Plan Review Details - Permit 22061138
Plan Review Stops For Permit 22061138
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-30 Cont ID  
Sent By shill Date 2022-09-30 Time 09:21 Rev Time 0.00
Received By shill Date 2022-09-30 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 17:56 Rev Time 0.00
Received By shill Date 2022-08-29 Time 17:10 Sent To  
Notes
2022-08-29 18:02:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SEE PREVIOUS LIST.
  
 ENGINEER'S RESPONSES WITH ADDITIONAL PLAN REVIEW
 QUESTIONS/STATEMENTS:
 A. IN THE PROPOSED CLADDING AND GRATING SPECIFIED IN
 THE SCREEN WALL DESIGN BY APX, THE RESIN MATERIAL USED
 IS NOT COMBUSTIBLE AS IT IS CLASSIFIED AS
 ?SELF-EXTINGUISHING? AND ?FIRE RETARDANT?,
 RESPECTIVELY. PLEASE REFERENCE THE ATTACHED MATERIAL
 SPECIFICATIONS FOR FURTHER INFORMATION.
  
 2ND REVIEW: PLEASE SEE PAGE 15-2 OF THE DOCUMENT NAMED
 "SCREEN WALL DESIGN" WHERE IT STATES:
  
 "COMPOSOLITE? IS AVAILABLE IN EITHER POLYESTER,
 POLYESTER FIRE RETARDANT, OR VINYL ESTER RESIN SYSTEMS.
 IT IS STOCKED IN THE POLYESTER FIRE RETARDANT RESIN
 SYSTEM IN SLATE GRAY COLOR. THE STANDARD FIRE RETARDANT
 RESINS MEET THE REQUIREMENTS OF CLASS 1 RATING OF 25 OR
 LESS PER ASTM E-84 AND THE SELF-EXTINGUISHING
 REQUIREMENTS OF ASTM D-635. THE RESIN MIXTURE IS UV
 INHIBITED AND THE COMPOSITE INCLUDES A SURFACE
 VEIL ON ALL EXPOSED SURFACES FOR ENHANCED CORROSION AND
 UV PROTECTION."
  
 SEE FBC B 1510.6 (VIA FBC B 1510.8.4), THE SCREEN
 WALL/FENCE IS TO BE CONSTRUCTED OF THE SAME MATERIAL
 SPECIFIED FOR EXTERIOR WALLS, EXCEPTION IS 5' AWAY FROM
 PROPERTY LINE. THE WALLS MAY HAVE A FIRE RATING
 REQUIREMENT. SINCE LIMITED INFORMATION ABOUT THE
 BUILDING WAS PROVIDED, COMPLIANCE NOT CLEAR. THIS
 BUILDING APPEARS TO BE A HIGH RISE, THE FENCE WOULD BE
 CONSIDERED A NON BEARING WALL, EITHER 1 OR 0 HOUR
 RATING REQUIRED. IT IS POSSIBLE THAT FBC 104.11
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT COULD BE CONSIDERED
 (REQUIRED BUILDING OFFICIAL APPROVAL), BUT THE STARTING
 POINT IS THE BASIC INFORMATION ABOUT THE BUILDING AND
 THE MATERIALS PROPOSED.
  
 PLEASE SEE FBC B 603.1 WHICH LISTS THE COMBUSTIBLE
 MATERIALS PERMITTED IN TYPES I AND II CONSTRUCTION. IF
 YOU WOULD LIKE FOR THE SCREEN WALL TO BE CONSIDERED AS
 ONE OF THE LISTED ALLOWABLE MATERIALS, ENOUGH
 INFORMATION REGARDING THE WALL PANELS AND THE GRATING
 NEEDS TO BE PROVIDED FOR THE BUILDING OFFICIAL TO MAKE
 A DETERMINATION. THIS MAY BE SENT VIA EMAIL PRIOR TO
 RESUBMITTING. IF YOU ELECT TO DO SO, AND I DO NOT
 RESPOND TO YOUR EMAIL TIMELY, PLEASE CALL 561-805-6727
 AND ASK FOR PLANS EXAMINER ON CALL TO REQUEST THAT I
 RESPOND TO YOUR EMAIL. I AM CURRENTLY WORKING ON
 SOFTWARE IMPLEMENTATION AND MY RESPONSE TO EMAIL MAY BE
 DELAYED.
  
 I COULD NOT LOCATE THE SPECIFIC TYPE OF COMPOSOLITE
 (WALL PANEL) PROPOSED ON THE PLAN. SINCE IT APPEARS
 THAT THE PANELS ARE AVAILABLE IN BOTH FIRE RETARDANT
 AND NON-FIRE RETARDANT MATERIALS, THE PLANS SHOULD BE
 SPECIFIC AS TO WHAT IS PROPOSED.
  
 I COULD NOT LOCATE INFORMATION REGARDING THE FIBERGLASS
 GRATING (FIRE RESISTANCE) IN THE SUBMITTAL, PLEASE
 DIRECT AS TO WHERE THIS CAN BE FOUND OR PROVIDE.
  
 B. ENGINEER'S RSEPONSE - IT IS OUR UNDERSTANDING THAT
 THE EQUIPMENT UPGRADE PLANS PREPARED BY USA ENGINEERING
 WERE INCLUDED WITH THIS SUBMITTAL, WHICH DEPICT
 INFORMATION REGARDING THE EXISTING SUPPORTING BUILDING.
  
 2ND REVIEW - I WAS UNABLE TO LOCATE THE DISTANCE TO THE
 PROPERTY LINE INFORMATION (APPEARS TO BE ZERO) OR THE
 INFORMATION REGARDING BUILDING TYPE (APPEARS TO BE NON
 COMBUSTIBLE HIGH RISE). PLEASE DIRECT AS TO WHERE THIS
 INFORMATION CAN BE LOCATED OR REVISE PLAN TO INCLUDE.
  
 C. ENGINEER'S RESPONSE - THE SPECIFICATIONS FOR THE
 PROPOSED RADIOFREQUENCY TRANSPARENT CLADDING WERE
 INCLUDED IN THE CALCULATIONS OF THE PROPOSED SCREEN
 WALL PREPARED BY APX BEGINNING ON PAGE 42 OF 71.
 REFERENCE RESPONSE #1A REGARDING THE GRATING
 SPECIFICATIONS.
  
 CALCULATIONS APPEAR TO BE PRIMARILY STRUCTURAL AND ARE
 ACCEPTABLE. ADDITIONAL INFORMATION IS NEEDED REGARDING
 FIRE RESISTANCE.
  
 D. FBC 1510.6 APPLIES TO MECHANICAL EQUIPMENT SCREENS
 WHEREAS THE PROPOSED STRUCTURE IS AN ANTENNA SUPPORTING
 STRUCTURE OF ?SPECIAL CONSTRUCTION? IN ACCORDANCE WITH
 FBC 3101.1 THAT ALSO PROVIDES CONCEALMENT OF SAID
 ANTENNAS AS REQUIRED BY CITY OF WEST PALM BEACH CODE
 SECTION 94- 333(5). THEREFORE, FBC 1510.6 IS NOT
 APPLICABLE TO THIS INSTALLATION AS THE MATERIALS
 REQUIRED THEREIN WOULD RENDER THESES ANTENNA
 CONCEALMENT WALLS USELESS AS A RESULT OF IMPEDING THEIR
 SIGNAL PASSAGE THROUGH THE MATERIAL.
  
 MY APOLOGIES FOR AN INCOMPLETE CODE REFERENCE, SEE FBC
 B 1510.8.4 (FENCES AND SIMILAR STRUCTURES) WHICH REFERS
 TO 1510.6. IT APPEARS THAT THIS PRODUCT DOES NOT HAVE A
 FIRE RATING, APPEARS TO HAVE A CLASS A FLAME SPREAD,
 WHICH MAY BE CONSIDERED, SEE ITEM A.
  
 RADIOFREQUENCY AND MUNICIPAL ORDINANCE ARE NOT
 CONSIDERATIONS FOR THIS PLAN REVIEW. THE PROPOSED
 INSTALLATION IS TO COMPLY WITH THE FLORIDA BUILDING
 CODE, ONLY FBC REQUIREMENTS WILL BE ADDRESSED. I HAVE
 DIRECTED YOU TO POSSIBLE OPTIONS IN FBC B 603. HOWEVER
 IT IS THE DESIGNER'S RESPONSIBLITY TO FIND A CODE
 COMPLIANT OPTION WHICH ALSO COMPLIES WITH OTHER
 REQUIREMENTS SUCH AS THE OWNER'S NEEDS AND
 PLANNING/ZONING REQUIREMENTS. PLEASE FEEL FREE TO
 CONTACT ME IF YOU WISH TO DISCUSS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 08:50 Rev Time 0.00
Received By shill Date 2022-08-03 Time 08:44 Sent To  
Notes
2022-08-03 08:50:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, IT APPEARS THAT A SCREEN WITH COMBUSTIBLE
 MATERIALS IS PROPOSED (REFERENCE TO TRANSPARENT
 CLADDING AND FIBERGLASS GRATING ON C4), REVISE PLAN TO
 INCLUDE BUILDING HEIGHT AND AREA, BUILDING TYPE, SITE
 PLAN SHOWING THE DISTANCE OF THE BUILDING TO THE
 PROPERTY LINE. PROVIDE SPECIFICATIONS FOR THE RADIO
 FREQUENCY TRANSPARENT CLADDING AND FIBERGLASS GRATING.
 ADDITIONAL INFORMATION IS REQUIRED BEFORE A PLAN REVIEW
 CAN BE COMPLETED.
  
 SEE FBC B 1510.6 FOR REQUIREMENTS FOR MECHANICAL
 EQUIPMENT SCREENS. REVISE PLAN TO CLEARLY DEMONSTRATE
 CODE COMPLIANCE.
  
 2. FBC 107, IF POSSIBLE, WHEN RESUBMITTING PLEASE
 UPLOAD INDIVIDUALLY SIGNED AND SEALED PAGES FOR THE
 SCREEN.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-03 Cont ID  
Sent By jleahy Date 2022-10-03 Time 08:35 Rev Time 0.00
Received By jleahy Date 2022-09-30 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 09:11 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 08:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By pleduc Date 2022-09-21 Time   Rev Time 0.00
Received By pleduc Date 2022-09-21 Time 13:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By pleduc Date 2022-07-18 Time   Rev Time 0.00
Received By pleduc Date 2022-07-18 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-03 Cont ID  
Sent By jleahy Date 2022-10-03 Time 08:36 Rev Time 0.00
Received By jleahy Date 2022-09-20 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 18:02 Rev Time 0.00
Received By shill Date 2022-08-19 Time 06:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-15 Cont ID  
Sent By afowlkes Date 2022-08-15 Time 15:29 Rev Time 0.00
Received By afowlkes Date 2022-07-15 Time 09:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-30 Cont ID  
Sent By shill Date 2022-09-30 Time 09:23 Rev Time 0.00
Received By shill Date 2022-09-30 Time 09:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 18:02 Rev Time 0.00
Received By shill Date 2022-08-29 Time 18:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 09:02 Rev Time 0.00
Received By shill Date 2022-08-03 Time 09:02 Sent To  
Notes
2022-08-03 09:06:35A MULTIPAGE PDF WAS SUBMITTED FOR THE EQUIPMENT SCREEN.
 SINCE IT APPEARS THAT PAGES WILL BE REVISED, IF
 POSSIBLE, WHEN RESUBMITTING PLEASE UPLOAD EACH PAGE
 DIGITALLY SIGNED TO FACILITATE PLAN REVIEW.
  
 DIGITAL SIGNATURE FOR EQUIPMENT OK
 DIGITAL SIGNATURE FOR SCREEN ENGINEERING OK
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-08-15 Cont ID  
Sent By ckimmerl Date 2022-08-15 Time 15:29 Rev Time 0.00
Received By afowlkes Date 2022-08-15 Time 15:29 Sent To  
Notes
***NONE***