Plan Review Details - Permit 22061550
Plan Review Stops For Permit 22061550
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By cpuell Date 2022-08-10 Time 14:33 Rev Time 0.00
Received By cpuell Date 2022-08-10 Time 14:33 Sent To  
Notes
2022-08-10 14:35:19THE NORTHERN PARCEL IS BEING REVIEWED UNDER PERMIT
 22010834. FOR THE SOUTHERN PARCEL THE 6 TENANT SPACES
 WILL BE IN THE SOUTHERN PARCEL, GIVEN THE ADDRESSES OF
 2404, 2406, 2408, 2410, 2412 AND 2414 FLORIDA AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-07-14 Cont ID  
Sent By cpuell Date 2022-07-14 Time 17:07 Rev Time 0.00
Received By cpuell Date 2022-07-14 Time 17:07 Sent To  
Notes
2022-07-14 17:13:24SCOPE OF WORK IS FOR TWO DIFFERENT PARCELS
 74434328080050010 AND 74434328080060010, A SECONDARY
 PERMIT WILL NEED TO BE APPLIED FOR THE SECOND PARCEL.
 CURRENT ACTIVE ADDRESSES FOR 74434328080050010 2350
 FLORIDA AVE (PRIMARY) AND 74434328080060010 2406, 2408
 AND 2414 FLORIDA AVE, TODISCUSS ADDRESSING ISSUES
 PLEASE COTACT [email protected] OR CALL
 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-09-30 Cont ID  
Sent By dbattles Date 2022-09-30 Time 16:32 Rev Time 0.00
Received By dbattles Date 2022-09-30 Time 16:32 Sent To  
Notes
2022-09-30 16:33:17LETTER WAS RECEIVED UNDER THE INT DEMO 22061366

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 16:10 Sent To  
Notes
2022-08-26 09:33:59PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-21 Cont ID  
Sent By rmcphers Date 2022-10-21 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2022-10-20 Time 08:38 Sent To  
Notes
2022-10-20 08:44:54COMMERCIAL BUILDING RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING TO THE COMMON ENTRY OF EACH UNIT - FBC A 202.3
 ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1.
 FBC A 201.1.1 VERTICAL ACCESSIBILITY.
 FBC A 202.3.3 BARRIERS AT COMMON OR EMERGENCY ENTRANCES
 AND EXITS.
 BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF
 BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE
 GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION,
 OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT
 A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE
 REMOVED.
  
 2) THE ACCESSIBLE PARKING SPACE SHOULD BE PLACED IN THE
 CENTER OF THE BUILDING WHICH WOULD MAKE IT ON THE
 SHORTEST PATH TO ALL OF THE ACCESSIBLE COMMON ENTRIES -
 FBC A 208.3.1 PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES MUST BE
 LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST 44
 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT
 COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES
 EXCEPT BEHIND HIS OR HER OWN VEHICLE.
  
 FYI - WINDOW AND DOOR PERMIT 22091155
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 10:35 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 16:10 Sent To  
Notes
2022-08-26 10:34:17COMMERCIAL BUILDING RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE GUARD RAIL DETAILS FBC 1015.2
  
 2) PLEASE SHOW THE ENCLOSURE UNDER THE MEZZANINE STAIRS
 TO COMPLY WITH - FBC 1011.7.3
  
 3) PLEASE SHOW THE MEZZANINE STAIR CONSTRUCTION DETAILS
 ( STEEL, CONCRETE ETC.) - CONSTRUCTION TYPE II PER
 DRAWINGS - NON COMBUSTIBLE PER FBC 603.1
  
 4) PLEASE SHOW THE MEZZANINE "USE" PER FBC CHAPTER 3
  
 5) PLEASE SHOW VERTICAL ACCESSIBILITY TO THE MEZZANINE
 - FBC A 201.1.1
  
 6) PLEASE SHOW THE CEILING HEIGHT FOR THE MEZZANINE -
 FBC 505.2
  
 7) PLEASE SHOW THE MEZZANINE SQUARE FOOTAGE AND THE
 SQUARE FOOTAGE ON THE GROUND FLOOR THAT THE MEZZANINE
 IS OPEN TO PER FBC 505.2.1AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN
 A ROOM SHALL BE NOT GREATER THAN ONE-THIRD OF THE FLOOR
 AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTION OF A ROOM SHALL NOT BE INCLUDED IN
 A DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED.
  
 8) PLEASE SHOW THE CONCRETE COLUMNS AND TIE BEAM
 DETAILS (FOR COLUMNS AND BEAM AT THE METAL CANOPY
 LOCATIONS) - ATTACHMENT TO FOUNDATION ? ATTACHMENT TO
 EXISTING TIE BEAM ? ETC. - FBC 1604.8.2
  
 9) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS AND
 WINDOWS - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD - FBC WPB
 107.3.4
  
 10) PLEASE SHOW THE ACCESSIBLE ROUTE TO EACH BAY - FROM
 THE ACCESSIBLE PARKING SPACE TO THE ENTRY - FBC A
 206.2.1
  
 11) PLEASE SHOW THE ACCESSIBLE PARKING SPACE ACCESS
 AISLE - FBC A 502.3
  
 12) ACCESSIBLE RESTROOM - PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE DIMENSION
 FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC A
 603.3MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 13) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB
 BAR HEIGHT TO THE TOP OF THE GRIPPING SURFACE - FBC A
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 14) PLEASE SHOW THE OCCUPANCY LOAD FOR THE MEZZANINE -
 FBC 1004
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-12-21 Cont ID  
Sent By jleahy Date 2022-12-21 Time 06:58 Rev Time 0.00
Received By jleahy Date 2022-12-21 Time 06:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-30 Cont ID  
Sent By dbattles Date 2022-09-30 Time 16:41 Rev Time 0.00
Received By dbattles Date 2022-09-30 Time 16:41 Sent To  
Notes
2022-09-30 16:42:47APPROVED AND STAMPED IN FIRST REVIEW AND NO NEW
 DRAWINGS OR CHANGES IN THE RESUBMITTAL FOR ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-12 Cont ID  
Sent By jleahy Date 2022-08-12 Time 10:05 Rev Time 0.00
Received By jleahy Date 2022-08-12 Time 08:21 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2022-12-08 Cont ID  
Sent By rrossano Date 2022-12-08 Time   Rev Time 0.00
Received By rrossano Date 2022-12-08 Time   Sent To  
Notes
2022-12-08 10:16:33PASSED WITH PROVISO:
  
 A FORMAL ENGINEERING SUBMITTAL WILL BE REQUIRED FOR
 CONNECTIONS TO CITY WATER AND SEWER INFRASTRUCTURE IN
 THE RIGHT OF WAY. ENGINEERING DEVELOIPMENT PACKAGE
 EMAILED TO CURY GROUP ON 12.8.22.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-11-22 Cont ID  
Sent By   Date 2022-11-22 Time   Rev Time 0.00
Received By jcclark Date 2022-11-22 Time 15:32 Sent To  
Notes
2022-11-22 15:33:02ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By   Date 2022-10-04 Time   Rev Time  
Received By bdolan Date 2022-10-04 Time 12:02 Sent To  
Notes
2022-10-04 12:31:50PREVIOUS COMMENTS ADDRESSED IN RESUB.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-14 Cont ID  
Sent By   Date 2022-07-14 Time   Rev Time 0.00
Received By bdolan Date 2022-07-14 Time 12:38 Sent To  
Notes
2022-07-14 12:50:03PLAN SHEET REFERENCES A FIRE ALARM SYSTEM. PLEASE
 PROVIDE
 A SUMMARY/PLAN FOR EXISTING FIRE ALARM SYSTEM AND ANY
 UPDATES TO BE MADE.
  
 PLEASE NOTE WHERE EMERGENCY LIGHTING
 IS PROPOSED TO BE MOUNTED FOR EGRESS PATHS/EXITS
  
 PLEASE INCLUDE A LIFE SAFETY PLAN IN PLAN SET FOR NEW
 LAYOUT.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-08-01 Cont ID  
Sent By amhamilt Date 2022-08-01 Time 15:37 Rev Time 0.00
Received By amhamilt Date 2022-08-01 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-28 Cont ID  
Sent By lmarchan Date 2022-12-28 Time 09:14 Rev Time 0.00
Received By lmarchan Date 2022-12-06 Time 07:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-21 Cont ID  
Sent By rmcphers Date 2022-10-21 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2022-09-30 Time 10:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 10:35 Rev Time 0.00
Received By rmcphers Date 2022-07-13 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-01-09 Cont ID  
Sent By lmarchan Date 2023-01-09 Time 10:01 Rev Time 0.00
Received By lmarchan Date 2022-12-30 Time 09:12 Sent To  
Notes
2023-01-06 11:43:53RECEIPT MU-2023-000404-0000 - $2,502.76 PAID AO
2022-12-30 09:13:01EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By rmcphers Date 2022-08-26 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2022-08-26 Time 10:34 Sent To  
Notes
2022-08-26 10:35:05PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-20 Cont ID  
Sent By medwards Date 2022-12-20 Time 17:20 Rev Time 0.00
Received By medwards Date 2022-12-20 Time 17:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By medwards Date 2022-10-19 Time 15:38 Rev Time 0.00
Received By medwards Date 2022-10-19 Time 15:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By medwards Date 2022-07-27 Time 15:44 Rev Time 0.00
Received By medwards Date 2022-07-27 Time 15:44 Sent To  
Notes
2022-07-27 16:19:14 
 PROVIDE A DEMO DRAWING FOR THE REMOVING OF EXISTING
 WORK. FBC 107.2.1
 PROVIDE EQUIPMENT SIZING CALCULATIONS FOR EACH UNIT.
 FMC C403.2.1
 PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES
 THE USE OF EACH SPACE. IT APPEARS THAT OCCUPANCY WOULD
 BE MUSEUM/GALLERIES. PROVIDE A USE OF SPACE LETTER SO
 WE CAN DETERMINE THE BEST OCCUPANCY CLASSIFICATION TO
 USE FROM FMC TABLE 403.3.1.1.
 SHEET M-101 HAS A NOTE THAT STATES; SEE MEZZANINE PLAN
 FOR CONTINUATION. PROVIDE THIS DRAWING AS IT IS NOT IN
 THIS SUBMITTAL. FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-08 Cont ID  
Sent By rwbrown Date 2022-12-08 Time 08:24 Rev Time 0.00
Received By rwbrown Date 2022-12-08 Time 08:24 Sent To  
Notes
2022-12-08 08:25:02PROVISO ADDED PER CONTRACTOR/DESIGNER THAT A SERVICE
 SINK IS NEEDED IN EACH UNIT

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-17 Cont ID  
Sent By rwbrown Date 2022-10-17 Time 06:41 Rev Time 0.00
Received By rwbrown Date 2022-10-17 Time 06:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-02 Cont ID  
Sent By jesmith Date 2022-08-02 Time 11:21 Rev Time 0.00
Received By jesmith Date 2022-07-28 Time 14:25 Sent To  
Notes
2022-08-02 11:19:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22061550 2414 FLORIDA AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.THE BACKFLOW PERMIT(S) ARE REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
  
 2. A-700/DETAILS 1 & 2:CLEARANCE AROUND A WATER CLOSET
 SHALL BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE SIDE WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG
 WATER CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR
 MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO THE
 REAR WALL PER FBC ACC 604.3.1 AND 604.8.1.1.
 SEE P-103 PLUMBING FIXTURE SCHEDULE. SPECIFIED A.S.
 3043.001 MADERA WATER CLOSET IS FLOOR MOUNTED AND
 REQUIRES 59 INCHES DEEP MINIMUM CLEAR FLOOR SPACE FOR
 FLOOR MOUNTED WATER CLOSETS MEASURED PERPENDICULAR TO
 THE REAR WALL,
  
 3.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
  
 4.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
  
 5.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
  
 6. RE: MEZZANINE SINK: PLEASE NOTE WHERE SINKS ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF
 EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE
 SHALL COMPLY WITH FBC ACC 606 PER FBC ACC 212.3.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 606.3. PER WPB FBC 107.2.1, SHOW COMPLIANCE.
 FBC ACC ADVISORY 202.3 ALTERATIONS. ALTHOUGH COVERED
 ENTITIES ARE PERMITTED TO LIMIT THE SCOPE OF AN
 ALTERATION TO INDIVIDUAL ELEMENTS, THE ALTERATION OF
 MULTIPLE ELEMENTS WITHIN A ROOM OR SPACE MAY PROVIDE A
 COST-EFFECTIVE OPPORTUNITY TO MAKE THE ENTIRE ROOM OR
 SPACE ACCESSIBLE. ANY ELEMENTS OR SPACES OF THE
 BUILDING OR FACILITY THAT ARE REQUIRED TO COMPLY WITH
 THESE REQUIREMENTS MUST BE MADE ACCESSIBLE WITHIN THE
 SCOPE OF THE ALTERATION, TO THE MAXIMUM EXTENT
 FEASIBLE. IF PROVIDING ACCESSIBILITY IN COMPLIANCE WITH
 THESE REQUIREMENTS FOR PEOPLE WITH ONE TYPE OF
 DISABILITY (E.G., PEOPLE WHO USE WHEELCHAIRS) IS NOT
 FEASIBLE, ACCESSIBILITY MUST STILL BE PROVIDED IN
 COMPLIANCE WITH THE REQUIREMENTS FOR PEOPLE WITH OTHER
 TYPES OF DISABILITIES (E.G., PEOPLE WHO HAVE HEARING
 IMPAIRMENTS OR WHO HAVE VISION IMPAIRMENTS) TO THE
 EXTENT THAT SUCH ACCESSIBILITY IS FEASIBLE.
 FLORIDA REQUIREMENTS FOR EXISTING PARKING
 S.553.5041(G), F.S., AND VERTICAL ACCESSIBILITY
 S.553.509, F.S., ARE INCORPORATED INTO THIS GENERAL
 SECTION APPLICABLE TO ALTERATIONS. FLORIDA REQUIREMENTS
 MAY BE WAIVED DOWN TO THE ADA STANDARDS REQUIREMENTS.
  
  
 7. BUILDING OCCUPANCY IS CLASSIFIED BUSINESS. PER FBC
 PL 403.1, 403.5, 410.3 AND FBC ACC 211.3, PROVIDE TWO
 DRINKING FOUNTAINS. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7. WHERE A SINGLE DRINKING
 FOUNTAIN COMPLIES WITH 602.1 THROUGH 602.6 AND 602.7,
 IT SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO
 SEPARATE DRINKING FOUNTAINS.
 DRINKING FOUNTAINS SHALL BE LOCATED ON AN ACCESSIBLE
 ROUTE WITHIN 500 FEET OF ALL TENANTS.
  
 8.MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER- CHRONOMITE CMI SERIES W/INTEGRAL
 ASSE 1070 TEMPERATURE LIMITING DEVICE AS NOTED ON P-104
 WATER RISERS AND LISTED BELOW:
 CMI-20L/120
 CMI-15L/208
 CMI-30L/208
 ***B) BACKFLOW PREVENTER DEVICES
  
 9. WATER HEATERS SERVING TENANT TOILET ROOM LAVATORIES
 ARE PROVIDED WITH INTEGRAL ASSE 1070 TEMPERATURE
 LIMITING DEVICES (P-104); PLUMBING FIXTURE SCHEDULE
 P-2-LAVATORY CALLS SENSOR FAUCET WITH A 605XTMV1070
 THERMOSTATIC MIXING VALVE. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 10.P-104: 1 INCH COLD WATER FEED TO INDIVIDUAL TOILET
 ROOMS AT 28 GPM EXCEEDS RECOMMENDED VELOCITY CALLED OUT
 IN FBC PL APPENDIX E/ FIGURE E103.3(3).
  
 11. P-101/P-103: MEZZANINE SANITARY SHALL CONNECT
 DOWNSTREAM OF THE MOST DOWNSTREAM WATER CLOSET IN
 TENANT SPACE 6 PER FBC PL 909.1 AND 912.1.
  
 12.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE SINK
 (P-3) AND DISHWASHER CONNECTION IN TENANT SPACE 6;
 ***A) THE WASTE CONNECTION OF A RESIDENTIAL DISHWASHER
 SHALL CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOP. FBC PL 409.4
 ***B) COMPONENTS (SINK, WATER HEATER, TMV) AND SHUT-OFF
 VALVES OF THE COLD, HOT AND TEMPERED WATER.
  
 13.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR LAVATORIES
 (P-2) IN TENANT SPACE 6 TO INCLUDE LAVATORIES, WATER
 HEATER, TMV AND SHUT-OFF VALVES OF THE COLD, HOT AND
 TEMPERED WATER.
  
 14.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR LAVATORY
 (P-2) IN TYPICAL SINGLE TOILET ROOM TO INCLUDE
 LAVATORY, WATER HEATER, TMV AND SHUT-OFF VALVES OF THE
 COLD, HOT AND TEMPERED WATER
  
 15.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 16.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 17.PROVIDE ENERGY EFFICIENCY FOR WATER HEATER(S);
 COMPLY WITH FBC EC TABLE C404.2
  
 18.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 19.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 20.A VACUUM BREAKER IS REQUIRED ON ALL HOSE BIBS.
 PROVIDE A SPEC AND DETAIL.
  
 21.PER FBC PL 708.1.4, PROVIDE A CLEANOUT AT THE 90
 DEGREE CHANGES OF DIRECTION IN THE BUILDING DRAINS FOR
 BAYS 1, 2, 3, 4 AND 5.
  
 22.PER WPB FBC 107.2.1, PROVIDE DETAILS FOR THE
 FOLLOWING:
 ***A) EXTERIOR CLEANOUT AT JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER
 ***B) INTERIOR FLOOR CLEANOUT
 ***C) INTERIOR WALL CLEANOUT
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-12-12 Cont ID  
Sent By rmcphers Date 2022-12-12 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-12-12 Time 11:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-20 Cont ID  
Sent By rmcphers Date 2022-10-20 Time 12:03 Rev Time 0.00
Received By rmcphers Date 2022-10-20 Time 12:03 Sent To  
Notes
2022-10-19 15:39:36MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-29 Cont ID  
Sent By rwbrown Date 2022-07-29 Time 13:39 Rev Time 0.00
Received By rwbrown Date 2022-07-29 Time 13:39 Sent To  
Notes
2022-08-02 11:17:08PLUMBING DIGITAL SIGNATURES APPROVED. JS
2022-07-27 16:19:51MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 3 Status P Date 2022-12-28 Cont ID  
Sent By ajones Date 2022-12-28 Time 08:52 Rev Time 0.00
Received By ajones Date 2022-12-28 Time 08:52 Sent To  
Notes
2022-12-28 09:04:2912/28/22- SEPERATE PERMIT REQUIRED FOR SIGNAGE AND
 STRIPING.
  
 ANGELLA VANN
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By afowlkes Date 2022-10-19 Time 16:20 Rev Time 0.00
Received By afowlkes Date 2022-10-19 Time 16:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By afowlkes Date 2022-07-19 Time 10:49 Rev Time 0.00
Received By afowlkes Date 2022-07-19 Time 10:49 Sent To  
Notes
2022-07-19 10:51:5307/19/22 FAILED
  
 THE VALUE OF THE CONSTRUCTION ($1.15 M) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($914,959) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]