| 2023-02-03 08:39:24 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10674-R16 |
| | HAS BEEN REVISED TO FL10674-R17. PLEASE PROVIDE A |
| | COMPLETE SET TO INCLUDE COVER PAGES; IT COVERS MULTIPLE |
| | PRODUCTS & INSTALLATION METHODS. SELECT PRODUCT & |
| | INSTALLATION METHOD TO BE USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL26482-R6 |
| | HAS BEEN REVISED TO FL26482-R7. PLEASE PROVIDE A |
| | COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| | COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT ALL |
| | APPLICABLE OPTIONS FROM EACH CATEGORY. ALL APPLICABLE |
| | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON |
| | THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS |
| | NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL26482-R6 |
| | (HVHZ) IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF |
| | WEST PALM BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT |
| | CONSIDER USING FL26482-R7 (NON-HVHZ). |
| | 4. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL19979-R2 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-3 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-3 ONLY. |
| | 5. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL19979-R2 SYSTEM NO. W-24 DO NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -131.42 |
| | FOR EXPOSURE CATEGORY D AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY D/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. |
| | 6. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF |
| | DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING |
| | CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S), |
| | MEAN ROOF HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW |
| | POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |