Plan Review Details - Permit 22061169
Plan Review Stops For Permit 22061169
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-10 Cont ID  
Sent By rmcphers Date 2022-08-10 Time 10:25 Rev Time 0.00
Received By rmcphers Date 2022-08-10 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-04 Cont ID  
Sent By rmcphers Date 2022-08-04 Time 10:51 Rev Time 0.00
Received By rmcphers Date 2022-08-04 Time 10:51 Sent To  
Notes
2022-08-04 10:53:35 
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) REVISED DRAWING A4.22 AND A4.23 - FBC 604.8.2.1
 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2022-07-11 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By jleahy Date 2022-07-18 Time 08:01 Rev Time 0.00
Received By jleahy Date 2022-07-18 Time 07:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-25 Cont ID  
Sent By pleduc Date 2022-07-25 Time   Rev Time 0.00
Received By pleduc Date 2022-07-25 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-28 Cont ID  
Sent By pleduc Date 2022-06-28 Time   Rev Time 0.00
Received By pleduc Date 2022-06-28 Time 14:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By rmcphers Date 2022-08-04 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2022-07-22 Time 08:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By jleahy Date 2022-07-18 Time 08:01 Rev Time 0.00
Received By jleahy Date 2022-06-27 Time 12:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By medwards Date 2022-07-01 Time 09:03 Rev Time 0.00
Received By medwards Date 2022-07-01 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By ccole Date 2022-07-27 Time 13:50 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 13:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-01 Cont ID  
Sent By ccole Date 2022-07-01 Time 13:33 Rev Time 0.00
Received By ccole Date 2022-07-01 Time 12:29 Sent To  
Notes
2022-07-01 13:34:511ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22061169
 7/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ARCHITECTURAL AND PLUMBING PLAN SHEETS: A MINIMUM OF
 ONE AMBULATORY ACCESSIBLE WATER CLOSET COMPARTMENT EACH
 SHALL BE INSTALLED IN THE MEN'S AND WOMEN'S RESTROOMS
 #139 & 140- SEC. 213.3.1 FBC ACC. REVISE THE PLANS AND
 DETAILS TO SHOW COMPLIANCE WITH SECS. 604.8.2-
 604.8.2.3 FBC ACC.
  
 2) SHEET A4.24: REFER TO SECTIONS 306, 307, AND 602 FBC
 ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS
 AND ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES,
 SPOUT HEIGHTS, AND SPOUT LOCATIONS. INDICATE COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 3) INSTALLATION OF NEW FIXTURE DRAIN OUTLETS WILL
 REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 4) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAILS ON THE PLAN- SECTION
 315.1 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By ccole Date 2022-07-27 Time 13:50 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 13:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-11 Cont ID  
Sent By rmcphers Date 2022-07-11 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2022-07-11 Time 10:05 Sent To  
Notes
2022-07-01 09:04:12MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-30 Cont ID  
Sent By eschneid Date 2022-06-30 Time 12:27 Rev Time 0.25
Received By eschneid Date 2022-06-30 Time 12:27 Sent To  
Notes
***NONE***