Plan Review Details - Permit 22061269
Plan Review Stops For Permit 22061269
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By pleduc Date 2022-07-15 Time   Rev Time 0.00
Received By pleduc Date 2022-07-15 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-05 Cont ID  
Sent By clfranci Date 2022-07-05 Time   Rev Time 0.00
Received By clfranci Date 2022-07-05 Time   Sent To  
Notes
2022-07-05 14:27:22THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS,
 FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS:
  
 1.CLASS K FIRE EXTINGUISHER IS REQUIRED AND MUST BE IN
 PLACE TIME OF INSPECTION.
  
 NFPA 96 10.10.2 CLASS K FIRE EXTINGUISHERS SHALL BE
 PROVIDED FOR COOKING
 APPLIANCE HAZARDS THAT INVOLVE COMBUSTIBLE COOKING
 MEDIA
 (VEGETABLE OILS AND ANIMAL OILS AND FATS).
  
 2. .INDICATE THE HEIGHT ON THE PLANS FOR THE CLASS K
 FIRE EXTINGUISHER.
  
 NFPA 10 6.1.3.8 INSTALLATION HEIGHT.
 6.1.3.8.1 FIRE EXTINGUISHERS HAVING A GROSS WEIGHT NOT
 EXCEEDING
 40 LB (18.14 KG) SHALL BE INSTALLED SO THAT THE TOP OF
 THE FIRE
 EXTINGUISHER IS NOT MORE THAN 5 FT (1.53 M) ABOVE THE
 FLOOR.
 6.1.3.8.2 FIRE EXTINGUISHERS HAVING A GROSS WEIGHT
 GREATER
 THAN 40 LB (18.14 KG) (EXCEPT WHEELED TYPES) SHALL BE
 INSTALLED
 SO THAT THE TOP OF THE FIRE EXTINGUISHER IS NOT MORE
 THAN 31?2 FT
 (1.07 M) ABOVE THE FLOOR.
  
 3.INDICATE THE HEIGHT ON THE PLANS FOR THE MANUAL
 ACTIVATION.
  
 NFPA 96 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL
 ACTIVATION SHALL
 BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48
 IN.)
 ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE,
 BE LOCATED
 IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 4. PLEASE INDICATE THE COMBUSTIBLITY OF THE SHELF UNDER
 THE HOOD.
  
 NFPA 96 4.2.1 WHERE ENCLOSURES ARE NOT REQUIRED, HOODS,
 GREASE REMOVAL
 DEVICES, EXHAUST FANS, AND DUCTS SHALL HAVE A CLEARANCE
 OF AT
 LEAST 457 MM (18 IN.) TO COMBUSTIBLE MATERIAL, 76 MM (3
 IN.) TO
 LIMITED-COMBUSTIBLE MATERIAL, AND 0 MM (0 IN.) TO
 NONCOMBUSTIBLE
 MATERIAL.
  
 CAITLIN L FRANCIS
 FIRE INVESTIGATOR
 WEST PALM BEACH FIRE RESCUE
 561-804-4728
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-18 Cont ID  
Sent By aoliver Date 2022-07-18 Time 08:08 Rev Time 0.00
Received By aoliver Date 2022-07-13 Time 06:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 16:16 Rev Time 0.00
Received By medwards Date 2022-07-01 Time 12:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 15:59 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 15:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-08 Cont ID  
Sent By medwards Date 2022-07-08 Time 16:16 Rev Time 0.00
Received By medwards Date 2022-07-08 Time 16:16 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy