Plan Review Details - Permit 22061485
Plan Review Stops For Permit 22061485
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By fgiaquin Date 2022-08-16 Time 18:25 Rev Time 0.00
Received By fgiaquin Date 2022-08-16 Time 18:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By fgiaquin Date 2022-08-03 Time 23:58 Rev Time 0.00
Received By fgiaquin Date 2022-08-03 Time 23:43 Sent To  
Notes
2022-08-03 23:58:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. I. FS
 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-22 Cont ID  
Sent By pleduc Date 2022-07-22 Time   Rev Time 0.00
Received By pleduc Date 2022-07-21 Time 14:48 Sent To  
Notes
2022-07-22 11:35:45FIRE PROVISO:
  
 PROVIDE 80 BC RATED PORTABLE FIRE EXTINGUISHER WITHIN
 100 FEET OF THE DISPENSERS. NFPA 30A 9.2.5.2
  
 DETAILED WARNING SIGNAGE SHALL BE CONSPICUOUSLY POSTED
 PER NFPA 30A 9.2.5.4
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-03 Cont ID  
Sent By fgiaquin Date 2022-08-03 Time 23:59 Rev Time 0.00
Received By fgiaquin Date 2022-07-20 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By medwards Date 2022-07-26 Time 13:59 Rev Time 0.00
Received By medwards Date 2022-07-26 Time 13:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By medwards Date 2022-07-26 Time 14:08 Rev Time 0.00
Received By medwards Date 2022-07-26 Time 14:02 Sent To  
Notes
***NONE***