| 2023-03-14 09:53:41 | 03/02/2023- MEETING IS REQUESTED WITH THE DESIGNER OF |
| | RECORD BEFORE REVIEW IS COMPLETED!!!!!!!!! |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | ******************************************************* |
| | ******************************************************* |
| | ************************************** |
| | |
| | 3RD REVIEW |
| | DATE: MON. MARCH 20TH / 2023 |
| | ACTION: DENIED |
| | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22061262 |
| | ADD: 1911 N TAMARIND AVE |
| | CONT: BELACRIS CONSTRUCTION |
| | TEL: 305-244-0277 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 03/02/2023- 03/14/2023. MEETING IS REQUESTED WITH THE |
| | DESIGNER OF RECORD BEFORE REVIEW IS COMPLETED!!!!!!!!! |
| | 12 WORKDAYS HAVE PASSED WITH NO CONTACT FROM THE DESIGN |
| | PROFESSIONAL. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | |
| | ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA |
| | STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS??? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | |
| | |
| | 1) 3RD REVIEW. SEE ADDRESSING COMMENT, NOT ADDRESSED. |
| | PLEASE ADDRESS THE ADDRESSING CONCERNS BEING THIS |
| | PROPERTY IS A CORNER PROPERTY WITH MULTIPLE PROPOSED |
| | TENANTS AND USES. 2020 WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED |
| | |
| | 2A) 2ND REQUEST. SHEET A-1.0 CONSTRUCTION TYPE IS |
| | STATED AS CONSTRUCTION TYPE-III-A. THE PLAN STATES THE |
| | COMBUSTIBLE MATERIALS HAS BEEN TREATED TO HAVE AT LEAST |
| | 1-HOUR RATING. WITHOUT HAVING THE SPECIFICATION FOR THE |
| | FIRE RATING PRODUCT AND AT WHAT RATE PER GALLON OR RATE |
| | OF 100 SQ. FT. THE PRODUCT IS TO BE APPLIED, AND THE |
| | FIRE RESISTANT PRODUCT NOT BEING APPLIED IN THE |
| | PRESENCES OF THE FIRE DEPARTMENT AND BUILDING |
| | DEPARTMENT, THIS WILL NEED TO BE COMPLETED UNDER THIS |
| | PERMIT IN THE PRESENCE OF THE INSPECTORS. PLEASE NOTE |
| | TABLE 601 ROOF CONSTRUCTION REQUIRES ALL PLYWOOD ROOF |
| | SHEATHING AND TRUSSES WILL REQUIRE THE FIRE RESISTANCE |
| | TREATMENT SINCE THE CONSTRUCTION TYPE IS LISTED IIIA. |
| | PLEASE IDENTIFY IF THE ROOF FRAMING IS TRUSSES OR HAND |
| | FRAMED ROOF JOIST WHERE BEARING WALLS WILL ALSO BE A |
| | CONCERN, TABLE 602 ALSO REQUIRES 1-HOUR FIRE RESISTANCE |
| | RATING FOR BEARING WALLS. PLEASE NOTE THE NEW EXTERIOR |
| | WALLS WILL REQUIRE A 2-HOUR FIRE RATING AS SHOWN IN THE |
| | LIFE SAFETY PLAN. PLEASE NOTE THE COMMON 8X8X16 INCH |
| | CONCRETE BLOCK DOES NOT CARRY A 2-HOUR FIRE RATING, |
| | APPROXIMATELY A 1-HR RATING. TABLE 722.3.2 PROVIDES THE |
| | MINIMUM EQUIVALENT THICKNESS OF BLOCK AND FOR THE TYPE |
| | OF AGGREGATE USED. |
| | |
| | 2B) NEW COMMENT. FOR THE ADDRESS 1911 THE PLANS STATE A |
| | LEVEL 2 ALTERATION, WHEREAS THE CARPORT IS BEING |
| | CONVERTED FOR A CARPORT OR STORAGE AREA TO AN ENCLOSED |
| | LIVING SPACE, THIS IS CONSIDERED AN ADDITION SEE |
| | DEFINITIONS SECTION 202 OF THE 2020 FBC-BUILDING CODE. |
| | AN EXTENSION OR INCREASE IN FLOOR AREA. ALSO REVIEW IN |
| | THE 2020 FBC-ENERGY CODE. |
| | |
| | 3) 3RD REQUEST. SEMI-COMPLIED. SHEET A-1.0 LIST THE |
| | DIFFERENT TYPE OF OCCUPANCIES, GROUP R3, GROUP R-1 |
| | TRANSIENT, AND MERCANTILE OCCUPANCY. THE FLOOR PLAN |
| | A-2.0 DOES NOT INDICATE WHICH AREAS ARE CONSIDERED R3 |
| | AND R1 TRANSIENT. PLEASE REVIEW SECTION 310.5 |
| | RESIDENTIAL GROUP R-3. BOARDING HOUSES TRANSIENT WITH |
| | 10 OR FEWER OCCUPANTS. |
| | 1ST ROUND OF COMMENTS. THERE IS NO EXISTING FLOOR PLAN |
| | SHEET A-2.0 SHOWS THE PROPOSED FLOOR PLAN WITH THE |
| | PROPOSED BEDROOMS 3 & 4 WHAT WERE THESE AREAS |
| | PREVIOUSLY USED AS? WITH THE NEW PROPOSED USE, THE |
| | PROPERTY LINE IS LISTED AS 2FEET 2 INCHES. THE 2020 |
| | FBC-BUILDING CODE TABLE 602 FIRE-RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON DISTANCE & |
| | TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS |
| | BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING |
| | PROTECTION. THIS SAME WALL THE SURVEY SHOWS |
| | APPROXIMATELY 9 FEET FROM THE PROPERTY LINE, WHY THE |
| | DISCREPANCY? |
| | |
| | |
| | 4A) 3RD REQUEST. SHEET A-2.0 SHOWS ON THE WEST OF THE |
| | BUILDING BETWEEN 8 TO 9 FEET FROM THE PROPERTY LINE, |
| | THE WEST WALL 5 TO 6 FEET FROM THE PROPERTY LINE. THE |
| | 2020 FBC-BUILDING CODE TABLE 602 FIRE-RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON DISTANCE & |
| | TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS |
| | BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING |
| | PROTECTION. PLEASE PROVIDE THE % OF OPENINGS VERSES |
| | WALL AREA. NOTE THE WEST WALL IS NOT SHOWN ON SHEET |
| | A-3.0 ELEVATIONS. |
| | |
| | 4B) 2ND REQUEST. SHEET A-2.0 SHOWS A NEW |
| | SWING-BREAK-AWAY WINDOW PLEASE PROVIDE THE PRODUCT |
| | APPROVAL FOR THIS TYPE WINDOW WITH LARGE MISSILE IMPACT |
| | RESISTANCE TESTING. COMPONENTS & CLADDING. PLEASE |
| | SUBMIT THE COMPONENTS AND CLADDING PRODUCT APPROVALS. |
| | 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 5) 3RD REQUEST. SHEET A-2.0 PLEASE SHOW FOR THE |
| | PROPOSED BEDROOM NUMBER THREE THE NEW LOCATION FOR THE |
| | EGRESS WINDOW IN ACCORDANCE WITH 2020 FBC-BUILDING CODE |
| | 1030.2 & 1030.3. |
| | |
| | 6A) 3RD REQUEST. SHEET A-2.0 PLEASE PROVIDE OCCUPANCY |
| | CLASSIFICATION FOR THE PROPOSED 3 BEDROOMS? 2020 |
| | FBC-BUILDING CODE 310.3 R-1, 310.4 R-2, 310.5 R-3 OR |
| | 310.6 R-4. |
| | |
| | 6B) 3RD REQUEST. DEPENDING ON OCCUPANCY TYPE THERE |
| | MAYBE REQUIREMENTS FOR ACCESSIBILITY. ADDITIONAL |
| | INFORMATION IS REQUIRED. 107.2.1. |
| | |
| | 7A) 3RD REQUEST. SHEET A-2.0 THE PROPOSED 3-BEDROOM |
| | SHOW COMPLIANCE WITH SECTION 420.4 SEPARATION WALLS |
| | (RESIDENTIAL/ MERCANTILE) AND THE REQUIREMENTS FOUND IN |
| | 708.4. SHOW FOR BLOCK OR FOR WOOD BEARING WALL, THIS |
| | WALL IT WOULD APPEAR IS BLOCK. PLEASE NOTE THE COMMON |
| | 8X8X16 INCH CONCRETE BLOCK DOES NOT CARRY A 2-HOUR FIRE |
| | RATING, APPROXIMATELY A 1-HR RATING. TABLE 722.3.2 |
| | PROVIDES THE MINIMUM EQUIVALENT THICKNESS OF BLOCK AND |
| | FOR THE TYPE OF AGGREGATE USED. |
| | |
| | 7B) 3RD REQUEST. PROVIDE THE UL OR GYPSUM ASSOCIATION |
| | LISTING NUMBER FOR THE FIRE PARTITION SEE 708.3 FIRE |
| | RESISTANCE RATING. |
| | |
| | 8A)2ND REQUEST. SHEET A-2.0 FLOOR PLAN THE EXISTING |
| | FRONT PORCH AT 3-BEDROOM UNIT INDICATES NEW GWB (GYPSUM |
| | WALL BOARD) BUILDOUT OVER EXISTING STRUCTURAL COLUMN. |
| | GYPSUM WALL BOARD IS USED FOR INTERIOR WALLS AND |
| | CEILINGS. GYPSUM SHEATHING IS FOR EXTERIOR USE WITH A |
| | STUCCO OR SIMILAR FINISH PRODUCT. PLEASE ALSO PROVIDE |
| | THE FRAMING SINCE THIS IS AN EXTERIOR ELEMENT, 170 VULT |
| | WIND SPEED. |
| | |
| | 8B) 3RD REQUEST. PROVIDE COMPLIANCE WITH FBC-BUILDING |
| | SECTION 420.6 FIRE & SMOKE ALARMS. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) 3RD REQUEST. SHEET LIFE SAFETY PLAN WHAT APPEARS TO |
| | BE A LIVE/ WORK UNIT (BEDROOM 2) THAT WILL NEED SHOW |
| | COMPLIANCE WITH THE 2020 FBC-BUILDING CODE SECTION 419. |
| | SHEET A-2.0 SHOWS A 2ND OFFICE, DISCREPANCY IN PLANS. |
| | 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION |
| | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 10A) 3RD REQUEST. SHOW AREA LIMITATIONS IN ACCORDANCE |
| | WITH 419.1.1 LIMITATIONS. 410.1.1.2 THE NONRESIDENTIAL |
| | AREA IS PERMITTED TO BE NOT MORE THAN 50 PER CENT OF |
| | THE AREA OF EACH LIVE WORK UNIT. |
| | 10A) (1) LIVE WORK LOFT. 419.9 LIVE WORK LOFT, |
| | PLUMBING. WHERE THE NONRESIDENTIAL AREA OF THE LIVE/ |
| | WORK LOFT UNIT IS REQUIRED TO BE ACCESSIBLE (BATHROOM) |
| | BY THE FLORIDA BUILDING CODE, ACCESSIBILITY, THE |
| | PLUMBING FIXTURES SPECIFIED BY THE CHAPTER 29 SHALL BE |
| | ACCESSIBLE. |
| | 10A)(2) LIVE/ WORK LOFT. 419.5 FIRE ALARM, FIRE |
| | PROTECTION. |
| | |
| | 10A)(3) LIVE / WORK LOFT, 419.2. OCCUPANCIES. LIVE/ |
| | WORK LOFTS ARE CONSIDERED A R2 OCCUPANCY AND NEED TO |
| | MEET THE OCCUPANCY SEPARATION REQUIREMENTS FOUND IN |
| | 420. |
| | 10A)(4) IF THIS UNIT IS TO BE CONSIDERED A LIVE / WORK |
| | LOFT THEN COMPLIANCE WITH THE 2020 FBC-BUILDING SECTION |
| | 1030.1- 1030.5.1. ARE REQUIRED. |
| | |
| | 10B) 3RD REQUEST. THE FLOOR PLAN SHOWS 3 EGRESSES TO |
| | THE COMMERCIAL AREA ACCESSIBLE BY THE PUBLIC. AT LEAST |
| | ONE ENTRANCE NEEDS TO BE A ACCESSIBLE ENTRANCE LEVEL |
| | WITH THE EXTERIOR OF THE BUILDING. 2020 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | NEW BUILDINGS ONLY, SEE EXCEPTIONS IN EXISTING |
| | BUILDINGS. |
| | |
| | 10C) 3RD REQUEST. THE FLOOR PLAN SHOWS A POWDER ROOM |
| | WITH A LAV AND WATER CLOSET, DOES NOT MEET SECTION |
| | CLEARANCES AT WATER CLOSETS. 604.3 CLEARANCE. |
| | CLEARANCES AROUND THE WATER CLOSETS AND IN TOILET |
| | COMPARTMENTS SHALL COMPLY WITH 604.3. THE FLOOR PLAN |
| | SHOWS THE WIDTH OF THE RESTROOM AS 6 FEET 3 INCHES, |
| | MINIMUM WIDTH FINISH WALL IS 7 FEET 1 INCH. |
| | 2ND REQUEST. 604.3.1. SIZE. CLEARANCE AROUND A WATER |
| | CLOSET SHALL BE 60 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES MINIMUM |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 10D) COMPLIED. |
| | |
| | 10E) 3RD REQUEST. 2020 FBC-B 1210.2.2. WALLS & |
| | PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| | OFFICIAL INTERPRETATION ON 06/2020. IN BATHROOMS, |
| | RESTROOMS & SERVICE SINK AREAS EPOXY PAINT IS NO LONGER |
| | CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE |
| | SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 10F) 3RD REQUEST. THE FLOOR PLAN FOR THE LIVE/ WORK |
| | UNIT NEEDS TO SHOW COMPLIANCE WITH 420 FIRE & SMOKE |
| | ALARMS. |
| | |
| | 10G) 3RD REQUEST. A-2. THE COVERSHEET LIST A WORK LIVE |
| | LOFT BUT THERE IS NO RESIDENTIAL ELEMENT IN THE |
| | MERCANTILE AREA LISTED AS OFFICE OR BUSINESS OCCUPANCY. |
| | 2ND REQUEST. SHEET A-2.0 THE LIVE/ WORK UNIT BEDROOM # |
| | 2 DOES NOT HAVE AT LEAST ONE EMERGENCY ESCAPE AND |
| | RESCUE OPENING, 2020 FBC-BUILDING SECTION 1030.1 & |
| | 1030.2. |
| | |
| | 11) 3RD REQUEST. ARIEL VIEW OF THE PROPERTY SHOWS IN |
| | THE MIDDLE OF THE RETAIL AREA WHAT APPEARS A BEARING |
| | WALL ABOVE THE ROOF LINE PARALLEL WITH STATE ST. THERE |
| | IS NO MENTION OF WHERE THIS WALL IS IN THE FLOOR PLAN, |
| | ALREADY REMODELED? 107.2.1. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 12) 3RD REQUEST SHEETS A-3.0 & A-4.0 BOTH SHOW EXTERIOR |
| | ELEVATIONS AND NEW EXTERIOR OPENINGS, WINDOWS AND |
| | DOORS. THERE IS NO WIND DESIGN CRITERIA. 2020 FBC-B |
| | 1603.1.4 WIND DESIGN CRITERIA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 12.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| | GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 12.2. RISK CATEGORY. |
| | |
| | 12.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | |
| | 12.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 12.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 12.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 13) . 3RD REQUEST. PLEASE SUBMIT THE COMPONENTS AND |
| | CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS |
| | |
| | 14) 3RD REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 15A) 2ND REQUEST. NOT ADDRESSED. SHEET A-3.0 ELEVATIONS |
| | SHOWS THE NORTH ELEVATION TO THE LEFT OF THE BUILDING |
| | PEOPLE ARE WALKING ON THE PUBLIC SIDEWALK ELEVATION 0 |
| | INCHES-0 FEET. THE NEW DOORS IN THE EXISTING OPENINGS |
| | SHOW A DOOR STOOP APPROXIMATELY 4 INCHES IN HEIGHT NONE |
| | OF THE DOORWAYS INTO ANY OF THE OFFICES OR LIVE/ WORK |
| | LOFT ARE ACCESSIBLE. GOOGLE MAPS SHOW THE DOORWAYS |
| | ELEVATED APPROXIMATELY 4 INCHES ABOVE THE SIDEWALK. |
| | 2020 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). 2020 FBC-ACCESS. CODE |
| | CHANGES IN LEVEL 303.2 AND 303.3. WHERE CHANGES IN |
| | LEVEL ARE PERMITTED IN THE FLOOR OR GROUND SURFACES, |
| | THEY SHALL COMPLY WITH SECTION 303. SEE 303.1 & 303.2. |
| | |
| | 15B) 2ND REQUEST. 2020 ACCESS. CODE 404.2.3. CLEAR |
| | WIDTH & SIZE OF DOORS, 2020 FBC-B 1010.1.1. WHERE THIS |
| | SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32- INCHES OR |
| | A 34-INCH DOOR MINIMUM. THE MINIMUM SIZE OF A SWING |
| | DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY WITH THE |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 15C) 2ND REQUEST. SHEET A-2.0 DOOR E102 & DOOR E103 |
| | SWING OUT OVER THE PROPERTY LINE. SEE THE 2020 |
| | FBC-BUILDING CODE SECTION 3202.2 DOORS SHALL NOT OPEN |
| | OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 16) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |