Plan Review Details - Permit 22061602
Plan Review Stops For Permit 22061602
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-29 Cont ID  
Sent By shill Date 2022-10-29 Time 13:45 Rev Time 0.00
Received By shill Date 2022-10-29 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 13:00 Rev Time 0.00
Received By shill Date 2022-09-01 Time 13:00 Sent To  
Notes
2022-09-01 13:00:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS471, THIS ARCHITECT HAS A DIGITAL SIGNATURE.
 UPLOAD DIGITALLY SIGNED PLANS FOR REVIEW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-24 Cont ID  
Sent By shill Date 2022-07-24 Time 09:56 Rev Time 0.00
Received By shill Date 2022-07-24 Time 09:56 Sent To  
Notes
2022-07-24 09:57:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS471, THIS ARCHITECT HAS A DIGITAL SIGNATURE.
 UPLOAD DIGITALLY SIGNED PLANS FOR REVIEW.
  
 1. FBC 107, PROVIDE ENERGY CALCS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-10-18 Cont ID  
Sent By jleahy Date 2022-10-18 Time 13:11 Rev Time 0.00
Received By jleahy Date 2022-10-18 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 16:41 Rev Time 0.00
Received By jleahy Date 2022-09-19 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-15 Cont ID  
Sent By jleahy Date 2022-07-15 Time 12:39 Rev Time 0.00
Received By jleahy Date 2022-07-15 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-29 Cont ID  
Sent By shill Date 2022-10-29 Time 13:46 Rev Time 0.00
Received By shill Date 2022-09-30 Time 09:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 16:41 Rev Time 0.00
Received By jleahy Date 2022-08-29 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-01 Cont ID  
Sent By aoliver Date 2022-08-08 Time 07:57 Rev Time 0.00
Received By aoliver Date 2022-07-01 Time 13:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-12-01 Cont ID  
Sent By lmarchan Date 2022-12-01 Time 09:52 Rev Time 0.00
Received By lmarchan Date 2022-11-28 Time 08:52 Sent To  
Notes
2022-12-01 09:52:37RECEIPT MU-2022-053207 - $0.00 DUE. LEM
2022-11-28 08:53:0111/28/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-24 Cont ID  
Sent By shill Date 2022-07-24 Time 10:00 Rev Time 0.00
Received By shill Date 2022-07-24 Time 10:00 Sent To  
Notes
2022-07-24 10:00:54PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 06:13 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 06:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-30 Cont ID  
Sent By medwards Date 2022-08-30 Time 14:52 Rev Time 0.00
Received By medwards Date 2022-08-30 Time 14:52 Sent To  
Notes
2022-08-30 14:53:06ADDRESS COMMENT NUMBER 3 OF PREVIOS REVIEW:
  
 3) PROVIDE A DETAIL OF THE ANCHORAGE OF THE CONDENSING
 UNIT. FRC M1307.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-05 Cont ID  
Sent By medwards Date 2022-07-05 Time 11:11 Rev Time 0.00
Received By medwards Date 2022-07-05 Time 11:11 Sent To  
Notes
2022-07-05 11:11:261ST REVIEW FMC
 PERMIT: 22061602
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FBC 101.5.1.1.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC R403.7.1
  
 3) PROVIDE A DETAIL OF THE ANCHORAGE OF THE CONDENSING
 UNIT. FRC M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-07-05 Cont ID  
Sent By rwbrown Date 2022-07-05 Time 10:57 Rev Time 0.00
Received By rwbrown Date 2022-07-05 Time 10:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-03 Cont ID  
Sent By medwards Date 2022-10-03 Time 06:14 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 06:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-30 Cont ID  
Sent By medwards Date 2022-08-30 Time 14:53 Rev Time 0.00
Received By medwards Date 2022-08-30 Time 14:53 Sent To  
Notes
2022-08-30 14:54:18ADDRESS PREVIOUS COMMENTS BELOW:
  
 SIGNATURE REVIEW:
  
 1- DRAWINGS C.1, 1.1 AND 2.1 HAVE A COPY OF THE
 ARCHITECT'S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE
 NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A
 LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL VERIFIABLE
 DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD AS
 REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 ORIGINAL DIGITAL SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-01 Cont ID  
Sent By jgomez Date 2022-07-01 Time 18:59 Rev Time 0.00
Received By jgomez Date 2022-07-01 Time 18:50 Sent To  
Notes
2022-07-01 19:03:53SIGNATURE REVIEW:
  
 1- DRAWINGS C.1, 1.1 AND 2.1 HAVE A COPY OF THE
 ARCHITECT'S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE
 NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A
 LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL VERIFIABLE
 DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD AS
 REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 ORIGINAL DIGITAL SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-10-11 Cont ID  
Sent By afowlkes Date 2022-10-11 Time 15:50 Rev Time 0.00
Received By afowlkes Date 2022-10-11 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-09-02 Cont ID  
Sent By afowlkes Date 2022-09-02 Time 10:57 Rev Time 0.00
Received By afowlkes Date 2022-09-02 Time 10:57 Sent To  
Notes
2022-09-02 10:59:0609/02/22 FAILED- NEED TO KNOW HOW FAR THE NEW MINI
 SPLIT UNIT IS FROM THE PROPERTY LINE. SHOW THE UNIT ON
 A SURVEY OF THE PROPERTY SO I CAN CONFIRM IT WILL NOT
 PROTRUDE MORE THAN 4 FT INTO ANY SETBACK.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-29 Cont ID  
Sent By afowlkes Date 2022-07-29 Time 10:56 Rev Time 0.00
Received By afowlkes Date 2022-07-29 Time 10:56 Sent To  
Notes
2022-07-29 11:03:2607/29/22 FAILED
  
 NEED TO PROVIDE A PROPOSED FLOOR PLAN. ESSENTIALLY I
 NEED TO KNOW WHAT THE GARAGE WILL BE CONVERTED INTO.
  
 THE ELECTRICAL PLAN SHOWS A NEW MINI SPLIT UNIT. PLEASE
 PROVIDE A SURVEY OF THE PROPERTY WITH THIS UNIT SHOWN
 ON IT SO ICAN DETERMINE IF IT MEETS SETBACK
 REQUIREMENTS. PER CITY CODE, MECHANICAL EQUIPMENT
 CANNOT PROTRUDE MORE THAN 4 FT INTO ANY SETBACK.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431