Plan Review Details - Permit 22061548
Plan Review Stops For Permit 22061548
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-08-16 Cont ID  
Sent By jgomez Date 2022-08-16 Time 15:15 Rev Time 0.00
Received By jgomez Date 2022-08-16 Time 14:43 Sent To  
Notes
2022-08-16 15:16:13RECEIVED EMAIL FROM YVETTE SANSUR. PROFLEX LV-200 AND
 LAMINATED WOOD FLOORING JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-12 Cont ID  
Sent By jgomez Date 2022-08-12 Time 17:45 Rev Time 0.00
Received By jgomez Date 2022-08-12 Time 16:10 Sent To  
Notes
2022-08-12 17:46:38RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061548
  
 1- THE FLAME SPREAD TEST REPORT SUBMITTED IS FOR
 PROFLEX LV-200 UNDERLAYMENT. THE SOUND TRANSMISSION
 CLASS (STC) TEST REPORT AND THE IMPACT INSULATION CLASS
 (IIC) TEST REPORT SUBMITTED IS FOR PROTECT WRAP
 WHISPERMAT LVT.
 THE FLAME SPREAD TEST REPORT FOR THE FLOORING
 UNDERLAYMENT AND THE SOUND TRANSMISSION TEST REPORT
 SUBMITTED ARE FOR TWO DIFFERENT MANUFACTURERS. THE
 FLAME SPREAD REPORT AND THE SOUND TEST REPORT NEED TO
 BE DONE FOR THE SAME UNDERLAYMENT MATERIAL AND
 MANUFACTURER. PLEASE RESUBMIT.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 13:29 Rev Time 0.00
Received By shill Date 2022-08-02 Time 13:28 Sent To  
Notes
2022-08-02 13:32:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 FROM PREVIOUS LIST, F&D NUCORE FLAME SPREAD TEST WAS
 SUBMITTED (FOR FLOORING), BUT THE FOLLOWING TEST
 REPORTS ARE REQUIRED FOR THE UNDERLAYMENT. BEFORE
 RESUBMITTING PLEASE EMAIL [email protected] TO ADVISE OF
 THE UNDERLAYMENT PROPOSED.
  
 2. ENGINEERED WOOD FLOOR REQUIRES A FLOORING
 UNDERLAYMENT. PROVIDE THE STC, IIC, FLAME SPREAD TESTS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 15:02 Rev Time 0.00
Received By shill Date 2022-07-25 Time 15:01 Sent To  
Notes
2022-07-25 15:13:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 2509.1, SPECIFY BACKERBOARD FOR PROPOSED TILE
 IN THE SHOWER.
  
 2. ENGINEERED WOOD FLOOR REQUIRES A FLOORING
 UNDERLAYMENT. PROVIDE THE STC, IIC, FLAME SPREAD TESTS.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-08-15 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By pleduc Date 2022-08-01 Time   Rev Time 0.00
Received By pleduc Date 2022-08-01 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By pleduc Date 2022-06-30 Time   Rev Time 0.00
Received By pleduc Date 2022-06-30 Time 13:12 Sent To  
Notes
2022-06-30 13:16:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE INSTALL OF WOOD
 FLOORING IN THE MASTER BEDROOM, BUT NO SPEC SHEET NOR A
 PRODUCT NAME FOR THE ACTUAL PROPOSED FLOORING.
  
 WOOD FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WOOD
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED
 WOOD FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE IS AN INDICATION OF WALL TILE WORK IN THE
 MASTER BATHROOM THAT MY INVOLVE A FIRE RATED WALL.
  
 ENSURE FIRE RATED TENANT SEPARATION/CORRIDOR WALLS ARE
 REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-16 Cont ID  
Sent By jgomez Date 2022-08-16 Time 15:16 Rev Time 0.00
Received By jgomez Date 2022-08-16 Time 14:40 Sent To I
Notes
2022-08-16 14:41:44RECEIVED EMAIL FROM YVETTE SANSUR. PROFLEX LV-200 AND
 LAMINATED WOOD FLOORING JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-15 Cont ID  
Sent By lmarchan Date 2022-08-15 Time 12:37 Rev Time 0.00
Received By lmarchan Date 2022-08-12 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 13:32 Rev Time 0.00
Received By shill Date 2022-07-29 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 15:16 Rev Time 0.00
Received By shill Date 2022-06-29 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-01 Cont ID  
Sent By rwbrown Date 2022-08-01 Time 06:14 Rev Time 0.00
Received By rwbrown Date 2022-08-01 Time 06:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By rwbrown Date 2022-07-05 Time 11:50 Rev Time 0.00
Received By rwbrown Date 2022-07-05 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 15:15 Rev Time 0.00
Received By shill Date 2022-07-25 Time 15:15 Sent To  
Notes
***NONE***