAT WILL MEET THE REQUIREMENTS OF THE 2020
 FLORIDA BUILDING CODE FOR WINDLOADS OR DEMONSTRATE HOW
 THIS PRODUCT, INCLUDING TIKI HUT ROOF, CAN BE TAKEN
 DOWN AND PLACED IN A SECURE LOCATION IN THE EVENT OF A
 STORM/APPROACHING HIGH WINDS.
  
 2.) CITY OF WPB AMENDMENTS TO FBC B 107.2.5, PLEASE
 PROVIDE A CLEAR SITE PLAN SHOWING TO SIZE AND SCALE
 LOCATION OF NEW CONSTRUCTION & EXISTING STRUCTURES
 INCLUDING DISTANCE MEASUREMENTS OF SET-BACKS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-07 Cont ID  
Sent By pvalenti Date 2022-09-07 Time 15:55 Rev Time 0.00
Received By pvalenti Date 2022-09-07 Time 15:54 Sent To  
Notes
2022-09-07 15:57:19PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND REVIEW BUILDING REVIEW DENIED:
  
 1.) CITY OF WPB AMENDMENTS TO FBC B 107.2.1, FBC B
 107.2.1.2, PLEASE PROVIDE MORE INFORMATION AS THIS
 PROJECT DOES NOT APPEAR TO BE PORTABLE DUE TO THE 18"
 DIAMETER BY 4' DEEP FOOTINGS AND THE 12' DIAMETER OF
 THE TIKI HUT ROOF.
  
 THE TIKI BAR INFORMATION PACKAGE THAT DESCRIBES THE
 PARADISE GRILLS PORTABLE PRODUCTS INDICATES THAT THERE
 IS AN EXCEPTION TO THE PRODUCTS BEING PORTABLE. THAT IS
 FOR THE "MONACO PERGOLA" WHICH APPARENTLY IS PERMANENT
 AND COMES WITH A SET OF ENGINEERED DRAWINGS INCLUDING
 FOUNDATION CONNECTION. THIS MAY BE AN OPTION FOR THE
 TIKI HUT IF APPLICABLE.
  
 PLEASE PROVIDE ENGINEERED DRAWINGS FOR THIS TIKI HUT
 PROJECT THAT WILL MEET THE REQUIREMENTS OF THE 2020
 FLORIDA BUILDING CODE FOR WINDLOADS OR DEMONSTRATE HOW
 THIS PRODUCT, INCLUDING TIKI HUT ROOF, CAN BE TAKEN
 DOWN AND PLACED IN A SECURE LOCATION IN THE EVENT OF A
 STORM/APPROACHING HIGH WINDS.
  
 2.) CITY OF WPB AMENDMENTS TO FBC B 107.2.5, PLEASE
 PROVIDE A SITE PLAN SHOWING TO SIZE AND SCALE LOCATION
 OF NEW CONSTRUCTION & EXISTING STRUCTURES INCLUDING
 DISTANCE MEASUREMENTS OF SET-BACKS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By pvalenti Date 2022-08-03 Time 09:30 Rev Time 0.00
Received By pvalenti Date 2022-08-03 Time 08:43 Sent To  
Notes
2022-08-03 09:31:48PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) CITY OF WPB AMENDMENTS TO FBC B 107.2.1, FBC B
 107.2.1.2, PLEASE PROVIDE MORE INFORMATION AS THIS
 PROJECT DOES NOT APPEAR TO BE PORTABLE DUE TO THE 18"
 DIAMETER BY 4' DEEP FOOTINGS AND THE 12' DIAMETER OF
 THE TIKI HUT ROOF.
  
 THE TIKI BAR INFORMATION PACKAGE THAT DESCRIBES THE
 PARADISE GRILLS PORTABLE PRODUCTS INDICATES THAT THERE
 IS AN EXCEPTION TO THE PRODUCTS BEING PORTABLE. THAT IS
 FOR THE "MONACO PERGOLA" WHICH APPARENTLY IS PERMANENT
 AND COMES WITH A SET OF ENGINEERED DRAWINGS INCLUDING
 FOUNDATION CONNECTION. THIS MAY BE AN OPTION FOR THE
 TIKI HUT IF APPLICABLE.
  
