Plan Review Details - Permit 22061703
Plan Review Stops For Permit 22061703
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-11 Cont ID  
Sent By mpeterso Date 2022-10-11 Time 16:24 Rev Time 0.00
Received By mpeterso Date 2022-10-11 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By mpeterso Date 2022-07-27 Time 08:54 Rev Time 0.00
Received By mpeterso Date 2022-07-27 Time 08:20 Sent To  
Notes
2022-07-27 09:06:44ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL THE USE AND SEQUENCE OF OPERATION FOR
 THE HOOD THERMOSTAT DETAILED IN DRAWING. IT APPEARS THE
 HOOD THERMOSTAT DETAILED IS ATTEMPTING TO BE USED FOR
 THE COOKING APPLIANCE INTERLOCK. IF THIS IS THE PURPOSE
 OF THIS THERMOSTAT, IT APPEARS THIS THERMOSTAT SHOULD
 BE CONNECTED ACCROSS THE MANUAL HOOD PILOT LIGHT SWITCH
 TO FUNCTION AS A COOKING APPLIANCE INTERLOCK. PLEASE
 EXPLAIN AS APPLICABLE. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2022-07-28 Cont ID  
Sent By cwalker Date 2022-07-06 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-28 09:04:14NO FIRE REVIEW REQUIRED, SINGLE FAMILY RESIDENCE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  
  
 HELLO,
  
 I AM THE OWNER AND WANTED TO CLARIFY THAT THE KITCHEN
 IS NOT GOING TO BE USE FOR ANY COMMERCIAL NEED. ITS
 JUST A CHEF?S KITCHEN FOR OUR HOME. FOR OCCUPANCY IT IS
 JUST MY WIFE AND MYSELF THAT LIVE HERE AND FAMILY WILL
 JOIN US IN OCCASIONS.
  
 YOU MENTION ANOTHER TYPE OF PERMIT? WHAT TYPE WOULD
 THAT BE? THE PLANS SHOULD SHOW CLEARANCE?
 I CAN UPLOAD MAIN PLANS FOR REFERENCE OF THE SPACE?
 THAT WOULD BE HELPFUL.
  
 PLEASE LET ME KNOW
  
  
 THANK YOU,
  
 ARMANDO YAGUES
 328 EDGEWOOD DRIVE WPB 33405
  
 PROVIDE THE OCCUPANCY CLASSIFIACTION. IN ADDITION TO
  THE HOOD SUPPRESSION SYSTEM, THE OWNER WILL NEED OT
  CLARIFY THE OCCUPANCY, AND ALSO THE VENTING SYSTEM,
  HOOD, FLUE AND DUCT, FAN, CLEARANCE TO COMBUSTIBLES,
  ETC. UNDER A SEPARATE PERMIT.THE APPROVAL OF THIS
  INSTALLATION WILL DEPEND UPON OTHER FACTORS INCLUDING
  THE TYPE OCCUPANCY TO BE UTILIZED FOR A COMMERCIAL
  COOKING APPLICATION
  
2022-07-06 08:58:41PROVIDE THE OCCUPANCY CLASSIFIACTION. IN ADDITION TO
 THE HOOD SUPPRESSION SYSTEM, THE OWNER WILL NEED OT
 CLARIFY THE OCCUPANCY, AND ALSO THE VENTING SYSTEM,
 HOOD, FLUE AND DUCT, FAN, CLEARANCE TO COMBUSTIBLES,
 ETC. UNDER A SEPARATE PERMIT.THE APPROVAL OF THIS
 INSTALLATION WILL DEPEND UPON OTHER FACTORS INCLUDING
 THE TYPE OCCUPANCY TO BE UTILIZED FOR A COMMERCIAL
 COOKING APPLICATION. NFPA 1, 1.14
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-11 Cont ID  
Sent By mpeterso Date 2022-10-11 Time 16:24 Rev Time 0.00
Received By mpeterso Date 2022-09-22 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By mpeterso Date 2022-07-27 Time 09:06 Rev Time 0.00
Received By mpeterso Date 2022-07-05 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By medwards Date 2022-09-26 Time 13:48 Rev Time 0.00
Received By medwards Date 2022-09-26 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By medwards Date 2022-07-12 Time 13:50 Rev Time 0.00
Received By medwards Date 2022-07-12 Time 13:50 Sent To  
Notes
2022-07-12 13:55:56PROVIDE A DRAWING SHOWING WHICH STRUCTURE ON THIS
 PROPERTY THIS HOOD SUPRESSION SYTEM IS BEING INSTALLED.
 THERE IS NO MECHANICAL HOOD PERMIT ISSUED FOR THIS HOOD
 SUPPRESSION SYSTEM. A MECHANICAL HOOD PERMIT AND PLAN
 REVIEW WILL BE REQUIRED. THERE IS NOT ENOUGH
 INFORMATION TO DO A COMPLETE REVIEW.
 THE DESIGNER OF THE DRAWINGS MUST PRINT AND SIGN THEIR
 NAME ON EACH DRAWING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-10-11 Cont ID  
Sent By mpeterso Date 2022-10-11 Time 16:24 Rev Time 0.00
Received By mpeterso Date 2022-10-11 Time 16:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-12 Cont ID  
Sent By medwards Date 2022-07-12 Time 13:58 Rev Time 0.00
Received By medwards Date 2022-07-12 Time 13:58 Sent To  
Notes
***NONE***