Plan Review Details - Permit 22061421
Plan Review Stops For Permit 22061421
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2022-10-31 Time   Sent To  
Notes
2022-10-31 09:37:22BASE BUILDING ADDRESS 360 S ROSEMARY, NEW SHELL
 HIGHRISE, 1ST TENANT, NEW CONSTRUCTION.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By jwitmer Date 2022-08-17 Time 10:42 Rev Time 0.00
Received By jwitmer Date 2022-08-17 Time 07:42 Sent To  
Notes
2022-08-17 10:42:25COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-19 Cont ID  
Sent By jwitmer Date 2022-10-19 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2022-10-19 Time 09:01 Sent To  
Notes
2022-10-19 09:34:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061421
 ADD: 575 FERN ST. (360 S. ROSEMARY/ 21 STORY BUILDING)
 1ST TENANCY
 CONT: BLACK DIAMOND GENERAL CONTRACTING
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. OCT. 19TH/2022
 ACTION: PASSED / DEFFERRED SUBMITTAL
  
 1) LIFE SAFETY PLAN NOR A1.12-DIMENSION PLAN SHOW THE
 X-RAY ROOM # 145 IN COMPLIANCE WITH SECTION 465 CONTROL
 OF RADIATION HAZARD, PLEASE PROVIDE SPECIFICATIONS FOR
 A) SHIELDING 465.5.1 SHIELDING, B) 465.6 DOORS,
 INTERLOCK AND WARNING SYSTEMS BEFORE FRAMING
 INSPECTION.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By jwitmer Date 2022-08-17 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2022-08-17 Time 07:42 Sent To  
Notes
2022-08-17 10:43:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22061421
 ADD: 575 FERN ST. (360 S. ROSEMARY/ 21 STORY BUILDING)
 1ST TENANCY
 CONT: BLACK DIAMOND GENERAL CONTRACTING
 TEL: 561-746-3452
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 17TH/2022
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN:
 1A) THE OCCUPANCY LOAD SHOWN OF 36 PERSONS FROM TABLE
 1004.5 OF THE 2020 FBC-BUILDING CODE. THE OCCUPANT LOAD
 SHOWN ON THE LIFE SAFETY PLAN WILL BE OVER 50 PERSONS.
 PLEASE PROVIDE WHAT THE INCREASED OCCUPANT LOAD WILL BE
 IN ACCORDANCE WITH SECTION 1004.2 OF THE 2020
 FBC-BUILDING CODE.
  
 1B) HEADING CODE REQUIREMENTS. LIST THE REQUIREMENTS
 THAT 2 EXITS ARE REQUIRED, 3 PROVIDED. BECAUSE OF THE
 CLOSENESS OF THE 2 FRONT EXITS (LESS THAN 1/3RD OVERALL
 DIAGONAL DISTANCE APART) THE BACK EXIT THROUGH THE LAB
 IS A CONCERN. LOOKING AT THE BASE BUILDING PLAN FOR 360
 ROSEMARY THERE IS AN ELEVATED EXIT PASSAGEWAY THAT
 PASSES JUST BEHIND THIS TENANT SPACE, THE NORTH WALL OF
 THIS TENANT SPACE ROOMS 143 & 144. WHEN EXITING THROUGH
 THE LAB WHERE ARE YOU GOING, WHAT ROOM IS SHOWN HOW ARE
 YOU EXITING TO THE PUBLIC WAY. 2020 FBC-BUILDING CODE
 1007.1.1 & 1028.5.
  
 1C) THIS SAME EXIT PASSAGEWAY TO THE EXTERIOR OF THE
 BUILDING IS A 2-HOUR ENCLOSURE, THE BACK WALLS OF ROOMS
 143 & 144 IT APPEARS WOULD BE PART OF THE 2-HOUR
 ENCLOSURE. THE LEGEND SHOWS THE BACK WALL AS A 1-HOUR
 WALL. SECTION 1024.3 CONSTRUCTION IS THE SAME AS THE
 VERTICAL EXIT STAIRS, OVER4 STORIES 2 HOURS.
  
 1D) LIFE SAFETY PLAN & A1.12-DIMENSION PLAN.A1.11 DOOR
 TAGS. CLOSET DOORS 131, 132 & TOILET ROOM 111 (DOOR
 TAGS 36,37,& 38) IT APPEARS ARE OVER THE REQUIRED WIDTH
 OF THE CORRIDOR MORE THAN ONE-HALF. 1005.7.1. TABLE
 1020.2. CORRIDOR 44 INCHES X ?= 22 INCHES. 22 +36 = 58
 INCHES MIN. CORRIDOR WIDTH, CORRIDOR 133.
  
 1E)THE LIFE SAFETY PLAN NOR A1.12-DIMENSION FLOOR PLAN
 PROVIDE THE SQUARE FOOTAGE OF ROOM 123 DIRTY LAUNDRY
 STORAGE ROOM ASSUMED. TABLE 509 IN THE 2020 FBC-BUILD.
 CODE STATES LAUNDRY ROOMS OVER 100 SQ. FT. 1HR OR FIRE
 SPRINKLERS. PLEASE ALSO READ THE SECTION 509.4.2
 PROTECTION WALLS CAPABLE OF RESISTING SMOKE, WALLS
 SHALL EXTEND TO THE UNDERSIDE OF THE CEILING THAT IS A
 COMPONENT OF A FIRE RESISTANCE RATED FLOOR CEILING
 ASSEMBLY. DOORS SHALL BE SELF OR AUTOMATIC CLOSING.
  
 2) IF-300 TOILET ELEVATIONS. ELEVATION BACK WALL OF
 RESTROOM WITH W. C. DOES NOT SHOW COMPLIANCE WITH: 2020
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 2A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 2C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 3) LIFE SAFETY PLAN NOR A1.12-DIMENSION PLAN SHOW THE
 X-RAY ROOM # 145 IN COMPLIANCE WITH SECTION 465 CONTROL
 OF RADIATION HAZARD
 3A) SHIELDING 465.5.1 SHIELDING.
 3B) 465.6 DOORS, INTERLOCK AND WARNING SYSTEMS
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.22061353
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By jwitmer Date 2022-10-31 Time 11:59 Rev Time 0.00
Received By mpeterso Date 2022-10-31 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By jleahy Date 2022-08-17 Time 09:22 Rev Time 0.00
Received By jleahy Date 2022-08-17 Time 07:49 Sent To  
Notes
2022-08-17 09:27:47FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED
 PER NEC 517.13, 517.18, 517.19
  
 2) PAGE E3.1 SERVICE MAIN IS SHOWN AS A 400A DISCONNECT
 FEEDING A 200 AMPERE PANEL.
  
 3) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-11 Cont ID  
Sent By pleduc Date 2022-10-11 Time   Rev Time 0.00
Received By pleduc Date 2022-10-11 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By pleduc Date 2022-08-17 Time   Rev Time 0.00
Received By pleduc Date 2022-08-17 Time 11:34 Sent To  
Notes
2022-08-17 12:06:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET AO.02 - THERE IS AN INDICATION OF AN EXIR DOOR
 FROM THE LAB ROOM HOWEVER, THERE IS NO CLEAR INDICATION
 THAT THIS EXIT LEADS TO A PUBLIC WAY.
  
 PER NFPA 101 CH 7
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF WHERE THIS EXIT
 LEADS MEETING THE REQIREMENTS OF A EXIT/PUBLIC WAY.
  
  
 2) SHEET AO.15 - THERE ARE INDICATIONS WITHIN THE
 REMARKS SECTION OF THE DOOR SCHEDULE OR CARD READERS.
  
 CARD READER INSTALLATIONS SHALL BE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS AND COMPLY WITH NFPA 101 CH 7;
 7.2.1.6 WHERE APPLICABLE.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THIS PLAN
 SHEET.
  
  
 3) SHEET IF 200 - THERE IS AN INDICATION OF VWF,
 HOWEVER, THERE IS NO MANUFACTURE NAME NOR A PRODUCT
 SPECIFICATION SHEET MEETING THE REQUIRMENTS OF FLAME
 RATING.
  
 PER NFPA 101 CH 38 NEW BUSINESS
  
 38.3.3.3 INTERIOR FLOOR FINISH.
 38.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
  
  
 4) ELECTRICAL PLANS - THERE ARE NO CLEAR INDICATIONS OF
 EMERGENCY LIGHTING.
  
 PER NFPA 101 CH 38
  
 38.2.9 EMERGENCY LIGHTING.
 38.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH SEC TION 7.9 IN ANY BUILDING WHERE ANY
 ONE OF THE FOLLOWING CONDITIONS EXISTS:
 (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT.
 (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS
 ABOVE OR BELOW
 THE LEVEL OF EXIT DISCHARGE.
 (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL
 OCCUPANTS
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY OMISSION WITH
 SPECIFIC DETAILS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-03 Cont ID  
Sent By aoliver Date 2022-11-03 Time 09:02 Rev Time 0.00
Received By aoliver Date 2022-10-08 Time 19:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-17 Cont ID  
Sent By medwards Date 2022-08-17 Time 16:02 Rev Time 0.00
Received By medwards Date 2022-07-12 Time 16:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By medwards Date 2022-10-31 Time 13:50 Rev Time 0.00
Received By medwards Date 2022-10-31 Time 13:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By medwards Date 2022-08-17 Time 15:21 Rev Time 0.00
Received By medwards Date 2022-08-17 Time 15:21 Sent To  
Notes
2022-08-17 15:21:401ST REVIEW FMC
 PERMIT: 22061421
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS ON THE PERMIT APPLICATION AND THE
 DRAWINGS IS 575 FERN ST. WEST PALM BEACH BUT THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE AN
 ADDRESS OF 360 ROSEMARY. PLEASE PROVIDE THE CORRECT
 ADDRESS INCLUDING THE SUITE NUMBER. FBC 107.3.5
  
 2) PLEASE PROVIDE THE INTENDED USE OF THIS TENANT
 SPACE. IT APPEARS TO BE SOME TYPE OF MEDICAL OFFICE.
 FMC 407 AND FBC 469.
  
 3) THE LIFE SAFETY PLANS INDICATES RATED WALLS IN THIS
 TENANT SPACE. PLEASE SHOW THE FD IN ALL OF THE RATED
 WALL PENETRATIONS. FMC 607
  
 4) SHEET M-401 INDICATES THAT HP-D7 IS A 2-TON SYSTEM.
 THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR
 HP D7 IS 2.4 TONS. PLEASE EXPLAIN. FBC 107.3.5
  
 5) SHEET M-401 INDICATES THAT HP-D11 IS A 3-TON SYSTEM.
 THE EQUIPMENT SIZING CALCULATIONS SHOW THE MINIMUM FOR
 HP-D11 IS 1.9 TONS. PLEASE EXPLAIN THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 16:28 Rev Time 0.00
Received By ccole Date 2022-10-21 Time 15:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-08-17 Cont ID  
Sent By ccole Date 2022-08-17 Time 08:50 Rev Time 0.00
Received By ccole Date 2022-08-17 Time 06:58 Sent To  
Notes
2022-08-17 08:52:351ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22061421
 8/17/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SITE-SPECIFIC ENLARGED ACCESSIBLE
 TOILET ROOM DRAWINGS WITH THE FOLLOWING DETAILS PER FBC
 ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 2) A0.02: SHOW THE CLEAR FLOOR SPACE DIAGRAMS
 (POSITIONED FOR FORWARD OR PARALLEL APPROACH) AT THE
 ACCESSIBLE SINKS IN THE EXAM ROOMS AND BREAKROOM- SEC.
 606.2 FBC ACC.
  
 3) A0.02: THE DRINKING FOUNTAINS APPEAR TO BE
 PROTRUDING INTO THE CIRCULATION PATH WHICH IS NOT
 ALLOWED PER SEC. 307.2 FBC ACC.
  
 4) IF-501, 502, 503: THE BREAKROOM ELEVATION DETAIL
 DOES NOT SHOW THE REFRIGERATOR AND COFFEE MAKER, AND
 THEIR REACH RANGE COMPLIANCES- SEC. 308.1 FBC ACC.
  
 5) P3.1: PROVIDE THE EFFICIENCY RATINGS OF THE WATER
 HEATERS- TABLE C404.2 FBC EC.
  
 6) P3.1 EWH DETAIL: CORRECT THE 1/2-INCH THINK MINIMUM
 HW PIPE INSULATION THICKNESS TO SHOW 1-INCH MINIMUM-
 TABLE C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By mpeterso Date 2022-10-31 Time 12:02 Rev Time 0.00
Received By mpeterso Date 2022-10-31 Time 12:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-08-17 Cont ID  
Sent By medwards Date 2022-08-17 Time 16:02 Rev Time 0.00
Received By medwards Date 2022-08-17 Time 16:02 Sent To  
Notes
2022-08-17 15:22:26MECHANICAL DIGITAL SIGNATURES APPROVED ME
  
2022-08-17 10:44:37ARCHITECTURAL SHEETS GOOD. JW 8/17/22

Review Stop Z ZONING
Rev No 1 Status N Date 2022-11-01 Cont ID  
Sent By ckimmerl Date 2022-11-01 Time 10:42 Rev Time 0.00
Received By ckimmerl Date 2022-11-01 Time 10:42 Sent To  
Notes
***NONE***