 PLEASE PROVIDE ENGINEERED DRAWINGS FOR THIS TIKI HUT
 PROJECT THAT WILL MEET THE REQUIREMENTS OF THE 2020
 FLORIDA BUILDING CODE FOR WINDLOADS OR DEMONSTRATE HOW
 THIS PRODUCT, INCLUDING TIKI HUT ROOF, CAN BE TAKEN
 DOWN AND PLACED IN A SECURE LOCATION IN THE EVENT OF A
 STORM/APPROACHING HIGH WINDS.
  
 2.) CITY OF WPB AMENDMENTS TO FBC B 107.2.5, PLEASE
 PROVIDE A SITE PLAN SHOWING TO SIZE AND SCALE LOCATION
 OF NEW CONSTRUCTION & EXISTING STRUCTURES INCLUDING
 DISTANCE MEASUREMENTS OF SET-BACKS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-24 Cont ID  
Sent By pvalenti Date 2022-07-24 Time 09:41 Rev Time 0.00
Received By shill Date 2022-07-24 Time 09:41 Sent To  
Notes
2022-07-24 09:47:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107 SCOPE NOT CLEAR.
  
 THE SURVEY SHOWS A PROPOSED FENCE. PROVIDE A
 SURVEY/SITE PLAN WITH THE PROPOSED IMPROVEMENTS FOR
 THIS APPLICATION CLEARLY NOTED AS "PROPOSED" WITH NO
 OTHER MARKINGS.
  
 THE APPLICATION DESCRIPTION IS FOR "INSTALL IN GROUND
 CONCRETE PILLARS 18" WIDE & 4' DOWN TO SECURE GRILL".
  
 THE PROPERTY MANAGER DENIAL LETTER IS FOR "COVER BAR
 AND GRILL (TIKI HUT)".
  
 THE CONCEPTUAL PLAN IS FOR A TIKI HUT.
  
 OTHER PLANS APPEAR TO SHOW AN OUTDOOR KITCHEN INCLUDING
 CABINETRY.
  
 2. FOR ALL EXTERIOR STRUCTURES THAT ARE PROPOSED (TIKI
 HUT, CABINETRY, CONCRETE, ETC.), PROVIDE A STRUCTURAL
 DETAIL INCLUDING WIND DESIGN CRITERIA, FBC R 301. EACH
 ITEM IS REQUIRED TO BE DEPICTED, TO SCALE, ON THE SITE
 PLAN.
  
 3. ALL PLANS ARE TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN, FBC 107.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 16:10 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 10:33 Rev Time 0.00
Received By ccole Date 2022-08-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By ccole Date 2022-07-25 Time 08:01 Rev Time 0.00
Received By ccole Date 2022-07-25 Time 08:01 Sent To  
Notes
2022-07-25 08:22:15 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22070014
 7/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS APPEAR TO SHOW A GAS GRILL WILL BE
 INSTALLED AT THE TIKI HUT. PLEASE CLARIFY IF THE GAS TO
 THE GRILL WILL BE SUPPLIED BY A POTABLE LP TANK OR A
 PERMANENT NATURAL GAS SUPPLY PIPE FROM A NEW OR
 EXISTING GAS SERVICE- SEC. 107.2.1 WPB. PLEASE NOTE
 SEC. G2447.1 FBC RES STATES-
 "COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS." THE
 PORTABLE GRILL APPEARS TO BE A PERMANENT INSTALLATION.
 PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GRILL TO VERIFY COMPLIANCE. THE MINIMUM CRITERIA FOR
 PERMANENTLY INSTALLED COOKING APPLIANCES INCLUDES GAS
 PIPING (RISER DIAGRAM REQUIRED ONLY FOR PERMANENT GAS
 SERVICE PIPING), COMBUSTION AIR, VENTING, AND REVIEW OF
 THE APPLIANCE SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2022-09-09 Time 07:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-07 Cont ID  
Sent By pvalenti Date 2022-09-07 Time 15:57 Rev Time 0.00
Received By pvalenti Date 2022-08-16 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-08 Cont ID  
Sent By asangele Date 2022-08-08 Time 15:18 Rev Time 0.00
Received By asangele Date 2022-08-08 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 16:10 Rev Time 0.00
Received By mpeterso Date 2022-07-01 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 08:53 Rev Time 0.00
Received By ccole Date 2022-08-03 Time 08:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By ccole Date 2022-07-25 Time 08:00 Rev Time 0.00
Received By ccole Date 2022-07-25 Time 06:56 Sent To  
Notes
2022-07-25 08:01:381ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22070014
 7/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CLARIFY IF A SINK AND FAUCET FOR POTABLE
 WATER USE WILL BE INSTALLED IN THE TIKI HUT- SEC.
 107.2.1 WPB. THE MINIMUM CRITERIA FOR PLAN REVIEW IS
 SUBMITTAL OF A PLUMBING PIPING RISER DRAWING- SEC.
 107.3.5.3 WPB. PLEASE REVIEW SEC. P2602.1 FBC RES IN
 REGARD TO THE POTABLE WATER SUPPLY TO THE SINK AND
 SANITARY DRAINAGE- "THE WATER-DISTRIBUTION AND DRAINAGE
 SYSTEM OF ANY BUILDING OR PREMISES WHERE PLUMBING
 FIXTURES ARE INSTALLED SHALL BE CONNECTED TO A PUBLIC
 WATER SUPPLY OR SEWER SYSTEM, RESPECTIVELY, IF
 AVAILABLE."
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-24 Cont ID  
Sent By shill Date 2022-07-24 Time 09:51 Rev Time 0.00
Received By shill Date 2022-07-24 Time 09:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2022-09-16 Cont ID  
Sent By asangele Date 2022-09-16 Time 11:34 Rev Time 0.00
Received By asangele Date 2022-09-16 Time 11:34 Sent To  
Notes
2022-09-16 11:45:11FAILED
 9/16/2022
 PLEASE CORRECT SURVEY MEASUREMENT WHILE LABELING
 SETBACKS YOUR SURVEY IS CURRENTLY DEMONSTRATING INCHES
 NOT FEET.
 PLEASE ALSO MEASURE FROM THE TIKI BAR LOCATION.
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]
 561-822-1443

Review Stop Z ZONING
Rev No 3 Status F Date 2022-08-23 Cont ID  
Sent By asangele Date 2022-08-23 Time 10:11 Rev Time 0.00
Received By asangele Date 2022-08-23 Time 10:11 Sent To  
Notes
2022-08-23 10:12:498/23/2022
 FAILED
 PLEASE ADDRESS PREVIOUS COMMENTS
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-08 Cont ID  
Sent By asangele Date 2022-08-08 Time 15:17 Rev Time 0.00
Received By asangele Date 2022-08-08 Time 15:17 Sent To  
Notes
2022-08-08 15:18:238/8/2022
 FAIL
 PLEASE LABEL THE SETBACKS OF THE TIKI BAR ON SURVEY.
  
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-14 Cont ID  
Sent By asangele Date 2022-07-14 Time 10:35 Rev Time 0.00
Received By asangele Date 2022-07-14 Time 10:35 Sent To  
Notes
2022-07-14 10:38:087/14/2022
 FAIL
 PLEASE LABEL YOUR SURVEY WHERE YOU WILL BE LOCATING THE
 TIKI BAR ADDITIONALLY PLEASE ALSO LABEL THE SETBACKS OF
 IN ON THE SURVEY.
  
  
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]