Plan Review Details - Permit 22061299
Plan Review Stops For Permit 22061299
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By cthroop Date 2023-05-31 Time 11:20 Rev Time 0.00
Received By cthroop Date 2023-05-31 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-03-23 Cont ID  
Sent By cthroop Date 2023-03-23 Time 11:02 Rev Time 0.00
Received By cthroop Date 2023-03-23 Time 11:00 Sent To  
Notes
2023-03-23 11:02:36NOTICE: BUILDING REVIEW APPROVAL IS PENDING THE
 APPROVAL OF THE SIGNATURE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-13 Cont ID  
Sent By cthroop Date 2023-02-13 Time 13:12 Rev Time 0.00
Received By cthroop Date 2023-02-13 Time 06:34 Sent To  
Notes
2023-02-13 13:20:292ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: UPLOADED PLAN PAGE S0.2 (DESIGN PARAMETERS)
 FROM MAIN DWELLING UNIT PERMIT 22051093
  
 PROVISO ON SITE PLAN: PEDESTRIAN GATES SHALL COMPLY
 WITH POOL BARRIER REQUIREMENTRS PER R4502.17.
  
 1. SITE WALL IS BEING USED AS A RETAINING WALL. PROVIDE
 WATER PROOFING DETAIL AND/OR LIQUID WATERPROOFING SPEC.
 SHEETS.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
 R406.2CONCRETE AND MASONRY FOUNDATION WATERPROOFING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 16:41 Rev Time 0.00
Received By shill Date 2022-07-23 Time 16:41 Sent To  
Notes
2022-07-23 16:44:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, SUBMIT A SURVEY.
  
 2. FBC 107, SUBMIT A SITE PLAN SHOWING FOOTING AND WALL
 RELATIVE TO PROPERTY LINE.
  
 3. FBC R 301, SUBMIT A STRUCTURAL DETAIL FOR THE
 PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN
 CRITERIA, AND IF A RETAINING WALL SHOULD SHOW THE
 AMOUNT OF SOIL THAT YOU PROPOSE FOR IT TO RETAIN. IF
 NOT PREPARED BY A DESIGN PROFESSIONAL, CALCULATIONS MAY
 BE REQUIRED.
  
 4. FBC 107, HAVE THE TWO PAGES UPLOADED REMOVED AS THEY
 APPEAR TO PRIMARILY SHOW INFORMATION FOR THE HOUSE
 FOUNDATION.
  
 5. PLAN SHOULD BE CLEAR IF IT PROPOSES FILL IN ADDITION
 TO THE WALL. IF IT DOES, A DRAINAGE PLAN IS REQUIRED.
 FBC 107.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2023-05-09 Cont ID  
Sent By lquinone Date 2023-05-09 Time 09:01 Rev Time 0.00
Received By lquinone Date 2023-05-09 Time 09:01 Sent To  
Notes
2023-05-09 09:03:32PASSED WITH PROVISO:
  
 WALL SHALL NOT BE PLACED IN ANY UTILITY EASEMENTS.
  
 PROPOSED WALL IS IN VICINITY OF CITY OWNED UTILITIES.
 CALL 811 TO HAVE ONE CALL UTILITIES LOCATE THE UTILITY
 LINE AND THEN MEET WITH APPROPRIATE CITY OF WPB O&M
 PERSONNEL FOR THE SPECIFIC UTILITY TO DETERMINE AMOUNT
 OF CLEARANCE NEEDED.
  
 SANITARY: CHARLES PHOENIX 561-822-2181 [email protected]
  
 THANKS,
 LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR,
 ENGINEERING SERVICES DEPARTMENT (561) 494-1085
 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2023-03-20 Cont ID  
Sent By rrossano Date 2023-03-20 Time   Rev Time 0.00
Received By rrossano Date 2023-03-20 Time   Sent To  
Notes
2023-03-20 11:20:57PLEASE RESPOND TO PREVIOUS COMMENT.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2023-01-30 Cont ID  
Sent By rrossano Date 2023-01-30 Time   Rev Time 0.00
Received By rrossano Date 2023-01-30 Time   Sent To  
Notes
2023-01-30 13:43:52PROPOSED WALL IS IN VICINITY OF CITY OWNED UTILITIES.
 CALL 811 TO HAVE ONE CALL UTILITIES LOCATE THE UTILITY
 LINE AND THEN MEET WITH APPROPRIATE CITY OF WPB O&M
 PERSONNEL FOR THE SPECIFIC UTILITY TO DETERMINE AMOUNT
 OF CLEARANCE NEEDED.
  
 SANITARY: CHARLES PHOENIX 561-822-2181 [email protected]
 WATER: COURTNEY MOORE 561-822-2174 [email protected]
 STORMWATER: STEPHON HARRIS 822-2185 [email protected]
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By rrossano Date 2022-07-25 Time   Rev Time 0.00
Received By rrossano Date 2022-07-25 Time   Sent To  
Notes
2022-07-25 15:08:21PLEASE CLEARLY SHOW UTILITY EASEMENTS ON CIVIL PLANS.
 SITE WALLS SHALL NOT BE PLACED WITHIN EASEMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 09:12 Rev Time 0.00
Received By vbroglia Date 2023-06-01 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-31 Cont ID  
Sent By cthroop Date 2023-05-31 Time 11:20 Rev Time 0.00
Received By cthroop Date 2023-05-03 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-03-23 Cont ID  
Sent By cthroop Date 2023-03-23 Time 11:02 Rev Time 0.00
Received By cthroop Date 2023-03-14 Time 07:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-15 Cont ID  
Sent By lmarchan Date 2023-02-15 Time 08:33 Rev Time 0.00
Received By lmarchan Date 2023-01-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 10:26 Rev Time 0.00
Received By shill Date 2022-06-28 Time 09:36 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-11-17 Cont ID  
Sent By shill Date 2022-11-17 Time 09:18 Rev Time 0.00
Received By shill Date 2022-11-17 Time 09:18 Sent To  
Notes
2022-11-17 09:18:55INSPECTIONS
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2023-02-15 Cont ID  
Sent By mhurley Date 2023-02-15 Time 07:27 Rev Time 0.00
Received By mhurley Date   Time   Sent To  
Notes
2023-02-15 07:27:03WALLS SHALL BE OUTSIDE OF UTILITY EASEMENT (NOT
 ENCROACH ON IT).

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By mhurley Date 2022-07-26 Time 12:51 Rev Time 0.00
Received By mhurley Date 2022-07-26 Time 12:47 Sent To  
Notes
2022-07-26 12:50:51PLANS ON THIS PERMIT DO NOT CLEARLY SHOW WALLS WITH
 RESPECT TO THE PROPERTY LINES, BUT OTHER ASSOCIATED
 PERMIT PLANS SHOW WALL ENCROACHING INTO WESTERN UTILITY
 EASEMENT. THAT UTILITY EASEMENT HAS AN ACTIVE SANITARY
 SEWER MAIN AND RETAINING WALL MAY NOT BE BUILT IN IT.
 PLEASE REVISE PLANS AND ALSO MAKE SURE UTILITY EASEMENT
 IS CLEARY SHOWN AND LABELED ON FUTURE PLAN SUBMISSIONS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By cthroop Date 2023-05-31 Time 11:19 Rev Time 0.00
Received By cthroop Date 2023-05-31 Time 10:24 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-03-23 Cont ID  
Sent By cthroop Date 2023-03-23 Time 11:00 Rev Time 0.00
Received By cthroop Date 2023-03-23 Time 11:00 Sent To  
Notes
2023-03-23 11:01:563RD SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: COMMENTS FROM 2ND SIGNATURE REVIEW HAVE NOT
 BEEN ADDRESSED. SEE BELOW:
  
 NOTICE: PLAN PAGES C-1, C-2 & L1.0
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-02-13 Cont ID  
Sent By cthroop Date 2023-02-13 Time 13:10 Rev Time 0.00
Received By cthroop Date 2023-02-13 Time 06:34 Sent To  
Notes
2023-02-13 13:12:042ND SIGNATURE REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: PLAN PAGES C-1, C-2 & L1.0
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE.
 A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE
 IS NOT CONSIDERED A VALID DIGITAL SIGNATURE.
  
 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S.
 668.003 (3);
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
 F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS)
 F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 16:45 Rev Time 0.00
Received By shill Date 2022-07-23 Time 16:44 Sent To  
Notes
2022-07-23 16:45:13SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 5 Status P Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 09:12 Rev Time 0.00
Received By vbroglia Date 2023-06-14 Time 09:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2023-05-16 Cont ID  
Sent By vbroglia Date 2023-05-16 Time 14:23 Rev Time 0.00
Received By vbroglia Date 2023-05-16 Time 14:23 Sent To  
Notes
2023-05-16 14:24:09FAILED FOR THE FOLLOWING REASON(S):
  
 1. VISIBILTY TRIANGLE IS NOTED OUTSIDE THE PROPERTY
 LINES, THIS MUST BE 20 FEET SETBACK FROM WHERE THE
 PROPERTY LINES INTERSECT
  
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-03-21 Cont ID  
Sent By vbroglia Date 2023-03-21 Time 12:38 Rev Time 0.00
Received By vbroglia Date 2023-03-21 Time 12:38 Sent To  
Notes
2023-03-21 12:39:01PREVIOUS COMMENT NOT ADDRESSED

Review Stop Z ZONING
Rev No 2 Status F Date 2023-02-07 Cont ID  
Sent By vbroglia Date 2023-02-07 Time 12:54 Rev Time 0.00
Received By vbroglia Date 2023-02-07 Time 12:54 Sent To  
Notes
2023-02-07 13:19:512/7/2023 FAILED
  
 -PEDESTRIAN ENTRY GATE ON SITE PLAN NEEDS TO BE 4 FEET
 IN HEIGHT FROM LOWEST POINT TO HIGHEST POINT OF THE
 GATE
  
 -SIDE SITE WALL WITH GATE ON TOP MUST BE 6 FEET TALL,
 FROM LOWEST TO TALLEST POINTS
 -PLEASE SEE PREVIOUS COMMENTS
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-07-06 Cont ID  
Sent By vbroglia Date 2022-07-06 Time 14:50 Rev Time 0.00
Received By vbroglia Date 2022-07-06 Time 14:50 Sent To  
Notes
2022-07-06 14:52:517/6/2022 FAILED
  
 PLEASE SHOW HOW THE HEIGHT OF THE WALL PROPOSED AND
 NOTE THAT FLAGLER IS CONSIDERED THE FRONT SETBACK ON
 CORNOR LOTS
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION 94-302(B)(1):
 MAXIMUM HEIGHT. IN RESIDENTIAL DISTRICTS, NO FENCE OR
 WALL SHALL EXCEED SIX FEET IN HEIGHT WITHIN REQUIRED
 SIDE AND REAR SETBACKS. FENCES OR WALLS SHALL NOT BE IN
 EXCESS OF 48 INCHES IN HEIGHT WITHIN THE REQUIRED FRONT
 SETBACK.
  
 PROVISO: NO FENCE, WALL, OR GATE THAT EXCEEDS 4 FEET IN
 HEIGHT SHALL BE PERMITTED WITHIN THE REQUIRED FRONT
 SETBACK OF 25 FEET.
  
  
 VISIBILITY AT INTERSECTIONS. AT ANY ROAD INTERSECTIONS,
 VISIBILITY SHALL NOT BE OBSCURED BY THE CONSTRUCTION,
 PLACEMENT, OR MAINTENANCE OF A STRUCTURE WALL, SIGN,
 FENCE, BERM, PLANT MATERIAL, SHRUBS, OR ANY SIMILAR
 ITEM BETWEEN 18 INCHES OR EIGHT FEET IN HEIGHT WITHIN A
 TRIANGLE BEGINNING AT THE POINT WHERE PROPERTY LINES
 MEET AT THE CORNER, THEN 20 FEET ALONG THE FRONT
 PROPERTY LINE, THENCE DIAGONALLY TO A POINT ALONG THE
 SIDE PROPERTY LINE 20 FEET FROM THE POINT OF BEGINNING,
 AND THENCE TO THE POINT OF BEGINNING. IN THE EVENT THE
 CORNER OF AN INTERSECTION IS ROUNDED, THE MEASUREMENT
 SHALL BEGIN AT THE POINT THE PROPERTY LINES WOULD MEET
 WITHOUT ROUNDING. (SEE FIGURE X-1)
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  