Plan Review Details - Permit 22061666
Plan Review Stops For Permit 22061666
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 15:12 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 14:24 Sent To  
Notes
2022-09-26 15:13:14BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS).
 1- ROOF FRAMING PLAN: (A)PROVIDE SECTION DETAIL FOR NEW
 (2)1-3/4"X16" LVL BEAM SHOWING HOW THE SIMPSON HANGER
 HU314-2 IS INSTALLED AT EACH END OF BEAM.
 NOTE: BEAM IS SITTING ON TOP OF THE MASONRY WALL.
 (B)NEW (2)1-3/4"X16" LVL BEAM: SPECIFY CONNECTORS
 RECEIVING EXISTING ROOF TRUSSES AND CONNECTORS
 RECEIVING NEW TRUSSES.
 C) PROVIDE DETAIL/ SPECS FOR BEAM ML2 SHOWN ON THE
 FRONT AND REAR ADDITIONS.
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS.
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 3- WALL SECTION S3/5.1: PROVIDE DETAIL OF NEW BEARING
 KNEE WALL OVER EXISTING ROOF STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS.
 4- SPECIFY ROOF CROSS VENTILATION. SPECIFY VENT SIZE
 AND LOCATION.
 5- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAI. SEC.
 R609.7.2.1 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK
 SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME.
 6- SOFFIT CONSTRUCTION DETAIL ON WALL SECTIONS:
 ENGINEER TO SPECIFY TYPE OF METAL PLASTER BASE FOR
 CEILINGS SHOWING COMPLIANCE WITH TABLE 3 OF ASTM C1063.
 NOTE: ALSO, PROVIDE DETAIL/SPECIFICATIONS FOR CEILING
 CONSTRUCTION AT NEW MASTER LANAI.
 7- SHEET 6.1: ENGINEER TO REVISE END ZONE DISTANCE. THE
 MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY
 NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL.
 8- TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER
 OF RECORD. AND, NEEDS TO BE HANDLED TO THE BUILDING
 INSPECTOR DURING THE FRAMING INSPECTION.
 9- PROVIDE PRODUCT APPROVAL FOR:
 A)EXTERIOR DOORS. JELD-WEN FLORIDA PRODUCT APPROVAL
 FL16708-R13 IS INCOMPLETE. NEED INSTALLATION
 INSTRUCTIONS DRAWINGS.
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES.
 C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED. FLORIDA PRODUCT APPROVAL FL17330-R4 IS
 INCOMPLETE. MISSING INSTALLATION INSTRUCTIONS. ALSO,
 NEED TO SPECIFY PADDY SIZE.
 D)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 E)ROOFING UNDERLAYMENT. SINGLE PLY ROOF SYSTEMS
 FL14318-R18 SUBMITTED IS NOT A ROOF TILE UNDERLAYMENT.
 THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 F)HIP & RIDGE METAL SUPPORT TO BE USED.
 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT
 APPROVAL SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY
 ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 REVISE SCHEDULE AS REQUIRED AND INCLUDE MISSING PRODUCT
 APPROVALS.
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT.
 B)CEILING R-VALUE ON PAGE 1 DOESN'T MATCH PLANS.
 C)DOORS ORIENTATION DOESN'T MATCH PLANS.
 D)REVISE WINDOWS INFORMATION ON PAGE 4. WINDOWS
 ORIENTATION, MATERIAL, AND OVERHANG SEPARATION TO MATCH
 PLANS.
 E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD.
 F)ENGINEER SPECIFIES 1/300 ATTIC VENT RATIO ON PAGE 4.
 PLANS DON'T SHOW THIS VENTILATION RATIO. ENGINEER TO
 PROVIDE DETAILS/SPECS SHOWING COMPLIANCE WITH 1/300
 RATIO. SEC. R806.2 FBC-RESIDENTIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By jgomez Date 2022-09-21 Time 16:27 Rev Time 0.00
Received By jgomez Date 2022-09-20 Time 18:01 Sent To  
Notes
2022-09-21 16:33:44RESIDENTIAL (R3)ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061666
 6205 WASHINGTON RD
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
 ORIGINAL COMMENT:
 1- UNABLE TO PERFORM REVIEW. MISSING
 STRUCTURAL/ARCHITECTURAL DRAWINGS FOR CONSTRUCTION OF
 PROPOSED ADDITION/ALTERATION. SEC. 107.5.5.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 A)ROOF FRAMING PLAN ON SHEET 8.0: PROVIDE SECTION
 DETAIL FOR NEW (2)1-3/4"X16" LVL BEAM SHOWING HOW THE
 SIMPSON HANGER HU314-2 IS INSTALLED AT EACH END OF
 BEAM. NOTE: ACCORDING TO WALL SECTION S1/5.0 THIS BEAM
 IS SITTING ON TOP OF THE MASONRY WALL.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)ROOF FRAMING PLAN ON SHEET 8.0: THERE IS NOT BEAM
 SCHEDULE PROVIDING SPECIFICATIONS FOR BEAM ML2 SHOWN ON
 THE FRONT AND REAR ADDITIONS. PROVIDE BEAM SCHEDULE.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C)ENGINEER OF RECORD TO REVISE ROOF SHEATHING NAILING
 SPECIFICATIONS TO COMPLY WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. NAIL SPACING TO COMPLY TABLE R803.2.3.1
 FBC-RESIDENTIAL. NAIL SPACING TO BE 4" 0.C.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS
  
 D)ENGINEER TO PROVIDE DETAIL OF NEW BEARING KNEE WALL
 OVER EXISTING ROOF STRUCTURE AS SPECIFIED ON WALL
 SECTION S3/5.1. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 E) ENGINEER TO SPECIFY ROOF CROSS VENTILATION AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY VENT
 SIZE AND LOCATION.
  
 F)PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 G)SOFFIT CONSTRUCTION DETAIL ON WALL SECTIONS: ENGINEER
 TO PROVIDE SPECIFICATIONS FOR TYPE OF METAL PLASTER
 BASE FOR CEILINGS SHOWING COMPLIANCE WITH TABLE 3 OF
 ASTM C1063.
 NOTE: ALSO, PROVIDE DETAIL/SPECIFICATIONS FOR CEILING
 CONSTRUCTION AT NEW MASTER LANAI.
  
 H)SHEET 6.1: ENGINEER TO REVISE END ZONE DISTANCE. THE
 MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY
 NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 I)TRUSS PACKAGE NEEDS TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD.
 NOTE: PLEASE DON'T RESUBMIT THE TRUSS PACKAGE AFTER IT
 IS APPROVED BY THE ENGINEER OF RECORD. THE APPROVED
 TRUSS PACKAGE NEEDS TO BE HANDLED TO THE BUILDING
 INSPECTOR DURING THE FRAMING INSPECTION.
  
 J) INTERIOR DESIGN DRAWINGS ARE NOT REQUIRED TO BE
 SUBMITTED. IF CONTRACTOR WANT TO SUBMIT THEM, THEN THEY
 NEED TO BE PROPERLY SIGNED AND SEALED BY THE INTERIOR
 DESIGNER OF RECORD AS REQUIRED BY CHAPER 481 F.S. WHEN
 SUBMITTING THEM FOR PUBLIC RECORDS.
  
  
 2- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 JELD-WEN FLORIDA PRODUCT APPROVAL FL16708-R13 IS
 INCOMPLETE. NEED INSTALLATION INSTRUCTIONS DRAWINGS.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
  
 RESPONSE:
 NOT ADDRESSED.
  
 D)OK.
  
 ORIGINAL COMMENT:
 E)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL17330-R4 IS INCOMPLETE.
 MISSING INSTALLATION INSTRUCTIONS. ALSO, NEED TO
 SPECIFY PADDY SIZE.
  
 ORIGINAL COMMENT:
 F)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 RESPONSE:
 SINGLE PLY ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A
 ROOF TILE UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR
 FLAT ROOFS.
  
 ORIGINAL COMMENT:
 H)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT APPROVAL
 SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY ROOF
 SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 REVISE AS REQUIRED AND INCLUDE MISSING PRODUCT
 APPROVALS.
  
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A)OK.
 B)OK.
  
 ORIGINAL COMMENT:
 C)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT. SEE PLANS
 AND REVISE AS REQUIRED. SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NUMBER OF BEDROOMS IS INCORRECT AGAIN. SEE PLANS AND
 REVISE.
  
 D)OK.
 E)OK.
  
 ORIGINAL COMMENT:
 F)CEILING TYPE INFORMATION ON PAGE 1 IS NOT CLEAR.
 CLARIFY WHY ENTERING TILE, SLATE, CONC.?. THIS IS NOT A
 CEILING TYPE. ALSO, NEED TO SPECIFY IF THE CEILING IS
 VENTED OR NOT. THIS NEEDS TO BE COORDINATED WITH THE
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
 NOTE: ARCHITECTURAL PLANS WERE NOT SUBMITTED FOR
 REVIEW. THIS INFORMATION WILL BE REVIEWED WHEN PLANS
 ARE SUBMITTED.
  
 RESPONSE:
 CEILING R-VALUE DOESN'T MATCH PLANS. ENGINEER OF RECORD
 SPECIFIES R20 NOT R25.
  
 G)OK.
 H)OK.
 I)OK.
  
 ORIGINAL COMMENT:
 J)DOORS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED.
 NOTE: KEEP IN MIND THAT DOORS WITH GLAZING NEED TO BE
 ENTERED IN THE GLAZING SECTION NOT IN DOORS.
  
 RESPONSE:
 DOORS ORIENTATION DOESN'T MATCH PLANS.
  
 ORIGINAL COMMENT:
 K)WINDOWS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED: WINDOWS AREA, AND
 OVERHANG DEPTH AND SEPARATION.
  
 RESPONSE:
 WINDOWS ORIENTATION, MATERIAL, AND OVERHANG SEPARATIOON
 DON'T MATCH PLANS. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 L)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 NEW COMMENT:
 M)TYPICALLY THE ATTIC VENT RATIO IS 1/150. ENGINEER
 CERTIFYING THE ENERGY CALCULATIONS SPECIFIES 1/300
 ATTIC VENT RATIO ON PAGE 4. PLANS DON'T SHOW THIS
 VENTILATION RATIO.
 ENGINEER CERTIFYING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL WHEN
 SPECIFYING A VENT RATIO OF 1/300.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-11 Cont ID  
Sent By jgomez Date 2022-08-11 Time 13:45 Rev Time 0.00
Received By jgomez Date 2022-08-11 Time 12:54 Sent To  
Notes
2022-08-10 19:05:41RESIDENTIAL (R3)ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061666
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- UNABLE TO PERFORM REVIEW. MISSING
 STRUCTURAL/ARCHITECTURAL DRAWINGS FOR CONSTRUCTION OF
 PROPOSED ADDITION/ALTERATION. SEC. 107.5.5.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 2- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
 B)WINDOWS AS SHOWN ON PLANS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 F)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 H)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS IS JURISDICTION 604700).
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT. SEE PLANS
 AND REVISE AS REQUIRED. SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 D)FLOOR TYPE SPECIFIED ON PAGE 1 IS INCORRECT. THIS IS
 A SLAB ON GRADE. WHAT IS "BG FLOOR, HEAVY DAMP SOIL, ON
 GR"?. REVISE AS REQUIRED.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E)WALL TYPE ON PAGE 1 IS INCORRECT. THERE IS NOT 2"X4"
 WOOD. SEE PLANS AND REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 F)CEILING TYPE INFORMATION ON PAGE 1 IS NOT CLEAR.
 CLARIFY WHY ENTERING TILE, SLATE, CONC.?. THIS IS NOT A
 CEILING TYPE. ALSO, NEED TO SPECIFY IF THE CEILING IS
 VENTED OR NOT. THIS NEEDS TO BE COORDINATED WITH THE
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
 NOTE: ARCHITECTURAL PLANS WERE NOT SUBMITTED FOR
 REVIEW. THIS INFORMATION WILL BE REVIEWED WHEN PLANS
 ARE SUBMITTED.
  
