Plan Review Details - Permit 22061093
Plan Review Stops For Permit 22061093
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:14 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:14 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 15:59 Rev Time 0.00
Received By shill Date 2022-07-26 Time 15:59 Sent To  
Notes
2022-07-26 15:59:34PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 10:20 Rev Time 0.00
Received By shill Date 2022-09-01 Time 10:20 Sent To  
Notes
2022-09-01 10:20:56LV200

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:15 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:15 Sent To  
Notes
2022-08-06 10:21:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 WHITE OAK FLOORING WITH MSC90 UNDERLAYMENT IS PROPOSED
  
 THE MSC90 TEST REPORTS WE HAVE USED AN 8" SLAB WITH
 QUARRY TILE. SLAB THICKNESS FOR THIS BUILDING IS NOT
 CLEAR, PLEASE PROVIDE THAT INFORMATION AND HOW YOU
 DETERMINED SLAB THICKNESS.
  
 SPEC SHEET WAS UPLOADED, BUT THE FOLLOWING TEST REPORTS
 ARE REQUIRED.
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 15:57 Rev Time 0.00
Received By shill Date 2022-07-26 Time 15:57 Sent To  
Notes
2022-07-26 15:58:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 NEW FLOORING IS PROPOSED. REVISE THE PLAN TO CLARIFY
 FLOORING TYPE - FOR INSTANCE TILE, LVT, WOOD, ETC. IF
 THE FLOORING ALONE DOES NOT HAVE TEST REPORTS TO SHOW
 COMPLIANCE WITH STC AND IIC REQUIREMENTS, UNDERLAYMENT
 IS REQUIRED. IF UNDERLAYMENT IS NOT REQUIRED, PROVIDE
 STC AND IIC TEST REPORTS FOR THE PROPOSED FLOORING. SEE
 BELOW FOR ADDITIONAL INFO.
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By mpeterso Date 2022-08-16 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2022-08-16 Time 11:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-27 Cont ID  
Sent By mpeterso Date 2022-07-27 Time 08:08 Rev Time 0.00
Received By mpeterso Date 2022-07-27 Time 08:08 Sent To  
Notes
2022-07-27 08:19:28ELECTRIC REVIEW FAILED
  
 1) IT APPEARS A RECEPTACLE REQUIRED AS PER NEC 210.52
 (D) IS NOT DETAILED IN MASTER BATHROOM LOCATED WITHIN 3
 FEET OF EACH SINK BASINS. PLEASE CORRECT AS APPLICABLE
 2) PLEASE DETAIL THE REQUIRED SMOKE ALARMS REQUIRED TO
 COMPL WITH FBC RES 314.3
 3) PLEASE DETAIL THAT RELOCATED RECEPTACLES IN MASTER
 BATHROOM WILL COMPLY WITH 20 AMP BRANCH CIRCUIT
 REQUIREMENTS OF NEC 210.11(C)(3)
 4) PLEASE DETAIL NEW WIRING WILL COMPLY WITH ARC FAULT
 CIRCUIT PROTECTION AS REQUIRED BY NEC 210.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By cwalker Date 2022-08-09 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By   Date 2022-07-06 Time   Rev Time 0.00
Received By bdolan Date 2022-07-05 Time 14:36 Sent To  
Notes
2022-07-06 10:28:00PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 10:21 Rev Time 0.00
Received By shill Date 2022-08-18 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-16 Cont ID  
Sent By mpeterso Date 2022-08-16 Time 11:23 Rev Time 0.00
Received By mpeterso Date 2022-08-05 Time 06:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By mpeterso Date 2022-07-27 Time 08:19 Rev Time 0.00
Received By mpeterso Date 2022-07-05 Time 05:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-08-06 Cont ID  
Sent By ccole Date 2022-08-06 Time 09:05 Rev Time 0.00
Received By ccole Date 2022-08-06 Time 09:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By ccole Date 2022-07-13 Time 11:30 Rev Time 0.00
Received By ccole Date 2022-07-13 Time 11:16 Sent To  
Notes
2022-07-13 11:31:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22061093
 7/13/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A PLUMBING PIPING LAYOUT PLAN AND ISOMETRIC
 DRAWINGS FOR THE REMODELED MASTER BEDROOM- SEC.
 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 10:23 Rev Time 0.00
Received By shill Date 2022-08-06 Time 10:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 16:00 Rev Time 0.00
Received By shill Date 2022-07-26 Time 16:00 Sent To  
Notes
***NONE***