Plan Review Details - Permit 22061627
Plan Review Stops For Permit 22061627
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By rmcdouga Date 2022-12-06 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2022-12-06 Time 10:50 Sent To  
Notes
2022-12-06 10:52:09ASBESTOS LETTER IS FOR THE SEPARATE DEMO PERMIT FOR
 THIS PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 13:40 Sent To  
Notes
2022-08-18 14:12:22PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-12-06 Cont ID  
Sent By rmcdouga Date 2022-12-06 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2022-12-06 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 13:40 Sent To  
Notes
2022-08-18 16:02:19PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE VALUE SPECIFIED ON THE APPLICATION OF $2500.00
 IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON THE DRAWINGS.
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF FBC 109.3 BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SPECIFY THE BUILDING DATA ON THE PLANS. CONSTRUCTION
 TYPE, OCCUPANCY TYPE, SPRINKLERED OR UN-SPRINKLERED,
 OCCUPANT LOAD, NUMBER OF STORIES AND SQUARE FOOT AREA.
 FBC AMENDMENTS 107.2.1
  
 3) SPECIFY THE LEVEL OF ALTERATION FOR THE WORK PER FBC
 EXISTING BUILDING SECTION 601.
  
 4) IT APPEARS THAT THERE WILL BE RAMPS TO THE ELEVATED
 AREAS. HOWEVER, NO DETAILS HAVE BEEN PROVIDED FOR THE
 RAMPS. SHOW COMPLIANCE WITH FBC ACCESSIBILITY SECTION
 201.1.1.
  
 5) PROVIDE DETAILS FOR EACH OF THE PROPOSED RAMPS TO
 SHOW COMPLIANCE WITH FBC ACCESSIBILITY SECTION 405.
  
 6) PROVIDE DETAILS FOR THE STAIRS AT THESE PROPOSED
 ELEVATED AREAS. FBC ACCESSIBILITY SECTION 504
  
 7) SUBMIT STRUCTURAL DRAWINGS FOR THE ELEVATED STAGE,
 DJ BOOTH AND VIP AREAS. SPECIFY THE FLOOR LIVE LOADS
 FOR THESE AREAS. FBC AMENDMENTS 107.2.1 AND FBC
 1603.1.1
  
 8) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
 PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF
 THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-12-07 Cont ID  
Sent By fgiaquin Date 2022-12-07 Time 21:35 Rev Time 0.00
Received By fgiaquin Date 2022-12-07 Time 18:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By fgiaquin Date 2022-08-03 Time 23:38 Rev Time 0.00
Received By fgiaquin Date 2022-08-03 Time 21:07 Sent To  
Notes
2022-08-03 23:38:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE COST
 BREAKDOWN WITH ACCURATE VALUE FOR PROPOSED WORK. FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By clfranci Date 2022-11-08 Time   Rev Time 0.00
Received By clfranci Date 2022-11-08 Time   Sent To  
Notes
2022-11-08 15:13:44 
 THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-22 Cont ID  
Sent By clfranci Date 2022-07-22 Time   Rev Time 0.00
Received By clfranci Date 2022-07-22 Time   Sent To  
Notes
2022-07-22 14:20:11THIS PLAN WAS REVIEWED AND APPROVED BY CAITLIN L
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-07 Cont ID  
Sent By fgiaquin Date 2022-12-07 Time 21:35 Rev Time 0.00
Received By fgiaquin Date 2022-11-04 Time 17:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2022-07-20 Time 09:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 14:28 Sent To  
Notes
2022-08-18 14:29:07NO CHANGE OF OCCUPANCY OR INCREASE IN AREA.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-11-17 Cont ID  
Sent By rwbrown Date 2022-11-17 Time 10:15 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 14:29 Sent To  
Notes
2022-08-18 14:42:24THE DIGITAL SIGNATURE ON THE ARCHITECTURAL AND LIFE
 SAFETY PLANS READS INVALID AND SHOWS THAT THE DRAWINGS
 HAVE BEEN ALTERED. THE DIGITAL SIGNATURE ON THE
 ELECTRICAL PLANS ARE GOOD.