Plan Review Details - Permit 22061090
| Plan Review Stops For Permit 22061090 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-08 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-08 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-07-28 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-07-28 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-10 |
Time |
06:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-08 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-14 |
Time |
07:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-15 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-15 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2022-07-15 11:22:14 | PROVIDE THE ENERGY CALCULATIONS FOR THE GARAGE. FEC | | | 101.5.1.1.2 | | | | | | PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THE MINI SPLIT IN THE GARAGE. FEC R403.7.1 | | | | | | REMOVE THE RETURN AIR DUCT FROM THE ROOM ATTACHED TO | | | THE NEW OFFICE, IF IT IS TO BE A CLOSET. IT IS NOT | | | IDENTIFIED IN THE RENOVATION. FRC M1602.3 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-11 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-11 |
Time |
07:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-07-18 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-07-18 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2022-08-11 07:07:59 | PAGE P101 INDICATES THERE HAVE BEEN CHANGES MADE AFTER | | | THE SIGNATURE WAS APPLIED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-07-18 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-07-18 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2022-07-18 09:24:04 | PAGE P101 IS NOT SIGNED/SEALED | | | | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C | | 2022-07-15 11:23:55 | MECHANICAL DIGITAL SIGNATURE APPROVED ME |
|
|
|