 G)HOT WATER INFORMATION ON PAGE 1 IS INCORRECT.
 ACCORDING TO PLANS, THE HOT WATER HEATER IS GAS NOT
 ELECTRIC. REVISE AS REQUIRED. SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 H)SPACES INFORMATION ON PAGE 2 IS INCORRECT. THERE IS A
 KITCHEN IN THIS HOUSE. AND, NUMBER OF PEOPLE IS
 TYPICALLY SHOWN NEXT TO THE EACH BEDROOM. REVISE AS
 REQUIRED. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 I)TYPE OF ROOF ON PAGE 2 IS INCORRECT. THIS HOUSE IS
 HIP ROOF NOT GABLE. REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 J)DOORS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED.
 NOTE: KEEP IN MIND THAT DOORS WITH GLAZING NEED TO BE
 ENTERED IN THE GLAZING SECTION NOT IN DOORS.
  
 K)WINDOWS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED: WINDOWS AREA, AND
 OVERHANG DEPTH AND SEPARATION.
  
 L)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-07 Cont ID  
Sent By fgiaquin Date 2022-09-07 Time 21:25 Rev Time 0.00
Received By fgiaquin Date 2022-09-07 Time 21:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-28 Cont ID  
Sent By fgiaquin Date 2022-07-28 Time 20:35 Rev Time 0.00
Received By fgiaquin Date 2022-07-28 Time 19:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2022-09-06 Cont ID  
Sent By rwbrown Date 2022-09-06 Time 13:11 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-09-06 13:11:59NO GAS PLANS WERE SUBMITTED WITH THIS SET OF DRAWINGS.
 A SEPARATE GAS PERMIT IS REQUIRED FOR THE GAS LINES.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By rwbrown Date 2022-07-19 Time 06:02 Rev Time 0.00
Received By rwbrown Date 2022-07-19 Time 06:02 Sent To  
Notes
2022-07-19 06:06:541ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - YOU'VE DETAILED A GAS
 WATER HEATER. ARE YOU CHANGING ONE OUT, INSTALLING A
 NEW WHERE THERE WASN'T ONE, OR INSTALLING A GAS HEATER
 WHERE THERE WAS AN ELECTRIC HEATER. PLEASE INCLUDE
 DETAILS.
  
 2. 2020 FRC G2407.1 - PLEASE SHOW THE COMBUSTION AIR
 CALCS FOR THE GAS WATER HEATER IF NECESSARY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 16:28 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 14:24 Sent To I
Notes
2022-09-26 14:25:10OK. TO APPROV BUILDING WITH PROVISO PER DYLAN BATTLES
 EMAIL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By jgomez Date 2022-09-21 Time 16:35 Rev Time 0.00
Received By jgomez Date 2022-09-02 Time 14:38 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-11 Cont ID  
Sent By jgomez Date 2022-08-11 Time 13:52 Rev Time 0.00
Received By jgomez Date 2022-07-13 Time 08:39 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By dbattles Date 2022-09-21 Time 15:09 Rev Time 0.00
Received By dbattles Date 2022-09-21 Time 15:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-11 Cont ID  
Sent By jgomez Date 2022-08-11 Time 13:50 Rev Time 0.00
Received By jgomez Date 2022-08-11 Time 13:50 Sent To  
Notes
2022-08-11 13:51:07IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 10:12 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-15 Cont ID  
Sent By medwards Date 2022-07-15 Time 14:44 Rev Time 0.00
Received By medwards Date 2022-07-15 Time 14:44 Sent To  
Notes
2022-07-15 14:46:59SHOW THE RETURN IN THE BEDROOMS AND THE ROOM BEHIND THE
 RANGE IN THE KITCHEN. FRC M1602.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By rwbrown Date 2022-09-06 Time 13:12 Rev Time 0.00
Received By rwbrown Date 2022-09-06 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By rwbrown Date 2022-07-19 Time 05:58 Rev Time 0.00
Received By rwbrown Date 2022-07-19 Time 05:54 Sent To  
Notes
2022-07-19 06:01:481ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - YOUR SCOPE DETAILS MOVING
 FIXTURES. PLEASE SHOW AN EXISTING FLOOR PLAN AND A
 PROPOSED.
  
 2. 2020 FRC P3108.1 - THE SHOWER APPEARS TO BE WET
 VENTED BY THE WASHER. ONLY BATHROOM GROUP FIXTURES CAN
 BE USED TO WET VENT OTHER BATHROOM GROUP FIXTURES.
 PLEASE RECONFIGURE THE VENT FOR THE SHOWER.
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 15:50 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 15:49 Sent To  
Notes
2022-09-26 15:51:511- PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED. FLORIDA PRODUCT APPROVAL FL17330-R4 IS
 INCOMPLETE. MISSING INSTALLATION INSTRUCTIONS. ALSO,
 NEED TO SPECIFY PADDY SIZE.
 B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 C)ROOFING UNDERLAYMENT. SINGLE PLY ROOF SYSTEMS
 FL14318-R18 SUBMITTED IS NOT A ROOF TILE UNDERLAYMENT.
 THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 D)HIP & RIDGE METAL SUPPORT TO BE USED.
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT
 APPROVAL SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY
 ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By jgomez Date 2022-09-21 Time 16:34 Rev Time 0.00
Received By jgomez Date 2022-09-21 Time 16:34 Sent To  
Notes
2022-09-21 17:04:24ROOFING REVIEW:
  
 1- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL17330-R4 IS INCOMPLETE.
 MISSING INSTALLATION INSTRUCTIONS. ALSO, NEED TO
 SPECIFY PADDY SIZE.
  
 ORIGINAL COMMENT:
 B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 RESPONSE:
 SINGLE PLY ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A
 ROOF TILE UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR
 FLAT ROOFS.
  
 ORIGINAL COMMENT:
 D)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT APPROVAL
 SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY ROOF
 SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 REVISE AS REQUIRED AND INCLUDE MISSING PRODUCT
 APPROVALS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-08-11 Cont ID  
Sent By jgomez Date 2022-08-11 Time 13:51 Rev Time 0.00
Received By jgomez Date 2022-08-11 Time 13:51 Sent To  
Notes
2022-08-11 13:52:04ROOFING REVIEW
  
 1- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 B)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 D)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-26 Cont ID  
Sent By jgomez Date 2022-09-26 Time 16:05 Rev Time 0.00
Received By jgomez Date 2022-09-26 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By jgomez Date 2022-09-21 Time 16:34 Rev Time 0.00
Received By jgomez Date 2022-09-21 Time 16:34 Sent To  
Notes
2022-09-21 17:01:13SIGNATURE REVIEW
  
 INTERIOR DESIGN DRAWINGS NEED TO BE PROPERLY SIGNED AND
 SEALED BY THE INTERIOR DESIGNER OF RECORD AS REQUIRED
 BY CHAPER 481 F.S. WHEN SUBMITTING THEM FOR PUBLIC
 RECORDS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
2022-09-06 10:13:26MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-04 Cont ID  
Sent By rwbrown Date 2022-08-04 Time 06:13 Rev Time 0.00
Received By rwbrown Date 2022-08-04 Time 06:12 Sent To  
Notes
2022-08-04 06:13:29THE SIGNATURES ARE INVALID. THERE HAVE BEEN CHANGES
 MADE AFTER THE SIGNATURE WAS APPLIED. PLEASE CHECK THE
 PLANS AND RESIGN.
  
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C

Review Stop Z ZONING
Rev No 2 Status P Date 2022-09-13 Cont ID  
Sent By afowlkes Date 2022-09-13 Time 16:04 Rev Time 0.00
Received By afowlkes Date 2022-09-13 Time 16:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By afowlkes Date 2022-07-19 Time 10:00 Rev Time 0.00
Received By afowlkes Date 2022-07-19 Time 10:00 Sent To  
Notes
2022-07-19 10:05:1507/19/22 FAILED
  
 PER THE SCOPE OF WORK, THISPERMIT WILL COVER THE
 EXTENSION OF THE FRONT OF THE HOUSE AND THE ADDITION OF
 AN OUTDOOR PERGOLA. THESE IMPROVEMENTS NEED TO BE SHOWN
 ON A SITE PLAN THAT OUTLINES THE NEW BUILDING
 FOOTPRINT. ADDITIONALLY, IF ANY NEW MECHANICAL
 EQUIPMENT IS BEING LOCATED OUTDOORS, THIS NEEDS TO BE
 SHOWN ON THE SITE PLAN AS WELL.
  
 ALSO, PLEASE PROVIDE A SURVEY OF THE PROPERTY.
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]