Plan Review Details - Permit 22061227
Plan Review Stops For Permit 22061227
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-27 Cont ID  
Sent By cthroop Date 2022-09-27 Time 11:07 Rev Time 0.00
Received By cthroop Date 2022-09-27 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 06:58 Rev Time 0.00
Received By shill Date 2022-07-25 Time 06:43 Sent To  
Notes
2022-07-25 07:00:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLEASE ADD A GENERAL NOTE THAT THE POOL IS DESIGNED
 IN ACCORDANCE WITH ANSI/APSP/ICC3,4,5,6,7, FBC R
 4501.6, OR ADVISE WHERE I CAN LOCATE THIS ON THE PLAN.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By ppetty Date 2022-10-04 Time 11:55 Rev Time 0.00
Received By ppetty Date 2022-10-04 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By ppetty Date 2022-07-18 Time 10:34 Rev Time 0.00
Received By ppetty Date 2022-07-18 Time 09:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 17:01 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 17:01 Sent To  
Notes
2022-09-16 17:02:39A SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING TO THE
 POOL HEATER.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-09-30 Cont ID  
Sent By amhamilt Date 2022-09-30 Time 12:23 Rev Time 0.00
Received By amhamilt Date 2022-09-30 Time 12:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By amhamilt Date 2022-07-08 Time 11:19 Rev Time 0.00
Received By amhamilt Date 2022-07-08 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-10-17 Time   Rev Time 0.00
Received By aoliver Date 2022-10-12 Time 06:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-04 Cont ID  
Sent By ppetty Date 2022-10-04 Time 11:55 Rev Time 0.00
Received By ppetty Date 2022-09-14 Time 11:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 07:00 Rev Time 0.00
Received By shill Date 2022-06-27 Time 06:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By ccole Date 2022-10-17 Time 13:14 Rev Time 0.00
Received By ccole Date 2022-10-17 Time 13:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-16 Cont ID  
Sent By ccole Date 2022-09-16 Time 17:03 Rev Time 0.00
Received By ccole Date 2022-09-16 Time 16:45 Sent To  
Notes
2022-09-16 17:19:322ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060432
 9/16/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: 2ND REQUEST FOR TDH CALCULATIONS- SECS.
 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3
 FBC RES. THE REVISED PLAN SHOWS 60 TDH, HOWEVER
 SUB-TOTALS FOR PRESSURE AND SUCTION LINES AND FITTINGS
 WERE NOT PROVIDED.
  
 2) SHEET 2: THE PIPE VELOCITY CALCULATIONS SHOWING A
 2-INCH PIPE AT 11.22 FPS IS NOT IN COMPLIANCE WITH
 SEC.R4501.6.3 FBC RES WHICH LIMITS PIPE VELOCITY TO 10
 FPS FOR PRESSURE PIPING.
  
 3) SHEET 2: 2ND REQUEST FOR THE AQUASTAR CHANNEL DRAIN
 SPECS AND/OR LIST THE FLOW RATE OF THE ASSEMBLY ON THE
 PLAN- SECS. R4501.6.2, R4501.6.6 FBC RES.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-01 Cont ID  
Sent By ccole Date 2022-07-01 Time 11:23 Rev Time 0.00
Received By ccole Date 2022-07-01 Time 10:51 Sent To  
Notes
2022-07-01 11:26:151ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22060432
 6/22/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: PROVIDE TDH CALCULATIONS- SECS. 4.4.9,
 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 FBC
 RES.
  
 2) SHEET 2: PROVIDE THE PUMP CURVE ON THE SHEET MARKED
 UP TO SHOW THE TDH AND FLOW RATE OF THE SYSTEM- SECS.
 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3
 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMP,
 FILTER, CHLORINATOR, HEATER, AND MAIN DRAIN ASSEMBLIES-
 SECS. R4501.6.2, R4501.6.6 FBC RES.
  
 4) PLEASE NOTE THAT THE GAS HEATER SHALL BE INSTALLED
 UNDER A SEPARATE PERMIT- SECS. 105.1, 107.2.1,
 107.3.5.3 WPB.
  
 5) PLEASE NOTE AN RPZ BACKFLOW PREVENTER SHALL BE
 INSTALLED AT THE METER TO PROTECT THE POTABLE WATER
 SERVICE- SECS. C, D, & E WPB CROSS CONNECTION MANUAL.
 THE DEVICE SHALL BE INSTALLED UNDER A SEPARATE. A PVB
 BACKFLOW DEVICE IS ALSO REQUIRED FOR AUTOFILL
 INSTALLATIONS- SEC. P2908.3 FBC RES.
  
 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SEC.
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By ccole Date 2022-10-17 Time 13:18 Rev Time 0.00
Received By ccole Date 2022-10-17 Time 13:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By ppetty Date 2022-10-04 Time 11:55 Rev Time 0.00
Received By ppetty Date 2022-10-04 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By shill Date 2022-07-25 Time 06:43 Rev Time 0.00
Received By shill Date 2022-07-25 Time 06:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-09-20 Cont ID  
Sent By afowlkes Date 2022-09-20 Time 11:56 Rev Time 0.00
Received By afowlkes Date 2022-09-20 Time 11:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By afowlkes Date 2022-07-05 Time 14:36 Rev Time 0.00
Received By afowlkes Date 2022-07-05 Time 14:36 Sent To  
Notes
***NONE***