Plan Review Details - Permit 22061278
Plan Review Stops For Permit 22061278
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 09:32 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By rmcphers Date 2022-08-19 Time 16:01 Rev Time 0.00
Received By rmcphers Date 2022-08-19 Time 15:49 Sent To  
Notes
2022-08-19 16:01:24TRAILER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION AND
 SETBACKS FROM THE PROPERTY LINES AND OTHER BUILDINGS
 FBC WPB 107.2.5
  
 2) MORE INFORMATION IS NEEDED FOR REVIEW - PLEASE SHOW
 ON THE DRAWINGS WHAT THE TRAILER IS TO BE USED FOR -
  
 FBC WPB 102.2 BUILDING
  
 (D) TEMPORARY BUILDINGS OR SHEDS USED EXCLUSIVELY FOR
 CONSTRUCTION PURPOSES.
  
 (E) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY
 OFFICES, EXCEPT THAT THE PROVISIONS
 OF PART I I (SECTION 553.501-553.513 FLORIDA STATUTES
 RELATING TO ACCESSIBILITY BY
 PERSONS WITH DISABILITIES

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-27 Cont ID  
Sent By jleahy Date 2022-09-27 Time 13:58 Rev Time 0.00
Received By jleahy Date 2022-09-27 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-08 Cont ID  
Sent By mpeterso Date 2022-08-08 Time 14:17 Rev Time 0.00
Received By mpeterso Date 2022-08-08 Time 14:17 Sent To  
Notes
2022-08-08 14:28:56ELECTRIC REVIEW FAILED
 1) SEE SIGNATURE REVIEW
 2) PLEASE PROVIDE PLANS FOR ELECTRICAL SERVICE. PLEASE
 INCLUDE SITE PLAN WITH ALL RELEVANT ELECTRIC EQUIPMENT
 LOCATIONS AND RATINGS. PLEASE PROVIDE A ONE LINE RISER
 DIAGRAM.NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-09-07 Cont ID  
Sent By pleduc Date 2022-09-07 Time   Rev Time 0.00
Received By pleduc Date 2022-09-07 Time 15:31 Sent To  
Notes
2022-09-07 15:41:04THE SITE PLAN INDICATES THAT IT IS WITHIN 11 FT OF THE
 BUILDING.
  
 THE PREVIOUS COMMENTS ARE RESUBMITTED.
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ACCORDING TO THE SITE PLAN THE TRAILER IS TO BE
 SPEARATED BY AT LEAST 30'.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEAE REIVEW AND PROVIDE FOR COMPLIANCE.
  
 FOR INFORMATIONAL PURPOSES, ABC DRYCHEM EXTINGUISHERS
 WILL BE ACCEPTED IN LIEU OF WET FIRE SPRINKLERS.
  
  
 2) THERE IS NO FE LOCATED ON THE FLOOR PLAN.
  
 PER NFPA 101, CH 38 BUSINESS OCCUPANCY
  
 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE
 EXTINGUISHERS
 SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN
 ACCORDANCE WITH SEC TION 9.9
  
 9.9* PORTABLE FIRE EXTINGUISHERS
 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 PORTABLE FIRE EXTINGUISH ERS SHALL BE SELECTED,
 INSTALLED, INSPECTED, AND MAINTAINED IN ACCORDANCE
 WITH NFPA 10
  
 A MINIMUM 2A10BC IS REQUIRED WITHIN OR DIRECTY OUTSIDE
 THIS TRAILER.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT OF LOCATE A FE
 ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By pleduc Date 2022-07-27 Time   Rev Time 0.00
Received By pleduc Date 2022-07-27 Time 13:55 Sent To  
Notes
2022-07-27 14:07:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO SITE PLAN INDICATING THE LOCATION OF THE
 PROPOSED TRAILER WITH DIMENSION TO OTHER STRUCTURES,
 THE PROPOSED CONSTRUCTED BUILDING, PROPERTY LINES AND
 AREA BUILDINGS.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 PLEAE REIVEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
 2) THERE IS FE LOCATED ON THE FLOOR PLAN.
  
 PER NFPA 101, CH 38 BUSINESS OCCUPANCY
  
 38.3.5 EXTINGUISHMENT REQUIREMENTS. PORTABLE FIRE
 EXTINGUISHERS
 SHALL BE PROVIDED IN EVERY BUSINESS OCCUPANCY IN
 ACCORDANCE WITH SEC TION 9.9
  
 9.9* PORTABLE FIRE EXTINGUISHERS
 WHERE REQUIRED BY ANOTHER SECTION OF THIS CODE,
 PORTABLE FIRE EXTINGUISH ERS SHALL BE SELECTED,
 INSTALLED, INSPECTED, AND MAINTAINED IN ACCORDANCE
 WITH NFPA 10
  
 A MINIMUM 2A10BC IS REQUIRED WITHIN OR DIRECTY OUTSIDE
 THIS TRAILER.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT OF LOCATE A FE
 ON THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-27 Cont ID  
Sent By jleahy Date 2022-09-27 Time 13:59 Rev Time 0.00
Received By jleahy Date 2022-09-06 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-26 Cont ID  
Sent By lmarchan Date 2022-08-26 Time 11:16 Rev Time 0.00
Received By lmarchan Date 2022-07-26 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By ccole Date 2022-07-27 Time 08:12 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 08:07 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status N Date 2022-07-20 Cont ID  
Sent By rgathrig Date 2022-07-20 Time 15:29 Rev Time 0.00
Received By rgathrig Date 2022-07-20 Time 15:28 Sent To  
Notes
2022-07-20 15:30:58THE MOBILE OFFICE IS NOT GOING TO BE PRIVATE PROVIDER
 INTERIOR RENOVATION IS NOW A RESIDENT INSEPECTOR JOB.
 TIE DOWNS WILL BE INSPECTED BY CITY STAFF
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 7/20/2022

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2022-06-28 Cont ID  
Sent By rgathrig Date 2022-06-28 Time 09:59 Rev Time 0.00
Received By rgathrig Date 2022-06-28 Time 09:59 Sent To  
Notes
2022-06-28 10:00:14PRIVATE PROVIDER REVIEW FAILED
 THE NOTICE TO BUILDING OFFICIAL FROM THE OWNER JILL
 BERNSTEIN NAMES DAVID L HUSTAD AS THE PRIVATE PROVIDER
 FOR INSPECTIONS ONLY. MR. HUSTAD IS THE STRUCTURAL
 ENGINEER FOR THIS PROJECT AND HE CANNOT BE THE PRIVATE
 PROVIDER PER FLORIDA STATUTES 553.791 (3)
  
 553.791 (3) A PRIVATE PROVIDER AND ANY DULY AUTHORIZED
 REPRESENTATIVE MAY ONLY PERFORM BUILDING CODE
 INSPECTION
 SERVICES THAT ARE WITHIN THE DISCIPLINES COVERED BY
 THAT PERSON?S LICENSURE OR CERTIFICATION UNDER CHAPTER
 468,
 CHAPTER 471, OR CHAPTER 481, INCLUDING SINGLE-TRADE
 INSPECTIONS. A PRIVATE PROVIDER MAY NOT PROVIDE
 BUILDING CODE
 INSPECTION SERVICES PURSUANT TO THIS SECTION UPON ANY
 BUILDING DESIGNED OR CONSTRUCTED BY THE PRIVATE
 PROVIDER OR
 THE PRIVATE PROVIDER?S FIRM.
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 09:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-08 Cont ID  
Sent By mpeterso Date 2022-08-08 Time 14:29 Rev Time 0.00
Received By mpeterso Date 2022-08-08 Time 14:29 Sent To  
Notes
2022-08-08 14:30:09SIGNATURE REVIEW FAILED
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-09-16 Cont ID  
Sent By llouie Date 2022-09-16 Time   Rev Time 0.00
Received By llouie Date 2022-09-16 Time   Sent To  
Notes
2022-09-16 12:12:01** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED.
  
 [8/26/22 REPEAT COMMENT: SURVEY IS OUTDATED AND NOT
 SIGNED AND SEALED. THE SURVEY SHALL BE LESS THAN A YEAR
 OLD.]
  
  
 2.) A SITE PLAN, SHOWING THE LOCATION OF THE TRAILER,
 SETBACKS FROM THE PROPERTY LINE, ANY ASSOCIATED
 PARKING, ETC. REQUIRED AS PART OF THIS PERMIT
 SUBMITTAL. SCREENING REQUIREMENTS MAY APPLY.
  
 [8/26/22 REPEAT COMMENT: SITE PLAN SHOWING THE PROPOSED
 LOCATION OF THE TRAILER, INCLUDING THE DIMENSIONS FOR
 THE TRAILER SETBACK FROM THE PROPERTY LINE REQUIRED. A
 MINIMUM OF 5 FT. IS REQUIRED FROM THE PROPERTY
 LINE(S).]
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/SUNSHINE PARK HISTORIC DISTRICT
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By ahamilto Date 2022-08-26 Time   Rev Time  
Received By llouie Date 2022-08-26 Time   Sent To  
Notes
2022-08-26 10:58:54** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY
 REQUIRED.
  
 2.) MORE INFORMATION NEEDED. WHAT IS THE PURPOSE OF THE
 MOBILE TRAILER?
  
 3.) A SITE PLAN, SHOWING THE LOCATION OF THE TRAILER,
 SETBACKS FROM THE PROPERTY LINE, ANY ASSOCIATED
 PARKING, ETC. REQUIRED AS PART OF THIS PERMIT
 SUBMITTAL. SCREENING REQUIREMENTS MAY APPLY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC/SUNSHINE PARK HISTORIC DISTRICT
  