| 2022-08-10 12:42:10 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22061636 |
| | ADD: 2751 S. DIXIE HWY. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: [email protected] PAUL NIELSEN |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 10TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET. THE COVERSHEET AND TITLEBLOCK BOTH REFER |
| | TO THE ADDRESS OF 2751 S DIXIE HWY SUITE JR # 4. THE |
| | SUITE NUMBER DOES NOT FIT OUR ADDRESSING SCHEME, YOU |
| | CAN NOT RECOGNIZE WHICH FLOOR THIS TENANT SPACE IS ON, |
| | THIS IS A MULTISTORY BUILDING. 2020 FBC-B 501.2 ADDRESS |
| | IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE |
| | PROVIDED WITH APPROVED ADDRESS IDENTIFICATION. |
| | |
| | 2) SHEET A100 DEMOLITION: |
| | 2A) THE DEMOLITION SHEET A100 AND PROPOSED WORK ON |
| | SHEET A101 FLOOR PLAN ARE THE SAME PLAN, PLEASE PROVIDE |
| | ADDITIONAL INFORMATION. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2B) THERE ARE 2 DEMOLITION NOTES FOR STOREFRONT |
| | WINDOWS. NOTE ONE STATES TO REMOVE AND REUSE EXISTING |
| | STOREFRONT. 2020 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | SECTION 104.9.1 USED MATERIAL & EQUIPMENT. THE USE OF |
| | USED, RECYCLED OR RECLAIMED MATERIALS WHICH MEET THE |
| | REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS |
| | PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE |
| | REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL. PLEASE |
| | PROVIDE DOCUMENTATION HOW THE USED WINDOWS WILL MEET |
| | THE WIND DESIGN CRITERIA OF THE CURRENT CODE AND LARGE |
| | MISSILE TESTING FOR THE GLAZING. |
| | THE OTHER ISSUE WITH USED WINDOWS IS WHO IS GOING TO |
| | CERTIFY ANCHORAGE VS WIND PRESSURE PER PSF, TYPE, |
| | SPACING OF ANCHOR, LENGTH OF ANCHOR, GLAZING TYPE |
| | TRIBUTARY AREA OF GLAZING VERSES VASD DESIGN PRESSURES. |
| | WHO IS GOING TO CERTIFY, ARCHITECT OR STRUCTURAL |
| | ENGINEER? |
| | |
| | 2C) PLEASE PROVIDE WHY THE USE OF USED WINDOW/ GLAZING |
| | WHEN ON THE COVERSHEET THEY LIST STOREFRONT, YKK/ AP |
| | YHS FL 14218.5? ADDITIONAL INFORMATION IS REQUIRED. |
| | ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 3) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS |
| | AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(C) PANEL WALLS: STOREFRONTS |
| | |
| | 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE |
| | OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6) A501 DETAIL B2 SHOWS THE TOILET TISSUE DISPENSER TO |
| | COMPLY WITH ICC SECTION 309.4. PLEASE NOTE FLORIDA USES |
| | THE 2020 FBC-ACCESSIBILITY CODE AND THE TOILET PAPER |
| | DISPENSERS MUST MEET SECTION 604.7. THE TOILET PAPER |
| | DISPENSER SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES |
| | MINIMUM TO 9 INCHES MAXIMUM IN FRONT OF THE WATER |
| | CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER. NOT |
| | DIMENSIONED OR SHOWN THAT WAY. |
| | THE OUTLET OF THE DISPENSER SHALL BE 15 INCHES MINIMUM |
| | AND 48 INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL |
| | NOT BE LOCATED BEHIND THE GRAB BARS. |
| | |
| | 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |