| 2022-06-28 15:13:11 | FIRE PROVISO: |
| | |
| | 1) THERE IS AN INDICATION OF SPRINKLER HEADS AT THE TOP |
| | OF THE ELEVATOR SHAFT |
| | |
| | THESE HEADS MAY NOT BE REQUIRED. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLAINCE. |
| | |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR MACHINE ROOMS, ELEVATOR |
| | MACHINERY SPACES, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE APPLICABLE PROVISIONS IN NFPA 101, OR THE |
| | APPLICABLE BUILDING CODE, WHERE ALL OF THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION ELEVATOR IS DEDICATED TO ELEVATOR EQUIPMENT |
| | ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL |
| | SPACE, OR HOISTWAY OF TRACTION ELEVATORS ARE PROTECTED |
| | BY SMOKE DETECTORS, OR OTHER AUTO MATIC FIRE DETECTION, |
| | INSTALLED IN ACCORDANCE WITH NFPA 72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, OR HOISTWAY OF TRACTION ELEVA TORS IS SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY WALLS AND |
| | FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS THAN THAT SPECIFIED BY THE |
| | APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED TO BE STORED IN ELEVATOR |
| | MACHINE ROOMS, MACHINERY SPACES, CONTROL ROOMS, CONTROL |
| | SPACES, OR HOISTWAYS OF TRAC TION ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |