Plan Review Details - Permit 22061239
Plan Review Stops For Permit 22061239
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 13:22 Rev Time 0.00
Received By shill Date 2022-09-01 Time 13:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 17:51 Rev Time 0.00
Received By shill Date 2022-08-03 Time 17:51 Sent To  
Notes
2022-08-03 17:52:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS471, PLANS ARE NOT DIGITALLY SIGNED. UPLOAD
 DIGITALLY SIGNED DOCUMENTS.
  
 2ND REVIEW, THE PLANS STATE THEY ARE DIGITALLY SIGNED
 BUT LACK A DIGITAL SIGNATURE.
  
 PLEASE EMAIL TO [email protected] FOR VERIFICATION PRIOR TO
 RESUBMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 17:52 Rev Time 0.00
Received By shill Date 2022-07-26 Time 17:52 Sent To  
Notes
2022-07-26 17:56:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FS471, THE PLANS ARE NOT DIGITALLY SIGNED. THEY
 INCLUDE THE IMAGE OF THE DIGITAL SIGNATURE BUT THE
 CERTIFICATE HAS BEEN REMOVED. UPLOAD DIGITALLY SIGNED
 PLANS.
  
 IF YOU 'D LIKE FOR ME TO VERIFY THE DIGITAL SIGNATURE,
 EMAIL ONE PAGE TO ME AT [email protected].
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 16:36 Rev Time 0.00
Received By jleahy Date 2022-09-19 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By jleahy Date 2022-08-06 Time 17:49 Rev Time 0.00
Received By jleahy Date 2022-08-06 Time 17:49 Sent To  
Notes
2022-08-06 17:50:28PLANS NOT DIGITALLY SIGNED JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By jleahy Date 2022-07-25 Time 11:50 Rev Time 0.00
Received By jleahy Date 2022-07-22 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 16:36 Rev Time 0.00
Received By jleahy Date 2022-08-24 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-10 Cont ID  
Sent By lmarchan Date 2022-08-10 Time 13:49 Rev Time 0.00
Received By lmarchan Date 2022-08-01 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 17:56 Rev Time 0.00
Received By shill Date 2022-07-05 Time 07:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 13:22 Rev Time 0.00
Received By shill Date 2022-09-01 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 17:52 Rev Time 0.00
Received By shill Date 2022-08-03 Time 17:52 Sent To  
Notes
2022-08-03 17:52:20SEE BUILDING

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By jleahy Date 2022-07-25 Time 11:51 Rev Time 0.00
Received By jleahy Date 2022-07-25 Time 11:51 Sent To  
Notes
2022-07-25 11:52:09ELECTRONIC SEALS AND SIGNATURES ARE FOR USE ON
 ELECTRONIC PLANS AND DOCUMENTS, COPIED ELECTRONIC SEALS
 ARE NOT PERMITTED PER SECTION 61G15-23.005 FAC.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE(S) SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By vbroglia Date 2022-08-10 Time 12:53 Rev Time 0.00
Received By vbroglia Date 2022-08-10 Time 12:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-12 Cont ID  
Sent By vbroglia Date 2022-07-12 Time 16:44 Rev Time 0.00
Received By vbroglia Date 2022-07-12 Time 16:44 Sent To  
Notes
***NONE***