| 2022-07-05 14:27:22 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, |
| | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1.CLASS K FIRE EXTINGUISHER IS REQUIRED AND MUST BE IN |
| | PLACE TIME OF INSPECTION. |
| | |
| | NFPA 96 10.10.2 CLASS K FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED FOR COOKING |
| | APPLIANCE HAZARDS THAT INVOLVE COMBUSTIBLE COOKING |
| | MEDIA |
| | (VEGETABLE OILS AND ANIMAL OILS AND FATS). |
| | |
| | 2. .INDICATE THE HEIGHT ON THE PLANS FOR THE CLASS K |
| | FIRE EXTINGUISHER. |
| | |
| | NFPA 10 6.1.3.8 INSTALLATION HEIGHT. |
| | 6.1.3.8.1 FIRE EXTINGUISHERS HAVING A GROSS WEIGHT NOT |
| | EXCEEDING |
| | 40 LB (18.14 KG) SHALL BE INSTALLED SO THAT THE TOP OF |
| | THE FIRE |
| | EXTINGUISHER IS NOT MORE THAN 5 FT (1.53 M) ABOVE THE |
| | FLOOR. |
| | 6.1.3.8.2 FIRE EXTINGUISHERS HAVING A GROSS WEIGHT |
| | GREATER |
| | THAN 40 LB (18.14 KG) (EXCEPT WHEELED TYPES) SHALL BE |
| | INSTALLED |
| | SO THAT THE TOP OF THE FIRE EXTINGUISHER IS NOT MORE |
| | THAN 31?2 FT |
| | (1.07 M) ABOVE THE FLOOR. |
| | |
| | 3.INDICATE THE HEIGHT ON THE PLANS FOR THE MANUAL |
| | ACTIVATION. |
| | |
| | NFPA 96 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL |
| | ACTIVATION SHALL |
| | BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN. AND 48 |
| | IN.) |
| | ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT OF A FIRE, |
| | BE LOCATED |
| | IN A PATH OF EGRESS, AND CLEARLY IDENTIFY THE HAZARD |
| | PROTECTED. |
| | |
| | 4. PLEASE INDICATE THE COMBUSTIBLITY OF THE SHELF UNDER |
| | THE HOOD. |
| | |
| | NFPA 96 4.2.1 WHERE ENCLOSURES ARE NOT REQUIRED, HOODS, |
| | GREASE REMOVAL |
| | DEVICES, EXHAUST FANS, AND DUCTS SHALL HAVE A CLEARANCE |
| | OF AT |
| | LEAST 457 MM (18 IN.) TO COMBUSTIBLE MATERIAL, 76 MM (3 |
| | IN.) TO |
| | LIMITED-COMBUSTIBLE MATERIAL, AND 0 MM (0 IN.) TO |
| | NONCOMBUSTIBLE |
| | MATERIAL. |
| | |
| | CAITLIN L FRANCIS |
| | FIRE INVESTIGATOR |
| | WEST PALM BEACH FIRE RESCUE |
| | 561-804-4728 |
| | [email protected] |