Plan Review Details - Permit 22061524
Plan Review Stops For Permit 22061524
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-02-03 Cont ID  
Sent By rmcdouga Date 2023-02-03 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2023-02-03 Time 13:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2022-09-22 Time 15:03 Sent To  
Notes
2022-09-22 15:03:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ NOT RESOLVED. ] SUBMIT A STRUCTURAL ANALYSIS WITH
 CALCULATIONS TO SHOW THAT THE EXISTING STRUCTURE CAN
 SAFELY SUPPORT THE PROPOSED EQUIPMENT FOR DEAD AND LIVE
 LOADS. FBC 1603.1.8 SPECIAL LOADS
 SPECIAL LOADS THAT ARE APPLICABLE TO THE DESIGN OF THE
 BUILDING, STRUCTURE OR PORTIONS THEREOF, INCLUDING BUT
 NOT LIMITED TO THE LOADS OF MACHINERY OR EQUIPMENT,
 THAT ARE OF GREATER MAGNITUDE THAN THE LOADS DEFINED IN
 THE SPECIFIED FLOOR AND ROOF LOADS SHALL BE SPECIFIED
 BY THEIR DESCRIPTIONS AND LOCATIONS.
 FBC 1604.4 ANALYSIS
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES.
  
 MEMBERS THAT TEND TO ACCUMULATE RESIDUAL DEFORMATIONS
 UNDER REPEATED SERVICE LOADS SHALL HAVE INCLUDED IN
 THEIR ANALYSIS THE ADDED ECCENTRICITIES EXPECTED TO
 OCCUR DURING THEIR SERVICE LIFE.
  
 ANY SYSTEM OR METHOD OF CONSTRUCTION TO BE USED SHALL
 BE BASED ON A RATIONAL ANALYSIS IN ACCORDANCE WITH
 WELL-ESTABLISHED PRINCIPLES OF MECHANICS. SUCH ANALYSIS
 SHALL RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD
 PATH CAPABLE OF TRANSFERRING LOADS FROM THEIR POINT OF
 ORIGIN TO THE LOAD-RESISTING ELEMENTS.
  
 THE TOTAL LATERAL FORCE SHALL BE DISTRIBUTED TO THE
 VARIOUS VERTICAL ELEMENTS OF THE LATERAL
 FORCE-RESISTING SYSTEM IN PROPORTION TO THEIR
 RIGIDITIES, CONSIDERING THE RIGIDITY OF THE HORIZONTAL
 BRACING SYSTEM OR DIAPHRAGM. RIGID ELEMENTS ASSUMED NOT
 TO BE A PART OF THE LATERAL FORCE-RESISTING SYSTEM ARE
 PERMITTED TO BE INCORPORATED INTO BUILDINGS PROVIDED
 THEIR EFFECT ON THE ACTION OF THE SYSTEM IS CONSIDERED
 AND PROVIDED FOR IN THE DESIGN. A DIAPHRAGM IS RIGID
 FOR THE PURPOSE OF DISTRIBUTION OF STORY SHEAR AND
 TORSIONAL MOMENT WHEN THE LATERAL DEFORMATION OF THE
 DIAPHRAGM IS LESS THAN OR EQUAL TO TWO TIMES THE
 AVERAGE STORY DRIFT. WHERE REQUIRED BY ASCE 7,
 PROVISIONS SHALL BE MADE FOR THE INCREASED FORCES
 INDUCED ON RESISTING ELEMENTS OF THE STRUCTURAL SYSTEM
 RESULTING FROM TORSION DUE TO ECCENTRICITY BETWEEN THE
 CENTER OF APPLICATION OF THE LATERAL FORCES AND THE
 CENTER OF RIGIDITY OF THE LATERAL FORCE-RESISTING
 SYSTEM.
  
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS, SECTION 1610 FOR LATERAL SOIL LOADS AND SECTION
 1613 FOR EARTHQUAKE LOAD
  
 2) [ NOT RESOLVED. ] PROVIDE THE WINDLOAD DESIGN DATA
 FOR THE PROPOSED ROOF TOP EQUIPMENT INSTALLATION. THE
 VULT WINDSPEED FOR THE CITY OF WEST PALM BEACH IS 170
 MPH AND THE EXPOSURE CATEGORY IS C. FBC 1603.1.4
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 NEW COMMENT:
  
 4) THE LETTER FROM SPAN ENGINEERING IS REQUIRED TO BE
 SIGNED AND SEALED BY A FLORIDA LICENSED ENGINEER. THE
 EXISTING PLATFORM THAT WILL BE REUSED WILL HAVE TO BE
 EVALUATED BY A FLORIDA LICENSED ENGINEER TO DETERMINE
 IF IT CAN RESIST A 170 MPH WIND LOAD IN EXPOSURE C.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By rmcdouga Date 2022-08-26 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2022-08-26 Time 07:15 Sent To  
Notes
2022-08-26 07:49:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A STRUCTURAL ANALYSIS WITH CALCULATIONS TO
 SHOW THAT THE EXISTING STRUCTURE CAN SAFELY SUPPORT THE
 PROPOSED EQUIPMENT FOR DEAD AND LIVE LOADS. FBC
 1603.1.8 SPECIAL LOADS
 SPECIAL LOADS THAT ARE APPLICABLE TO THE DESIGN OF THE
 BUILDING, STRUCTURE OR PORTIONS THEREOF, INCLUDING BUT
 NOT LIMITED TO THE LOADS OF MACHINERY OR EQUIPMENT,
 THAT ARE OF GREATER MAGNITUDE THAN THE LOADS DEFINED IN
 THE SPECIFIED FLOOR AND ROOF LOADS SHALL BE SPECIFIED
 BY THEIR DESCRIPTIONS AND LOCATIONS.
 FBC 1604.4 ANALYSIS
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES.
  
 MEMBERS THAT TEND TO ACCUMULATE RESIDUAL DEFORMATIONS
 UNDER REPEATED SERVICE LOADS SHALL HAVE INCLUDED IN
 THEIR ANALYSIS THE ADDED ECCENTRICITIES EXPECTED TO
 OCCUR DURING THEIR SERVICE LIFE.
  
 ANY SYSTEM OR METHOD OF CONSTRUCTION TO BE USED SHALL
 BE BASED ON A RATIONAL ANALYSIS IN ACCORDANCE WITH
 WELL-ESTABLISHED PRINCIPLES OF MECHANICS. SUCH ANALYSIS
 SHALL RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD
 PATH CAPABLE OF TRANSFERRING LOADS FROM THEIR POINT OF
 ORIGIN TO THE LOAD-RESISTING ELEMENTS.
  
 THE TOTAL LATERAL FORCE SHALL BE DISTRIBUTED TO THE
 VARIOUS VERTICAL ELEMENTS OF THE LATERAL
 FORCE-RESISTING SYSTEM IN PROPORTION TO THEIR
 RIGIDITIES, CONSIDERING THE RIGIDITY OF THE HORIZONTAL
 BRACING SYSTEM OR DIAPHRAGM. RIGID ELEMENTS ASSUMED NOT
 TO BE A PART OF THE LATERAL FORCE-RESISTING SYSTEM ARE
 PERMITTED TO BE INCORPORATED INTO BUILDINGS PROVIDED
 THEIR EFFECT ON THE ACTION OF THE SYSTEM IS CONSIDERED
 AND PROVIDED FOR IN THE DESIGN. A DIAPHRAGM IS RIGID
 FOR THE PURPOSE OF DISTRIBUTION OF STORY SHEAR AND
 TORSIONAL MOMENT WHEN THE LATERAL DEFORMATION OF THE
 DIAPHRAGM IS LESS THAN OR EQUAL TO TWO TIMES THE
 AVERAGE STORY DRIFT. WHERE REQUIRED BY ASCE 7,
 PROVISIONS SHALL BE MADE FOR THE INCREASED FORCES
 INDUCED ON RESISTING ELEMENTS OF THE STRUCTURAL SYSTEM
 RESULTING FROM TORSION DUE TO ECCENTRICITY BETWEEN THE
 CENTER OF APPLICATION OF THE LATERAL FORCES AND THE
 CENTER OF RIGIDITY OF THE LATERAL FORCE-RESISTING
 SYSTEM.
  
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS, SECTION 1610 FOR LATERAL SOIL LOADS AND SECTION
 1613 FOR EARTHQUAKE LOAD
  
 2) PROVIDE THE WINDLOAD DESIGN DATA FOR THE PROPOSED
 ROOF TOP EQUIPMENT INSTALLATION. THE VULT WINDSPEED FOR
 THE CITY OF WEST PALM BEACH IS 170 MPH AND THE EXPOSURE
 CATEGORY IS C. FBC 1603.1.4
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-02-03 Cont ID  
Sent By rmcdouga Date 2023-02-03 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2023-01-30 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-22 Cont ID  
Sent By rmcdouga Date 2022-09-22 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2022-08-29 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-26 Cont ID  
Sent By rmcdouga Date 2022-08-26 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2022-08-01 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 12:48 Rev Time 0.00
Received By medwards Date 2022-07-07 Time 05:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-08-08 Cont ID  
Sent By medwards Date 2022-08-08 Time 11:19 Rev Time 0.00
Received By medwards Date 2022-08-08 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 12:44 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 12:44 Sent To  
Notes
2022-07-08 12:47:57PROVIDE DETAILS FOR THE STANDS FOR THE ADDITIONAL
 WEIGHT ADDED. PROVIDE ROOF DETAILS THAT IT WILL SUPPORT
 THE ADDITIONAL WEIGHT. FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-03 Cont ID  
Sent By rmcdouga Date 2023-02-03 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2023-02-03 Time 13:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 12:48 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 12:48 Sent To  
Notes
***NONE***