Plan Review Details - Permit 22061647
Plan Review Stops For Permit 22061647
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2022-07-07 Cont ID  
Sent By shill Date 2022-07-07 Time 06:04 Rev Time 0.00
Received By shill Date 2022-07-07 Time 06:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-12-09 Cont ID  
Sent By jgomez Date 2022-12-09 Time 19:04 Rev Time 0.00
Received By jgomez Date 2022-12-09 Time 19:04 Sent To  
Notes
2022-12-09 19:05:13BUILDING AUDIT OK. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-11-28 Cont ID  
Sent By jgomez Date 2022-11-28 Time 09:52 Rev Time 0.00
Received By jgomez Date 2022-11-28 Time 09:52 Sent To  
Notes
2022-11-28 09:53:14GENERATOR CONCRETE PAD ENGINEERING FOURTH BUILDING
 AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
  
 PREVIOUS COMMENT:
 1- DRAWING E1 WAS REVISED WITH NEW DRAWING SHEET 1.
 DESIGN CRITERIA NOTE #4 CALLS FOR A STAND TO BE
 FASTENED W/(3) 4"X5/8" NON-CORROSIVE BOLTS. DRAWINGS
 AND SPECIFICATIONS FOR THE PROPOSED STAND WERE NOT
 SUBMITTED. ALSO, PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING HOW THE PROPOSED STAND IS
 FASTENED WITH 3 BOLTS AS SPECIFIED ON DESIGN NOTE #4.
 ALSO, SPECIFY FASTENING OF THE GENERATOR TO THE
 PROPOSED STAND.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NEW COMMENT BASED ON REVISED DRAWING SHEET 1 OF 1
 SUBMITTED:
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE ENGINEERING AS REQUIRED.
 ORIGINAL DRAWING HAD THE CORRECT BUILDING EXPOSURE.
  
 PREVIOUS COMMENT:
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 18:02 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 17:58 Sent To  
Notes
2022-11-18 18:02:57GENERATOR CONCRETE PAD ENGINEERING THIRD BUILDING
 AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
  
 PREVIOUS COMMENT:
 1- DRAWING E1 WAS REVISED WITH NEW DRAWING SHEET 1.
 DESIGN CRITERIA NOTE #4 CALLS FOR A STAND TO BE
 FASTENED W/(3) 4"X5/8" NON-CORROSIVE BOLTS. DRAWINGS
 AND SPECIFICATIONS FOR THE PROPOSED STAND WERE NOT
 SUBMITTED. ALSO, PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING HOW THE PROPOSED STAND IS
 FASTENED WITH 3 BOLTS AS SPECIFIED ON DESIGN NOTE #4.
 ALSO, SPECIFY FASTENING OF THE GENERATOR TO THE
 PROPOSED STAND.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NEW COMMENT BASED ON REVISED DRAWING SHEET 1 OF 1
 SUBMITTED:
 ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE ENGINEERING AS REQUIRED.
 ORIGINAL DRAWING HAD THE CORRECT BUILDING EXPOSURE.
  
 PREVIOUS COMMENT:
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-19 Cont ID  
Sent By jgomez Date 2022-09-19 Time 10:53 Rev Time 0.00
Received By jgomez Date 2022-09-19 Time 09:56 Sent To  
Notes
2022-09-19 10:57:37GENERATOR CONCRETE PAD ENGINEERING SECOND BUILDING
 AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
 GENERATOR CONCRETE PAD ENGINEERING SHEET E1:
 ORIGINAL COMMENT:
 A)DESIGN CRITERIA NOTES SPECIFY "GENERATOR TO BE
 FASTENED WITH (3)5"X1/4" NON-CORROSIVE ZINC-PLATED
 BOLTS W/1 1/8" WASHERS OR EQ".
 ENGINEER OF RECORD DOESN'T PROVIDE DETAIL SHOWING
 LOCATION OF THE BOLTS ON THE CONCRETE SLAB.
 SPECIFIED ANCHOR NEEDS TO BE SPECIFIC. SPECIFYING "OR
 EQ." TO BE USED AS A SUBSTITUTE FOR THIS SPECIFIC
 ANCHOR IS NOT ALLOWED BY SEC. 107.2.1 CITY AMENDMENTS.
 REVISE DESIGN CRITERIA NOTES AND CONCRETE SLAB DETAIL
 AS REQUIRED. CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DRAWING E1 WAS REVISED WITH NEW DRAWING SHEET 1. DESIGN
 CRITERIA NOTE #4 CALLS FOR A STAND TO BE FASTENED W/(3)
 4"X5/8" NON-CORROSIVE BOLTS. DRAWINGS AND
 SPECIFICATIONS FOR THE PROPOSED STAND WERE NOT
 SUBMITTED. ALSO, PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING HOW THE PROPOSED STAND IS
 FASTENED WITH 3 BOLTS AS SPECIFIED ON DESIGN NOTE #4.
 ALSO, SPECIFY FASTENING OF THE GENERATOR TO THE
 PROPOSED STAND.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 B) THE WEIGHT AND DIMENSIONS OF THE GENERATOR SPECIFIED
 ON THE DESIGN CALCULATIONS DOESN'T MATCH THE
 INFORMATION OF THE GENERATOR SPECS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. THE INFORMATION SUBMITTED DOESN'T MATCH
 THE INFORMATION OF THE GENERATOR SPECS SUBMITTED.
 INFORMATION PROVIDED IS FOR THE 24KW GENERATOR NOT FOR
 THE 22KW GENERATOR. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By jgomez Date 2022-08-19 Time 15:54 Rev Time 0.00
Received By jgomez Date 2022-08-19 Time 14:32 Sent To  
Notes
2022-08-19 16:46:45GENERATOR CONCRETE PAD ENGINEERING BUILDING AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
 GENERATOR CONCRETE PAD ENGINEERING SHEET E1:
 A) DESIGN CRITERIA NOTES SPECIFY "GENERATOR TO BE
 FASTENED WITH (3)5"X1/4" NON-CORROSIVE ZINC-PLATED
 BOLTS W/1 1/8" WASHERS OR EQ".
 ENGINEER OF RECORD DOESN'T PROVIDE DETAIL SHOWING
 LOCATION OF THE BOLTS ON THE CONCRETE SLAB.
 SPECIFIED ANCHOR NEEDS TO BE SPECIFIC. SPECIFYING "OR
 EQ." TO BE USED AS A SUBSTITUTE FOR THIS SPECIFIC
 ANCHOR IS NOT ALLOWED BY SEC. 107.2.1 CITY AMENDMENTS.
 REVISE DESIGN CRITERIA NOTES AND CONCRETE SLAB DETAIL
 AS REQUIRED. CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)THE WEIGHT AND DIMENSIONS OF THE GENERATOR SPECIFIED
 ON THE DESIGN CALCULATIONS DOESN'T MATCH THE
 INFORMATION OF THE GENERATOR SPECS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS AND
 SEC. R301.1 FBC-RESIDENTIAL.
  
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-22 Cont ID  
Sent By fgiaquin Date 2022-08-22 Time 08:43 Rev Time 0.00
Received By fgiaquin Date 2022-08-19 Time 21:13 Sent To  
Notes
2022-08-22 08:43:19AUDIT PASSED

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-09-22 Cont ID  
Sent By ccole Date 2022-09-22 Time 11:10 Rev Time 0.00
Received By ccole Date 2022-09-22 Time 10:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-08-15 Cont ID  
Sent By ccole Date 2022-08-15 Time 15:27 Rev Time 0.00
Received By ccole Date 2022-08-15 Time 14:40 Sent To  
Notes
2022-08-15 15:27:591ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22061647
 8/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: THE RISER DRAWING IS INCOMPLETE BECAUSE
 IT DOES NOT SHOW THE PREVIOUS LOW PRESSURE PIPING AND
 APPLIANCES APPROVED UNDER PERMIT 19051480. WHEN NEW GAS
 PIPING AND APPLIANCES ARE ADDED TO AN EXISTING SYSTEM A
 COMPLETE RISER IS REQUIRED IN ACCORDANCE WITH SECS.
 G2412.3 & G2412.4 FBC RES. PLEASE REVISE THE RISER TO
 SHOW:
 A) TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL
 APPLIANCE BTU LOADS.
 B) TYPES AND SIZES OF PIPING.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS AND INLET AND OUTLET
 PRESSURES AT REGULATORS.
 F) LOCATIONS AND TYPES OF PIPE SLEEVES.
 G) PIPE SIZING TABLES.
  
 2) SURVEY: THE SURVEY INDICATES CONNECT GENERATOR TO
 EXISTING NG, THE RISER SHOWS NEW PIPING FROM THE METER-
 PLEASE CORRECT PER SEC. 107.2.1 WPB.
  
 3) SURVEY: THE GENERATOR SHALL BE LOCATED A MINIMUM OF
 10 FT. FROM AIR INTAKES INTO THE BUILDING- SEC.
 R303.5.1 FBC RES. PLEASE CORRECT THE NOTE INDICATING 5
 FT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2022-12-13 Cont ID  
Sent By jgomez Date 2022-12-13 Time 16:50 Rev Time 0.00
Received By jgomez Date 2022-12-13 Time 16:42 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2022-12-12 Cont ID  
Sent By jgomez Date 2022-12-12 Time 09:02 Rev Time 0.00
Received By jgomez Date 2022-12-12 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2022-12-08 Cont ID  
Sent By jgomez Date 2022-12-08 Time 16:18 Rev Time 0.00
Received By jgomez Date 2022-12-08 Time 14:48 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 13 Status F Date 2022-12-07 Cont ID  
Sent By jgomez Date 2022-12-07 Time 09:33 Rev Time 0.00
Received By jgomez Date 2022-12-05 Time 09:52 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 16:51 Rev Time 0.00
Received By jgomez Date 2022-12-01 Time 15:49 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2022-11-28 Cont ID  
Sent By jgomez Date 2022-11-28 Time 09:56 Rev Time 0.00
Received By jgomez Date 2022-11-21 Time 09:17 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 18:25 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 17:51 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2022-11-14 Cont ID  
Sent By jgomez Date 2022-11-14 Time 18:16 Rev Time 0.00
Received By jgomez Date 2022-11-14 Time 10:23 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2022-11-07 Cont ID  
Sent By jgomez Date 2022-11-07 Time 13:14 Rev Time 0.00
Received By jgomez Date 2022-11-04 Time 16:48 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2022-09-22 Time   Rev Time 0.00
Received By lmarchan Date 2022-09-06 Time 07:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 07:18 Rev Time 0.00
Received By shill Date 2022-08-29 Time 07:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-08-22 Cont ID  
Sent By fgiaquin Date 2022-08-22 Time 08:43 Rev Time 0.00
Received By fgiaquin Date 2022-08-11 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-11 Cont ID  
Sent By lmarchan Date 2022-08-11 Time 09:38 Rev Time 0.00
Received By lmarchan Date 2022-08-02 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-02 Cont ID  
Sent By pvalenti Date 2022-08-02 Time 07:24 Rev Time 0.00
Received By pvalenti Date 2022-07-28 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-27 Cont ID  
Sent By pvalenti Date 2022-07-27 Time 08:56 Rev Time 0.00
Received By pvalenti Date 2022-07-25 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-11 Cont ID  
Sent By lmarchan Date 2022-07-11 Time 09:25 Rev Time 0.00
Received By jleahy Date 2022-07-06 Time 05:07 Sent To  
Notes
2022-07-07 06:05:10AUDIT - B,E,G,P AFTER ZONING
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-09-22 Cont ID  
Sent By ccole Date 2022-09-22 Time 10:48 Rev Time 0.00
Received By ccole Date 2022-09-22 Time 10:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-08-15 Cont ID  
Sent By rmcdouga Date 2022-08-15 Time 14:59 Rev Time 0.00
Received By ccole Date 2022-08-15 Time 14:40 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 15 Status P Date 2022-12-09 Cont ID  
Sent By jgomez Date 2022-12-09 Time 19:04 Rev Time 0.00
Received By jgomez Date 2022-12-09 Time 17:48 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 14 Status F Date 2022-12-08 Cont ID  
Sent By jgomez Date 2022-12-08 Time 15:11 Rev Time 0.00
Received By jgomez Date 2022-12-08 Time 15:07 Sent To  
Notes
2022-12-08 15:18:09PRIVATE PROVIDER
 SEC. 553.791 F.S.
  
 PREVIOUS COMMENT:
 1- PLAN REVIEWER WHO REVIEWED AND STAMPED THE REVISED
 PAD ENGINEERING SHEET 1 OF 1 FOR CODE COMPLIANCE IS NOT
 THE SAME PLAN REVIEWER LISTED IN THE REVISED PRIVATE
 PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT. REVISE AS
 REQUIRED TO MATCH.
 (NOTE: CREDENTIALS FOR PERSON REVIEWING THE PAD
 ENGINEERING WERE NOT SUBMITTED IN THE INITIAL PRIVATE
 PROVIDER APPROVAL PACKAGE).
  
 RESPONSE:
 REVISED PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT LISTS
 THE PLAN REVIEWER WHO REVIEWED THE PAD ENGINEERING
 DRAWING. CREDENTIALS FOR MARVIN DRYDEN WERE NOT
 SUBMITTED IN THE INITIAL PRIVATE PROVIDER APPROVAL
 PACKAGE. NEED TO PROVIDE THE CREDENTIALS FOR THIS NEW
 PLAN REVIEWER.
  
  
 NOTE:
 PAD ENGINEERING SHEET 1 OF 1 ARE COPIES OF ENGINEER'S
 DIGITAL SIGNATURE. DIGITAL SIGNATURE CANNOT BE PRINTED.
 SUBMIT DRAWING WITH VERIFIABLE DIGITAL SIGNATURE TO
 AVOID DELAYS.
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 13 Status F Date 2022-12-07 Cont ID  
Sent By jgomez Date 2022-12-07 Time 09:26 Rev Time 0.00
Received By jgomez Date 2022-12-07 Time 08:36 Sent To  
Notes
2022-12-07 09:32:54PRIVATE PROVIDER
 SEC. 553.791 F.S.
  
 1- PLAN REVIEWER WHO REVIEWED AND STAMPED THE REVISED
 PAD ENGINEERING SHEET 1 OF 1 FOR CODE COMPLIANCE IS NOT
 THE SAME PLAN REVIEWER LISTED IN THE REVISED PRIVATE
 PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT. REVISE AS
 REQUIRED TO MATCH.
 (NOTE: CREDENTIALS FOR PERSON REVIEWING THE PAD
 ENGINEERING WERE NOT SUBMITTED IN THE INITIAL PRIVATE
 PROVIDER APPROVAL PACKAGE).
  
  
 NOTE:
 PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT AND
 PAD ENGINEERING SHEET 1 OF 1 ARE COPIES OF ENGINEER'S
 DIGITAL SIGNATURE. DIGITAL SIGNATURE CAN NOT BE
 PRINTED. SUBMIT THEM WITH VERIFIABLE DIGITAL SIGNATURE
 TO AVOID DELAYS.
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 12 Status F Date 2022-12-02 Cont ID  
Sent By jgomez Date 2022-12-02 Time 16:48 Rev Time 0.00
Received By jgomez Date 2022-12-02 Time 16:46 Sent To  
Notes
2022-12-02 16:48:04PRIVATE PROVIDER
 SEC. 553.791 F.S.
  
 1- THERE IS NOT REVISED PRIVATE PROVIDER PLAN REVIEW
 COMPLIANCE AFFIDAVIT SUBMITTED. AFFIDAVIT NEEDS TO BE
 REVISED TO REFLECT THE REVISED PAD ENGINEERING.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 11 Status P Date 2022-11-28 Cont ID  
Sent By jgomez Date 2022-11-28 Time 09:52 Rev Time 0.00
Received By jgomez Date 2022-11-28 Time 09:47 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 10 Status P Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 17:58 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 17:51 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 9 Status F Date 2022-11-14 Cont ID  
Sent By jgomez Date 2022-11-14 Time 17:52 Rev Time 0.00
Received By jgomez Date 2022-11-14 Time 17:51 Sent To  
Notes
2022-11-14 17:52:311- THERE IS NOT REVISED PRIVATE PROVIDER PLAN REVIEW
 COMPLIANCE AFFIDAVIT SUBMITTED. AFFIDAVIT NEEDS TO BE
 REVISED TO REFLECT THE REVISED PAD ENGINEERING.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 8 Status F Date 2022-11-07 Cont ID  
Sent By jgomez Date 2022-11-07 Time 13:13 Rev Time 0.00
Received By jgomez Date 2022-11-07 Time 13:10 Sent To  
Notes
2022-11-07 13:14:011- THERE IS NOT REVISED PRIVATE PROVIDER PLAN REVIEW
 COMPLIANCE AFFIDAVIT SUBMITTED.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 7 Status P Date 2022-09-07 Cont ID  
Sent By mpeterso Date 2022-09-07 Time 13:32 Rev Time 0.00
Received By mpeterso Date 2022-09-07 Time 13:32 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status F Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 07:12 Rev Time 0.00
Received By shill Date 2022-08-29 Time 07:12 Sent To  
Notes
2022-08-29 07:18:47FS553.791, THIS PROJECT IS PRIVATE PROVIDER PLAN REVIEW
 AND INSPECTIONS.
  
 THE AFFIDAVIT WAS SIGNED 7/27/22, BUT NEW PAD
 ENGINEERING WAS SUBMITTED WHICH WAS DIGITALLY SIGNED ON
 8/2/22. THE NEW PAD ENGINEERING HAS A STAMP INDICATING
 IT WAS REVIEWED, BUT A NEW AFFIDAVIT WAS NOT SUBMITTED.
 THE AFFIDAVIT SHOULD INDICATE WHICH VERSION OF THE PAD
 ENGINEERING WAS REVIEWED (ENGINEER NAME, DATE PREPARED
 OR DATE SIGNED).
  
 THERE ARE NOW TWO DIFFERENT GENERATOR PAD ENGINEERING
 DOCUMENTS IN THE SUBMITTAL. PLEASE EMAIL
 [email protected] AND REQUEST THAT THE ONE THAT
 WAS SUPERSEDED BE LOCKED.
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-08-15 Cont ID  
Sent By pvalenti Date 2022-08-15 Time 09:24 Rev Time 0.00
Received By pvalenti Date 2022-08-15 Time 08:56 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-08-10 Cont ID  
Sent By rmcdouga Date 2022-08-10 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2022-08-10 Time 16:50 Sent To  
Notes
2022-08-10 17:20:31THE PRIVATE PROVIDER PLAN COMPLIANCE AFFIDAVITS BOTH
 LIST PAD ENGINEERING PREPARED BY TIMOTHY CONWAY, P.E.
 IT APPEARS THAT THIS DOCUMENT WAS NOT UPLOADED. I COULD
 NOT LOCATE THE ENGINEERED GENERATOR PAD DRAWING.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2022-08-01 Cont ID  
Sent By rmcdouga Date 2022-08-01 Time 17:04 Rev Time 0.00
Received By rmcdouga Date 2022-08-01 Time 17:04 Sent To  
Notes
2022-08-01 17:09:41NO NEW DOCUMENTS WERE SUBMITTED AFTER THE LAST REVIEW
 ON 7/27/2022. SEE PREVIOUS COMMENTS.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By pvalenti Date 2022-07-27 Time 07:47 Rev Time 0.00
Received By pvalenti Date 2022-07-26 Time 14:04 Sent To  
Notes
2022-07-27 08:53:39PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 PRIVATE PROVIDER AFFIDAVIT REVIEW DENIED:
  
 PROVIDE AN AFFIDAVIT THAT IS CLEAR AS TO WHAT HAS BEEN
 SUBMITTED. THE AFFIDAVIT SHEET NEEDS TO INCLUDE, FOR
 EACH DOCUMENT SUBMITTED, THE FOLLOWING: NAME OF
 DOCUMENT, DATE OF DOCUMENT, AND NAME OF DESIGNER.
 THE AFFIDAVIT SHEET DOES NOT NEED TO INCLUDE THE NOC
 AND AFFIDAVIT FILES BUT DOES NEED TO INCLUDE THE
 DOCUMENTS SUCH AS THE FOLLOWING:
  
 1.) ELECTRIC LINE DIAGRAM
 2.) GAS DIAGRAM
 3.) ELECTRIC CALCS & WIRE CUT SHEET
 4.) NEXGEN SURVEY
 5.) GENERAL SPECS
 6.) GAS REGULATOR SPECS

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By rgathrig Date 2022-07-11 Time 07:06 Rev Time 0.00
Received By shill Date 2022-07-11 Time 07:06 Sent To  
Notes
2022-07-11 07:16:18FS553.791, THE AFFIDAVIT SHOULD IDENTIFY THE DESIGN
 DOCUMENTS. FOR INSTANCE, THE DOCUMENT REFERRED TO AS
 "ELECTRIC LINE DIAGRAM" SHOULD REFER TO THE DOCUMENT,
 DATE OF THE DOCUMENT, AND DESIGNER - "ELECTRICAL LINE
 DIAGRAM PREPARED BY DALE JAROSZ, EC, DATED 6/10/2022".
  
 [email protected]
  
  
  
2022-07-07 17:14:05PRIVATE PROVIDER REVIEW FOR INSURANCE AND RESUMES ONLY.
 DOCUMENTS SUBMITTED COMPLY WITH REQUIREMENTS AND OK
 THIS WAS NOT A REVIEW OF CODE COMPLIANCE AFFIDAVITS
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 9 Status P Date 2022-12-13 Cont ID  
Sent By jgomez Date 2022-12-13 Time 16:52 Rev Time 0.00
Received By jgomez Date 2022-12-13 Time 16:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 8 Status F Date 2022-12-12 Cont ID  
Sent By jgomez Date 2022-12-12 Time 09:02 Rev Time 0.00
Received By jgomez Date 2022-12-12 Time 09:02 Sent To  
Notes
2022-12-12 09:02:48SIGNATURE REVIEW
  
 1- PRIVATE PROVIDER AFFIDAVIT HAVE A COPY OF A DIGITAL
 SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT AFFIDAVIT ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status F Date 2022-12-09 Cont ID  
Sent By jgomez Date 2022-12-09 Time 19:05 Rev Time 0.00
Received By jgomez Date 2022-12-09 Time 17:48 Sent To  
Notes
2022-12-09 19:05:53SIGNATURE REVIEW
  
 1- PRIVATE PROVIDER AFFIDAVIT HAVE A COPY OF A DIGITAL
 SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT AFFIDAVIT ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2022-11-28 Cont ID  
Sent By jgomez Date 2022-11-28 Time 09:56 Rev Time 0.00
Received By jgomez Date 2022-11-28 Time 09:53 Sent To  
Notes
2022-11-28 09:56:29SIGNATURE REVIEW
  
 1- ENGINEER DRAWING SHEET 1 OF 1 HAVE A COPY OF A
 DIGITAL SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 2- PRIVATE PROVIDER AFFIDAVIT HAVE A COPY OF A DIGITAL
 SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT AFFIDAVIT ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 18:21 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 18:21 Sent To  
Notes
2022-11-18 18:21:40SIGNATURE REVIEW
  
 1- ENGINEER DRAWING SHEET 1 OF 1 HAVE A COPY OF A
 DIGITAL SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 2- PRIVATE PROVIDER AFFIDAVIT HAVE A COPY OF A DIGITAL
 SIGNATURE. ALL DRAWINGS/DOCUMENTS NEED TO HAVE
 VERIFIABLE DIGITAL SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NEED TO SUBMIT AFFIDAVIT ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-11-18 Cont ID  
Sent By jgomez Date 2022-11-18 Time 18:15 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 18:15 Sent To  
Notes
2022-11-18 18:16:02PREVIOUS COMMENT:
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By jgomez Date 2022-09-19 Time 10:58 Rev Time 0.00
Received By jgomez Date 2022-09-19 Time 10:58 Sent To  
Notes
2022-09-19 10:58:55SECOND SIGNATURE REVIEW
  
 1- DIGITAL SIGNATURE
 1- ENGINEER DRAWING SHEET 1 HAVE A COPY OF A DIGITAL
 SIGNATURE THAT CAN NOT BE VERIFIED. ALL
 DRAWINGS/DOCUMENTS NEED TO HAVE VERIFIABLE DIGITAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-19 Cont ID  
Sent By jgomez Date 2022-08-19 Time 16:46 Rev Time 0.00
Received By jgomez Date 2022-08-19 Time 15:02 Sent To  
Notes
2022-08-19 16:47:58SIGNATURE REVIEW
  
 1- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE DIGITAL SEAL/SIGNATURE AS REQUIRED
 BY CHAPTER 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS
 FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-11 Cont ID  
Sent By jleahy Date 2022-07-11 Time 09:25 Rev Time 0.00
Received By jleahy Date 2022-07-11 Time 09:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By asangele Date 2022-07-08 Time 11:17 Rev Time 0.00
Received By asangele Date 2022-07-08 Time 11:17 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved