Plan Review Details - Permit 22061370
Plan Review Stops For Permit 22061370
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2022-08-08 Cont ID  
Sent By scwelter Date 2022-08-08 Time 10:13 Rev Time 0.00
Received By scwelter Date 2022-08-08 Time 10:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2023-01-11 Cont ID  
Sent By rmcphers Date 2023-01-11 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2023-01-11 Time 09:10 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 15:15 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 15:15 Sent To  
Notes
2022-12-05 15:17:16WE DO NOT NEED A LETTER FROM THE HEALTH DEPT. OR AN
 ASBESTOS SURVEY - JUST NEED A LETTER FROM THE
 CONTRACTOR AS NOTED HERE - PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED, AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-10-07 Cont ID  
Sent By rmcphers Date 2022-10-07 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-10-07 Time 14:02 Sent To  
Notes
2022-10-07 14:02:41PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 14:38 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 14:38 Sent To  
Notes
2022-08-05 14:39:25PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2023-05-19 Cont ID  
Sent By rmcphers Date 2023-05-19 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2023-05-19 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-05-01 Cont ID  
Sent By rmcphers Date 2023-05-01 Time 11:13 Rev Time 0.00
Received By rmcphers Date 2023-05-01 Time 11:13 Sent To  
Notes
2023-05-01 11:13:33BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING PSP-1 NEEDS TO BE SIGNED BY THE DESIGNER -
 FBC WPB 107.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-01-11 Cont ID  
Sent By rmcphers Date 2023-01-11 Time 09:07 Rev Time 0.00
Received By rmcphers Date 2023-01-11 Time 09:07 Sent To  
Notes
2023-01-11 09:09:11BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE SITE PLAN NEEDS TO SHOW STORM WATER DRAINAGE
 AWAY FROM THE BUILDING AND AWAY FROM THE ADJACENT
 PROPERTY OR PROVIDE A STORM WATER DRAINAGE PLAN FBC WPB
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT
 SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES)
  
 2) PLEASE PROVIDE A SURVEY.
  
 3) DRAWING PSP-1 NEEDS TO BE SIGNED BY THE DESIGNER -
 FBC WPB 107.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 15:24 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 15:24 Sent To  
Notes
2022-12-05 15:24:58BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE
 PARKING TO THE ACCESSIBLE ENTRY - FBC A 206.2.1 SITE
 ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 2) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 3) PLEASE PROVIDE A SURVEY.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-07 Cont ID  
Sent By rmcphers Date 2022-10-07 Time 14:03 Rev Time 0.00
Received By rmcphers Date 2022-10-07 Time 13:51 Sent To  
Notes
2022-10-07 13:58:12BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PROPOSED FLOOR PLAN ON DRAWING A-201 - DOES NOT
 MATCH THE LIFE SAFETY FLOOR PLAN LAYOUT - DRAWINGS NEED
 TO MATCH.
  
 2) SEPARATE PERMIT IS REQUIRED FOR THE BUILDING DEMO.
  
 3) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE
 PARKING TO THE ACCESSIBLE ENTRY - FBC A 206.2.1 SITE
 ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 4) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 5) PLEASE PROVIDE A SURVEY.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-30 Cont ID  
Sent By rmcphers Date 2022-08-30 Time 13:37 Rev Time 0.00
Received By rmcphers Date 2022-08-30 Time 13:37 Sent To  
Notes
2022-08-30 13:38:24BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 2ND REVIEW - NO CHANGES
  
 CORRECTIONS NEEDED -
  
 1) SEPARATE PERMIT IS REQUIRED FOR THE BUILDING DEMO.
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 3) PLEASE PROVIDE THE FOUNDATION/WALL ATTACHMENT TO
 EXISTING FOUNDATION DRAWINGS. FBC WPB 107.2
  
 4) UNABLE TO FIND THE COLUMN SCHEDULE. FBC WPB 107.2
  
 5) DRAWING S1 SHOWS CUT SECTIONS REFERRING TO DRAWING
 S4 - I DO NOT SEE DRAWING S4 IN PROJECTDOX.
  
 6) DRAWING S1 DETAIL 1 SHOWS ROOF SHEATHING ATTACHMENT
 TO STEEL JOIST - PLEASE SHOW ROOF SHEATHING ATTACHMENT
 TO THE WOOD JOIST. FBC 2304.10
  
 7) DOOR SCHEDULE IS NOT COMPLETE - FLOOR PLAN SHOWS
 MORE NUMBERED DOORS THEN WHAT IS SHOWN ON THE DOOR
 SCHEDULE.
  
 8) PLEASE PROVIDE A WINDOW SCHEDULE - SHOW THE WINDOW
 TYPE, SIZE ETC. ROOF DORMERS SHOW WINDOWS.
  
 9) PLEASE PROVIDE ROOF WIND ZONES AND PRESSURES - FBC
 1609
  
 10) PLEASE SHOW THE ACCESSIBLE DINING LOCATIONS - FBC
 226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
  
 11) PLEASE SHOW THE ACCESSIBLE BAR SEATING LOCATION -
 SHOW COUNTER HEIGHT, KNEE AND TOE CLEARANCES - FBC A
 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES - FBC A 305.4KNEE
 AND TOE CLEARANCE. FBC A 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 12) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE
 PARKING TO THE ACCESSIBLE ENTRY - FBC A 206.2.1 SITE
 ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 13) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 14) PLEASE PROVIDE A SURVEY.
  
 15) PLEASE PROVIDE THE ALUMINUM CANOPY DETAILS - FBC
 1609
  
 16) CANOPY DETAILS, ROOFING SYSTEMS, WINDOW AND DOOR
 PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 13:44 Sent To  
Notes
2022-08-05 14:30:07BUILDING ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SEPARATE PERMIT IS REQUIRED FOR THE BUILDING DEMO.
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 3) PLEASE PROVIDE THE FOUNDATION/WALL ATTACHMENT TO
 EXISTING FOUNDATION DRAWINGS. FBC WPB 107.2
  
 4) UNABLE TO FIND THE COLUMN SCHEDULE. FBC WPB 107.2
  
 5) DRAWING S1 SHOWS CUT SECTIONS REFERRING TO DRAWING
 S4 - I DO NOT SEE DRAWING S4 IN PROJECTDOX.
  
 6) DRAWING S1 DETAIL 1 SHOWS ROOF SHEATHING ATTACHMENT
 TO STEEL JOIST - PLEASE SHOW ROOF SHEATHING ATTACHMENT
 TO THE WOOD JOIST. FBC 2304.10
  
 7) DOOR SCHEDULE IS NOT COMPLETE - FLOOR PLAN SHOWS
 MORE NUMBERED DOORS THEN WHAT IS SHOWN ON THE DOOR
 SCHEDULE.
  
 8) PLEASE PROVIDE A WINDOW SCHEDULE - SHOW THE WINDOW
 TYPE, SIZE ETC. ROOF DORMERS SHOW WINDOWS.
  
 9) PLEASE PROVIDE ROOF WIND ZONES AND PRESSURES - FBC
 1609
  
 10) PLEASE SHOW THE ACCESSIBLE DINING LOCATIONS - FBC
 226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
  
 11) PLEASE SHOW THE ACCESSIBLE BAR SEATING LOCATION -
 SHOW COUNTER HEIGHT, KNEE AND TOE CLEARANCES - FBC A
 226.2 DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES - FBC A 305.4KNEE
 AND TOE CLEARANCE. FBC A 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 12) PLEASE SHOW THE ACCESSIBLE PATH FROM THE ACCESSIBLE
 PARKING TO THE ACCESSIBLE ENTRY - FBC A 206.2.1 SITE
 ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.
  
 13) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE
 FOLLOWING INFORMATION FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 14) PLEASE PROVIDE A SURVEY.
  
 15) PLEASE PROVIDE THE ALUMINUM CANOPY DETAILS - FBC
 1609
  
 16) CANOPY DETAILS, ROOFING SYSTEMS, WINDOW AND DOOR
 PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-12-20 Cont ID  
Sent By jleahy Date 2022-12-20 Time 12:37 Rev Time 0.00
Received By jleahy Date 2022-12-20 Time 12:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-10-19 Cont ID  
Sent By jleahy Date 2022-10-19 Time 16:32 Rev Time 0.00
Received By jleahy Date 2022-10-19 Time 15:50 Sent To  
Notes
2022-10-19 16:35:48FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE LISTING FOR WEATHER PROOF WATER
 RESISTANT OUTLET AND FLOOR BOX.
  
 PLEASE SHOW MANUFACTURER AND PART NUMBERS FOR OUTLET ,
 BOX, AND COVER.
  
 PLEAASE READ 210.8(B) FOR GFCI PROTECTION FOR KITCHEN
 OR SINK AREAS AND THE TYPES OF OUTLETS TO BE PROTECTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 14:22 Rev Time 0.00
Received By jleahy Date 2022-09-19 Time 13:36 Sent To  
Notes
2022-09-19 14:24:52FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED
  
 PLEASE SEE 210.8(B) OF THE 2017 NEC FOR ADDITIONAL GFCI
 PROTECTION REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By jleahy Date 2022-08-03 Time 12:53 Rev Time 0.00
Received By jleahy Date 2022-08-03 Time 12:37 Sent To  
Notes
2022-08-03 13:04:39FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT RATING OF THE MAIN AND PANELS REQUIRED
 PER 110.21.
  
 2) PLEASE DESIGNATE THE KITCHEN AREA ON ELECTRICAL
 PLAN.
  
 3) FLOOR OUTLETS IN BAR AREA? THIS IS CONSIDERED A WET
 LOCATION PLEASE SHOW DETAIL OF HOW OUTLETS WILL BE
 LISTED FOR LOCATON. 110.3
  
 4) GFCI PROTECTION HAS CHANGED IN THE 2017 NEC PLEASE
 SEE THE PLAN FOR ADDITIONAL AREAS WERE PROTECTION IS
 REQUIRED.

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2023-05-25 Cont ID  
Sent By lquinone Date 2023-05-25 Time 07:34 Rev Time 0.00
Received By lquinone Date 2023-05-25 Time 07:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-05-04 Cont ID  
Sent By lquinone Date 2023-05-04 Time 14:29 Rev Time 0.00
Received By lquinone Date 2023-05-04 Time 14:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2022-09-27 Cont ID  
Sent By rrossano Date 2022-09-27 Time   Rev Time 0.00
Received By rrossano Date 2022-09-27 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-08-15 Cont ID  
Sent By rrossano Date 2022-08-15 Time   Rev Time 0.00
Received By rrossano Date 2022-08-15 Time   Sent To  
Notes
2022-08-15 10:31:30PLEASE ADDRESS PREVIOUS ENGINEERING COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-07-05 Cont ID  
Sent By rrossano Date 2022-07-05 Time   Rev Time  
Received By rrossano Date 2022-07-05 Time   Sent To  
Notes
2022-07-05 09:59:33AN APPROVED SITE PLAN AND FORMAL ENGINEERING SUBMITTAL
 ARE REQUIRED. PLEASE CLARIFY SCOPE OF PROJECT AND
 STATUS OF BOTH.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, CITY OF WPB
 ENGINEERING SERVICES DEPARTMENT
 (561) 494-1098, FAX: (561) 494-1116 EMAIL:
 [email protected]
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-11-21 Cont ID  
Sent By cwalker Date 2022-11-21 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-11-21 09:44:47FIRE PROVISO COMMENTS:
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
  
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED
 WITH PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL
 MEET ALL
 OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF
 THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN.
 (760 MM), AND NOT MORE THAN 48 IN. (1220 MM),
 ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO
 EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD
 AND LATCHES.
 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE
 USED ON
 FIRE PROTECTION-RATED DOOR ASSEMBLIES. NEW PANIC
 HARDWARE
 AND NEW FIRE EXIT HARDWARE SHALL COMPLY WITH ANSI/UL
 305,
 STANDARD FOR SAFETY PANIC HARDWARE, AND ANSI/BHMA
 A156.3,
 EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN
 OTHER THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS
 OTHERWISE
 PROVIDED IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED
 WITH ANY LOCKING DEVICE, SET SCREW, OR OTHER
 ARRANGEMENT THAT
 PREVENTS THE RELEASE OF THE LATCH WHEN PRESSURE IS
 APPLIED TO
 THE RELEASING DEVICE.
 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED
 POSITION
 SHALL BE PROHIBITED ON FIRE EXIT HARDWARE, UNLESS SUCH
 DEVICES
 ARE LISTED AND APPROVED FOR SUCH A PURPOSE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-09-27 Cont ID  
Sent By cwalker Date 2022-09-27 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-09-27 10:29:16FIRE PROVISO COMMENTS:
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, SUCH
 HARDWARE SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF
 THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN.
 (760 MM), AND NOT MORE THAN 48 IN. (1220 MM),
 ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO
 EXCEED 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD
 AND LATCHES.
 7.2.1.7.2* ONLY APPROVED FIRE EXIT HARDWARE SHALL BE
 USED ON FIRE PROTECTION-RATED DOOR ASSEMBLIES. NEW
 PANIC HARDWARE AND NEW FIRE EXIT HARDWARE SHALL COMPLY
 WITH ANSI/UL 305, STANDARD FOR SAFETY PANIC HARDWARE,
 AND ANSI/BHMA A156.3,
 EXIT DEVICES.
 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT
 HARDWARE, IN OTHER THAN DETENTION AND CORRECTIONAL
 OCCUPANCIES AS OTHERWISE PROVIDED IN CHAPTERS 22 AND
 23, SHALL NOT BE EQUIPPED WITH ANY LOCKING DEVICE, SET
 SCREW, OR OTHER ARRANGEMENT THAT PREVENTS THE RELEASE
 OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING
 DEVICE.
 7.2.1.7.4 DEVICES THAT HOLD THE LATCH IN THE RETRACTED
 POSITION SHALL BE PROHIBITED ON FIRE EXIT HARDWARE,
 UNLESS SUCH DEVICES ARE LISTED AND APPROVED FOR SUCH A
 PURPOSE.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-08-15 Cont ID  
Sent By cwalker Date 2022-08-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-08-15 13:18:45THIS PLAN WAS FAILED BY C. WALKER, FIRE PREVENTION
 DIVISION, WITH THE FOLLOWING COMMENTS:
  
 (1) PROVIDE A SITE PLAN. NFPA 1, 1.14
  
 (2) EXIT DOORS FROM THE DINING ROOM SHALL BE EQUIPPED
 WITH PANIC HARDWARE. NFPA 101, 12.2.2.2.3
  
 (3) EMERGENCY LIGHTING LOCATIONS SHALL BE INDICATED ON
 THE PLANS. NFPA 101, 12.2.9
  
 (4) EXIT SIGN LOCATIONS SHALL BE INDICATED ON THE
 PLANS. NFPA 12.2.10
  
 (5) THE PLAN INDICATES THE BUILDING IS TO BE EQUIPPED
 WITH FIRE SPRINKLERS. THE ENGINEERING DOCUMENTS MUST BE
 INCLUDED WITH THE MATER PLAN PER FAC 61G15-30.003
 THE INSTALLATION OF A FIRE SPRINKLER SYSTEM WILL
 REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS.
  
 (6) THE KITCHEN HOOD AND KITCHEN HOOD SUPPRESSION WILL
 REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS FOR
 APPLIANCES PRODUCING GREASE LADEN VAPOR. NFPA 101,
 12.3.2.2
  
 (7) OCCUPANT LOAD POSTING SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 101, 12.7.9.3
  
 WHEN RESUBMITTING, INDICATE CHANGES WITH CLOUDING ON
 THE APPLICABLE PLAN SHEETS OR RESPOND IN NARRATIVE
 FORM.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-05 Cont ID  
Sent By cwalker Date 2022-07-05 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-07-05 14:56:39FIRE REVIEW COMMENTS:
 PROVIDE A SITE PLAN. NFPA 1, 1.14
 EXIT DOORS FROM THE DINING ROOM SHALL BE EQUIPPED WITH
 PANIC HARDWARE. NFPA 101, 12.2.2.2.3
 EMERGENCY LIGHTING LOCATIONS SHALL BE PROVIDED ON THE
 LIFE SAFETY PLAN. NFPA 101, 12.2.9
 EXIT SIGN LOCATIONS SHALL BE INDICATED ON THE LIFE
 SAFETY PLAN. NFPA 101, 12.2.10
 THE LIFE SAFETY PLAN INDICATES THE BUILDING IS A
 SPRINKLERED. THE ENGINEERING DOCUMENTS MUST BE INCLUDED
 WITH THE MASTER PLAN PER FAC 61G15-30.003
 THE INSTALLATION OF A FIRE SPRINKLER SYSTEM WILL ALSO
 REQUIRE A SEPARATE PERMIT AND SHOP DRAWINGS.
 THE KITCHEN HOOD AND THE KITCHEN HOOD FIRE SUPPRESSION
 WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS FOR
 APPLIANCES PRODUCING GREASE LADEN VAPOR. NFPA 101
 12.3.2.2
 OCCUPANT LOAD POSTING SHALL BE PROVIDED IN ACCORDANCE
 WITH NFPA 101 12.7.9.3
 C. WALKER
 561-804-4762
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 09:25 Rev Time 0.00
Received By vbroglia Date 2023-05-18 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-05-16 Cont ID  
Sent By vbroglia Date 2023-05-16 Time 13:50 Rev Time 0.00
Received By vbroglia Date 2023-04-28 Time 16:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-11 Cont ID  
Sent By vbroglia Date 2023-01-11 Time 16:01 Rev Time 0.00
Received By vbroglia Date 2023-01-03 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-20 Cont ID  
Sent By jleahy Date 2022-12-20 Time 12:37 Rev Time 0.00
Received By jleahy Date 2022-11-18 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2022-10-19 Cont ID  
Sent By jleahy Date 2022-10-19 Time 16:35 Rev Time 0.00
Received By jleahy Date 2022-09-23 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 14:25 Rev Time 0.00
Received By jleahy Date 2022-08-14 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-09 Cont ID  
Sent By aoliver Date 2022-08-09 Time 07:06 Rev Time 0.00
Received By aoliver Date 2022-06-30 Time 06:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 14:30 Sent To  
Notes
2022-08-05 14:30:45PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-10-06 Cont ID  
Sent By medwards Date 2022-10-06 Time 10:21 Rev Time 0.00
Received By medwards Date 2022-10-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By medwards Date 2022-08-29 Time 07:07 Rev Time 0.00
Received By medwards Date 2022-08-29 Time 07:07 Sent To  
Notes
2022-08-29 07:08:212ND REVIEW FMC
 PERMIT: 22061370
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO THE LISTED SQ FT IN THE OUTDOOR AIR
 CALCULATIONS ON SHEET M-20 THE OCCUPANT COUNT FOR THE
 SEATING AREA, DINING ROOMS, SHOULD BE 165 WHICH WOULD
 REQUIRE A TOTAL OF 2,077 CFM OF OUTDOOR AIR. THE ACTUAL
 OCC. LOAD LISTED ON THE VENTILATION CHART IS 135.
 PLEASE ADJUST THE OUTDOOR AIR CALCULATIONS TO REFLECT
 THE ADDITIONAL REQUIRED OUTDOOR AIR FOR THIS AREA. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By medwards Date 2022-07-19 Time 13:30 Rev Time 0.00
Received By medwards Date 2022-07-19 Time 13:30 Sent To  
Notes
2022-07-19 13:30:211ST REVIEW FMC
 PERMIT: 22061370
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS. FEC101.5.1.1.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC 403.2.1
  
 3) PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE OF
 SPACE IN THIS BUILDING; DINING, BAR, KITCHEN. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
 4) ADD A NOTE ON THE MECHANICAL DRAWINGS STATING THAT
 THE REFRIGERATION WILL REQUIRE A SEPARATE PERMIT
 APPLICATION AND MECHANICAL REVIEW.
  
 5) ADD A NOTE ON THE MECHANICAL DRAWINGS STATING THAT
 THE HOODS AND EXHAUST DUCT FOR THE HOODS WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND MECHANICAL REVIEW.
  
 6) PROVIDE THE KITCHEN EQUIPMENT SCHEDULE. FBC 107.2.1
  
 7) PROVIDE A DETAIL OF THE CONDENSING UNITS LOCATION
 AND ANCHORAGE. FBC 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-22 Cont ID  
Sent By rwbrown Date 2022-08-22 Time 07:29 Rev Time 0.00
Received By rwbrown Date 2022-08-22 Time 07:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By rwbrown Date 2022-07-21 Time 11:13 Rev Time 0.00
Received By rwbrown Date 2022-07-21 Time 10:38 Sent To  
Notes
2022-07-21 11:12:551ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.8 - PAGE P-4.0 - DETAIL NUMBER 7 -
 THE GREASE INTERCEPTOR DETIAL SHOWS AN INDIRECT
 CONNECTION. THE DISCHARGE FROM A GREASE INTERCEPTOR
 MUST BE DIRECTLY CONNECTED TO THE SANITARY SYSTEM.
  
 2. 2020 FPC 909.2 - PAGE P-4.0 - DETAIL NUMBER 6 - THE
 DETAIL SHOWS A COMBO-WYE FITTING. THIS WOULD NEED TO BE
 A TEE FITTING OR THE VENT CONNECTION WILL BE BELOW THE
 TRAP WEIR.
  
 3. 2017 WPB AMENDS 107.2.1 - THERE ARE TWO FLOOR DRAINS
 ON THE PLANS THAT SHOW A VENT RISING OUT OF THE FLOOR
 IN THE MIDDLE OF THE BAR AREA. PLEASE CORRECT.
  
 4. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE
 LIMIT FOR HOT WATER. THE THERMOSTAT ON THE WATER HEATER
 SHALL NOT BE THE LIMITING DEVICE FOR HOT WATER
 DELIVERY.
  
 5. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR
 THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING
 FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD
 CONFORM TO ASSE 1070.
  
 6. 2017 WPB AMEND ? 107.3 -- A SEPARATE PERMIT IS
 REQUIRED FOR THE INTERCEPTOR. WHEN YOU OBTAIN THE
 PERMIT NUMBER FOR THE INTERCEPTOR, SUBMIT IT TO ME FOR
 RELEASE OF THIS COMMENT.
  
 7. 2017 WPB AMEND ? 107.2.1 - PLEASE ADD YOUR GREASE
 CALCULATIONS FOR GI SIZING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-10-07 Cont ID  
Sent By rmcphers Date 2022-10-07 Time 14:03 Rev Time 0.00
Received By rmcphers Date 2022-10-07 Time 14:03 Sent To  
Notes
2022-10-07 14:03:29ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-08-30 Cont ID  
Sent By rmcphers Date 2022-08-30 Time 13:39 Rev Time 0.00
Received By rmcphers Date 2022-08-30 Time 13:39 Sent To  
Notes
2022-08-30 13:39:22SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 14:30 Sent To  
Notes
2022-08-05 14:31:13SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-05-19 Cont ID  
Sent By rmcphers Date 2023-05-19 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2023-05-19 Time 15:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-05-01 Cont ID  
Sent By rmcphers Date 2023-05-01 Time 11:13 Rev Time 0.00
Received By rmcphers Date 2023-05-01 Time 11:13 Sent To  
Notes
2023-05-01 11:13:56SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING PSP DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2023-01-11 Cont ID  
Sent By rmcphers Date 2023-01-11 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2023-01-11 Time 09:18 Sent To  
Notes
2023-01-11 09:19:46SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING PSP DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-05 Cont ID  
Sent By rmcphers Date 2022-12-05 Time 15:27 Rev Time 0.00
Received By rmcphers Date 2022-12-05 Time 15:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-06 Cont ID  
Sent By medwards Date 2022-10-06 Time 10:21 Rev Time 0.00
Received By medwards Date 2022-10-06 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-22 Cont ID  
Sent By rwbrown Date 2022-08-22 Time 07:32 Rev Time 0.00
Received By rwbrown Date 2022-08-22 Time 07:32 Sent To  
Notes
2022-08-22 07:34:43ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C
  
 PAGES E-0.0, 1.0, 2.0, 3.0 AND S-1, 2 ARE NOT DIGITALLY
 SIGNED/SEALED.
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 14:37 Sent To  
Notes
2022-08-05 14:38:12SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS P2.0, S1, S2 - DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-08-03 13:05:56ELECTRICAL PAGES ARE APPROVED FOR DIGITAL SIGNATURE.
 JLEAHY

Review Stop Z ZONING
Rev No 7 Status F Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 09:24 Rev Time 0.00
Received By vbroglia Date 2023-06-14 Time 09:24 Sent To  
Notes
2023-06-14 09:25:00APPLICATION UNDER REVIEW, PLEASE RESUBMIT WHEN APPROVAL
 LETTER IS OBTAINED FROM ALEXIS SANGELEER
  

Review Stop Z ZONING
Rev No 6 Status F Date 2023-05-16 Cont ID  
Sent By vbroglia Date 2023-05-16 Time 13:48 Rev Time 0.00
Received By vbroglia Date 2023-05-16 Time 13:48 Sent To  
Notes
2023-05-16 13:49:28PER THE ZONING REGUATLIONS, THIS ADDITION REQUIRES A
 SITE PLAN REVIEW.
  
 PLEASE EMAIL [email protected] FOR A DEVELOPEMENT
 APPLICATION

Review Stop Z ZONING
Rev No 5 Status F Date 2023-01-11 Cont ID  
Sent By vbroglia Date 2023-01-11 Time 16:00 Rev Time 0.00
Received By vbroglia Date 2023-01-11 Time 16:00 Sent To  
Notes
2023-01-11 16:01:081/11/23 SEE PAST REVIEW COMMENTS

Review Stop Z ZONING
Rev No 4 Status F Date 2022-12-13 Cont ID  
Sent By vbroglia Date 2022-12-13 Time 12:38 Rev Time 0.00
Received By vbroglia Date 2022-12-13 Time 12:38 Sent To  
Notes
2022-12-13 12:39:0312/13/22
  
 NO BAR FACILITIES PERMITTED IN NC ZONING DISTRICT

Review Stop Z ZONING
Rev No 3 Status F Date 2022-10-06 Cont ID  
Sent By vbroglia Date 2022-10-06 Time 10:22 Rev Time 0.00
Received By vbroglia Date 2022-10-06 Time 10:22 Sent To  
Notes
2022-10-06 10:23:3910/6/22 FAILED
  
 SEE COMMENTS FROM JULY SUBMITTAL, COMMENTS NOT
 ADDRESSED.

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By vbroglia Date 2022-08-29 Time 10:57 Rev Time 0.00
Received By vbroglia Date 2022-08-29 Time 10:57 Sent To  
Notes
2022-08-29 10:58:388/29/2022 FAILED
  
 PLEASE SEE PREVIOUS COMMMENTS FROM7/28/2022
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By vbroglia Date 2022-07-28 Time 12:59 Rev Time 0.00
Received By vbroglia Date 2022-07-28 Time 12:59 Sent To  
Notes
2022-07-28 13:11:087/28/2022 FAILED
  
 BAR FACILITIES NOT PERMITTED IN THE NIEGHBORHOOD
 COMMERICAL (NC) ZONING DISTRICT
  
 PARKING REQUIREMENTS NEED TO BE PROVIDED AS THE
 EXTENSIONS OF THE FOOT PREMIT NEEDS TO FOLLOW THE
 CITY'S CURRENT ZONING AND LAND REGUALTIONS CODE
  
 PLEASE SHOW A SITE PLAN WITH THE REQUIRED NUMBER OF
 PARKING SPACES
  
 SEPARATE PERMIT REQUIRED FOR:
 FENCE/WALL, AWNINGS, SIGNS, PARKING LOT, GENERATOR,
 MECHANICAL/AC/POOL EQUIPMENT, DUMPSTER ENCLOSURE,
 IRRIGATION, LANDSCAPE, OTHER.
  
  