Plan Review Details - Permit 22061099
Plan Review Stops For Permit 22061099
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-07-21 Cont ID  
Sent By pleduc Date 2022-07-21 Time   Rev Time 0.00
Received By pleduc Date 2022-07-21 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-07-15 Cont ID  
Sent By pleduc Date 2022-07-15 Time   Rev Time 0.00
Received By pleduc Date 2022-07-15 Time 11:26 Sent To  
Notes
2022-07-15 12:04:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THANK YOU FOR THE RESPONSE COMMENTS; HOWEVER, I AM
 AWARE OF THE CALCULATIONS INDICATED.
  
 I APOLOGIZE IF I AM MISSING THE INFORMATION NEEDED TO
 ENSURE THE VERTICAL & HORIZONTAL DUCT LENGHTS
 (ESPECIALLY TO THE ROOF) WILL NOT HINDER VENTILATION.
  
 WHAT IS NOT INDICATED IS THE ACTUAL LENGHTS, HORIZONTAL
 & VERTICAL AND IN TOTAL, (ESPECIALLY TO THE ROOF) OF
 THE PROPOSED DUCT WORK AND THE CALULATIONS INDICATING
 THAT THERE IS SUFFICIENT AIRFLOW TO ENSURE THE GREASE
 VAPORS ARE EXHAUSTED AND OR THERE IS NO EXXCESSIVE
 HEAT/SMOKE/VAPORS IN THE KITCHEN.
  
 FOR THE OFFICIAL RECORD PLEASE PROVIDE THE CALCULATIONS
 INDICATING THE DUCT LENGHTS AS PART OF THE
 CALCULATIONS.
  
  
 2) THE PAGE 2 OF 5, IF NOT APPLICABLE TO YOUR PROJECT
 NEEDS TO BE REMOVED FROM THE SUBMITTAL.
  
 PLEASE REMOVE THAT PAGE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By pleduc Date 2022-06-29 Time   Rev Time 0.00
Received By pleduc Date 2022-06-28 Time 15:27 Sent To  
Notes
2022-06-28 15:53:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF AN EXTENDED LENGTH OF
 EXHAUST DUCT VERTICAL & HORIZONTAL.
  
 PER NFPA 96
  
 8.2.1 AIR VELOCITY.
 8.2.1.1* THE AIR VELOCITY THROUGH ANY DUCT SHALL BE NOT
 LESS
 THAN 152.4 M/MIN (500 FT/MIN).
  
 8.2.2 AIR VOLUME.
 8.2.2.1 EXHAUST AIR VOLUMES FOR HOODS SHALL BE OF A
 SUFFICIENT
 LEVEL TO PROVIDE FOR CAPTURE AND REMOVAL OF
 GREASE-LADEN COOK ING VAPORS.
 8.2.2.2* TEST DATA, PERFORMANCE TESTS ACCEPTABLE TO THE
 AUTHOR ITY HAVING JURISDICTION, OR BOTH SHALL BE
 DISPLAYED, PROVIDED ON
 REQUEST, OR BOTH.
  
 PLEASE PROVIDE THE DATA EQUATION DETAILS IN COMPLIANCE.
  
  
 2) THERE IS AN INDICATION OF AN EXTENDED LENGTH OF
 MAKEUP AIR DUCT VERTICAL & HORIZONTAL.
  
 8.3* REPLACEMENT AIR.
 8.3.1 REPLACEMENT AIR QUANTITY SHALL BE ADEQUATE TO
 PREVENT
 NEGATIVE PRESSURES IN THE COMMERCIAL COOKING AREA(S)
 FROM
 EXCEEDING 4.98 PA (0.02 IN. WATER COLUMN).
  
 PLEASE PROVIDE THE DATA EQUATION DETAILS IN COMPLIANCE.
  
  
 3) THERE ARE INDICATIONS OF SUPPRESSION PIPING PAGE
 THAT HAS A SEPARATE ADDRESS WITHIN THE TITLE BLOCK -
 O'BRIENS RESIDENCE - CRAFT MASTER CUSTOM POOLS
  
 PLEASE REVIEW AND CORRECT/REMOVE.
  
  
  
 4) THE SUPPRESSION SYSTEM FOR THIS PROPOSED HOOD SHALL
 BE SUBMITTED UNDER SEPARATE PERMIT & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-21 Cont ID  
Sent By lmarchan Date 2022-07-21 Time 16:21 Rev Time 0.00
Received By lmarchan Date 2022-07-19 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-18 Cont ID  
Sent By aoliver Date 2022-07-18 Time 08:13 Rev Time 0.00
Received By aoliver Date 2022-07-14 Time 06:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-01 Cont ID  
Sent By medwards Date 2022-07-01 Time 14:06 Rev Time 0.00
Received By medwards Date 2022-06-27 Time 08:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 10:44 Rev Time 0.00
Received By medwards Date 2022-07-20 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By medwards Date 2022-07-15 Time 14:02 Rev Time 0.00
Received By medwards Date 2022-07-15 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By medwards Date 2022-07-01 Time 14:05 Rev Time 0.00
Received By medwards Date 2022-07-01 Time 14:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-20 Cont ID  
Sent By medwards Date 2022-07-20 Time 10:45 Rev Time 0.00
Received By medwards Date 2022-07-20 Time 10:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By medwards Date 2022-07-15 Time 14:03 Rev Time 0.00
Received By medwards Date 2022-07-15 Time 14:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By medwards Date 2022-07-01 Time 14:05 Rev Time 0.00
Received By medwards Date 2022-07-01 Time 14:05 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved