Plan Review Details - Permit 22061065
Plan Review Stops For Permit 22061065
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-10-19 Cont ID  
Sent By cpuell Date 2022-10-19 Time 17:03 Rev Time 0.00
Received By cpuell Date 2022-10-19 Time 17:03 Sent To  
Notes
2022-10-19 17:04:53ANALYZED PLANS, 879 W EXECUTIVE CENTER DR FALLS IN THE
 RANGE OF THE PRIMARY ENTRANCE, APPLICANT ASKED TO KEEP
 CURRENT ADDRESS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-10-13 Cont ID  
Sent By cpuell Date 2022-10-13 Time 16:55 Rev Time 0.00
Received By cpuell Date 2022-10-13 Time 16:55 Sent To  
Notes
2022-10-13 16:56:34ADDRESSING COMMENTS NOT ADDRESS AND NOBODY HAS CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 THE ADDRESS FOR THIS PROJECT. IN THE UPLOADED DOCUMENTS
 MICROSOFT 21166 - REV.01 - PLAN REVIEW RESPONSE LETTER
 ADDRESSING REVIEW DID NOT GET A RESPONCE.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By cpuell Date 2022-06-23 Time 11:32 Rev Time 0.00
Received By cpuell Date 2022-06-23 Time 11:32 Sent To  
Notes
2022-06-23 11:35:29PLEASE CONTACT [email protected] 561-805-6659 FOR
 AN ADDRESS TO BE ASSIGNED TO THE PROJECT.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status P Date 2022-12-05 Cont ID  
Sent By swelter Date 2022-12-05 Time 12:39 Rev Time 0.00
Received By swelter Date 2022-12-05 Time 12:42 Sent To  
Notes
2022-12-05 12:42:09PAYMENT COMPLETED 12.05.2022 - ART REQUIREMENT
 SATISFIED.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2022-08-08 Cont ID  
Sent By scwelter Date 2022-08-08 Time 10:04 Rev Time 0.00
Received By scwelter Date 2022-08-08 Time 10:11 Sent To  
Notes
2022-08-08 10:11:00DEVELOPMENT IS OVER $500,000 THEREFORE IT IS SUBJECT TO
 PUBLIC ART ASSESSMENT.
 OPTION 2 ? CONTRIBUTION INTO THE PUBLIC ART ACCOUNT
 1% OF TOTAL CONSTRUCTION COSTS MINUS 25% OF THE 1%
 VALUE $582,000
 1% $5,820
 (-25%) ($1,455)
 TOTAL DUE $4,365
 CONTACT SYBILLE WELTER [email protected]
 FOR A PUBLIC ART ASSESSMENT APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-01-03 Cont ID  
Sent By rmcphers Date 2023-01-03 Time 09:24 Rev Time 0.00
Received By rmcphers Date 2023-01-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-31 Cont ID  
Sent By rmcphers Date 2022-10-31 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-10-31 Time 08:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2022-08-04 Time 16:43 Sent To  
Notes
2022-08-05 10:46:51NEW BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) COPIES OF THE PRODUCT
 APPROVALS LISTED ON THE DRAWINGS FOR THE EXTERIOR
 WINDOWS, DOORS, ROOFING SYSTEMS, LOUVERS, ROOF HATCH
 ETC.
  
 2) ACCESSIBLE RESTROOM = DRAWING A1B- DETAIL "C" SHOWS
 6" FROM THE SIDE WALL TO THE EDGE OF THE REAR TOILET
 GRAB BAR AND 17" TO THE CENTER OF THE TOILET - THE MATH
 DOESN'T WORK WITH 12" FROM THE EDGE OF THE GRAB BAR TO
 THE CENTER OF THE TOILET. - FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 3) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE LOCATION
 DIMENSIONS FOR THE MIRROR - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) ACCESSIBLE RESTROOM = THE ADDED VERTICAL GRAB BAR ON
 THE SIDE WALL NEXT TO THE TOILET IS NOT A REQUIREMENT
 OF THE FBC ACCESSIBILITY CODE - PLEASE SHOW THE 12"
 CLEARANCE ABOVE THE TOILET SIDE WALL GRAB PER FBC A
 609.3 SPACING. THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM)
 MINIMUM.
  
 5) PLEASE PROVIDE CANOPY DETAILS -
 CANOPY DETAILS, ROOFING SYSTEMS, WINDOW AND DOOR
 PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 6) SEPARATE PERMITS ARE REQUIRED FOR - EXISTING
 BUILDING DEMO, DUMPSTER ENCLOSURE, VACUUME ENCLOSURE,
 PARKING LOT, PARKING LOT LIGHTING, FREE STANDING
 CANOPIES, VACUUME SYSTEM, SIGNS, FLAG POLE. PLEASE
 ACKNOWLEDGE THIS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-11-08 Cont ID  
Sent By mpeterso Date 2022-11-08 Time 09:39 Rev Time 0.00
Received By mpeterso Date 2022-11-08 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By mpeterso Date 2022-07-28 Time 16:12 Rev Time 0.00
Received By mpeterso Date 2022-07-28 Time 16:12 Sent To  
Notes
2022-07-28 16:26:35ELECTRICAL REVIEW FAILED
 1) IT APPEARS THE POWER PLAN DRAWING, RISER, PANEL
 SCHEDULES AND THE EQUIPMENT DRAWING PROVIDED DO NOT
 MATCH. THE EQUIPMENT DRAWING DETAILS HIGH AND LOW HORSE
 POWER PANELS AND AN MCC CABINET. THE RISER AND POWER
 PLAN AND PANEL SCHEDULES ONLY DETAIL AN MCC. PLEASE
 CLARIFY AS APPLICABLE. NEC 215.5
 2) PLEASE PROVIDE SPECIFICATIONS FOR ALL OVERCURRENT
 AND OVERLOAD PROTECTION IN MCC CABINET. NEC 215.5
 3) PLEASE PROVIDE NOTES ON PLANS THAT SIGN, LOW
 VOLTAGE, FIRE ALARM, SECURITY, SITE LIGHTING AND ACCESS
 CONTROL WIRING REQUIRE SEPARATE PERMITS
 4) PLEASE PROVIDE A LEGEND DETAILING THE EQUIPMENT
 NUMBERS ON THE POWER PLAN DRAWING. FBC 107.2
 5) PLEASE PROVIDE FAULT CURRENT CALCULATIONS AND FAULT
 CURRENT LETTER FROM FPL. NEC 110.9
 6) POWER PLAN DOES NOT DETAIL 150 480 VOLT DISCONNECT
 FEEDING TRANSFORMER. PLEASE CORRECT AS APPLICABLE. NEC
 215.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2022-12-27 Cont ID  
Sent By rrossano Date 2022-12-27 Time   Rev Time 0.00
Received By rrossano Date 2022-12-27 Time   Sent To  
Notes
2022-12-27 08:37:39PASSED WITH PROVISO: UPLOAD APPROVED ENGINEERING PLANS
 (ONCE RELEASED AT PENDING ENGINEERING PRE-CON MEETING).
  
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES
 DEPT., 561-494-1098, FAX: 561-494-1116 [email protected]
 FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-10-19 Cont ID  
Sent By rrossano Date 2022-10-19 Time   Rev Time 0.00
Received By rrossano Date 2022-10-19 Time   Sent To  
Notes
2022-10-19 12:54:31UNDER FORMAL ENGINEERING REVIEW E22080007.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-06-22 Cont ID  
Sent By rrossano Date 2022-06-22 Time   Rev Time  
Received By rrossano Date 2022-06-22 Time   Sent To  
Notes
2022-06-22 13:17:21A FORMAL ENGINEERING SUBMITTAL IS REQUIRED.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-12-21 Cont ID  
Sent By pleduc Date 2022-12-21 Time   Rev Time 0.00
Received By pleduc Date 2022-12-21 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-24 Cont ID  
Sent By   Date 2022-06-24 Time   Rev Time 0.00
Received By bdolan Date 2022-06-24 Time 10:37 Sent To  
Notes
2022-06-24 10:38:16FIRE HAS NO OBJECTION TO THE PROPOSED PROJECT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-01-05 Cont ID  
Sent By medwards Date 2023-01-05 Time 10:20 Rev Time 0.00
Received By medwards Date 2022-12-20 Time 16:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-12-05 Cont ID  
Sent By aoliver Date 2022-12-05 Time 10:11 Rev Time 0.00
Received By aoliver Date 2022-10-13 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-09 Cont ID  
Sent By aoliver Date 2022-08-09 Time 07:05 Rev Time 0.00
Received By aoliver Date 2022-06-22 Time 05:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-03-23 Cont ID  
Sent By lmarchan Date 2023-03-23 Time 12:02 Rev Time 0.00
Received By lmarchan Date 2023-01-05 Time 10:44 Sent To  
Notes
2023-03-23 12:02:22NO IMPACT FEES DUE. LEM
2023-01-05 10:44:441/5/23 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 10:53 Sent To  
Notes
2022-08-05 10:54:53PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-01-05 Cont ID  
Sent By medwards Date 2023-01-05 Time 10:20 Rev Time 0.00
Received By medwards Date 2023-01-05 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-11-07 Cont ID  
Sent By medwards Date 2022-11-07 Time 06:29 Rev Time 0.00
Received By medwards Date 2022-11-07 Time 06:29 Sent To  
Notes
2022-11-07 06:29:332ND REVIEW FMC
 PERMIT: 22061065
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: IF KEYNOTE 1 DOES NOT APPLY THEN PLEASE
 REMOVE KEYNOTE 1. FBC 17.3.5
  
 2) PLEASE SHOW THE RETURN AIR PATH FROM THE MAIN ENTRY.
 FMC 601.6
  
 3) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS WERE
 NOT SUBMITTED IN THIS RESUBMITTAL. PLEASE SUBMIT A
 MECHANICAL EQUIPMENT SIZING CALCULATIONS ACCORDING TO
 FEC C403.2.1
  
 4) THE MECHANICAL SYSTEM THAT IS CONDITIONING THE
 PUBLIC AREA OF THIS NEW CARWASH WILL NEED TO COMPLY
 WITH THE HVAC EQUIPMENT PERFORMANCE REQUIREMENTS OF FEC
 C403.2.3
  
 5) PLEASE PROVIDE A REVISED SHEET M2 INDICATING THAT
 THE CONDENSING UNIT ON THE ROOF WILL NOW MEET THE 10???
 GUARD PROTECTION REQUIREMENT OF FMC 304.11
  
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND
 AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN
 ACCORDANCE
 WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N OR
 BY AN APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE
 USING THE DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 HEATING AND COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT
 FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE ENERGY
 RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN
 ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT
 HANDBOOK BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE. DESIGN LOADS SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE MECHANICAL PERMIT.
  
 EXCEPTION:
 WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A REGISTERED
 ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING
 (BY ZONE):
 1. PROJECT NAME/OWNER
 2. PROJECT ADDRESS
 3. AREA IN SQUARE FEET
 4. SIZING METHOD USED
 5. OUTDOOR DRY BULB USE
 6. INDOOR DRY BULB
 7. OUTDOOR WET BULB USED
 8. GRAINS WATER (DIFFERENCE)
 9. TOTAL SENSIBLE GAIN
 10.TOTAL LATENT GAIN
 11.RELATIVE HUMIDITY
 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR
 13.TOTAL HEATING REQUIRED WITH OUTSIDE AIR
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-14 Cont ID  
Sent By medwards Date 2022-07-14 Time 06:55 Rev Time 0.00
Received By medwards Date 2022-07-14 Time 06:55 Sent To  
Notes
2022-07-14 06:55:421ST REVIEW FMC
 PERMIT: 22061065
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FMC C403.2.1
  
 2) SHEET M-1; KEYNOTE 1 INDICATES THAT THE AHU SHALL BE
 LOCATED IN THE PLENUM SPACE. KEYNOTE 2 INDICATES THE
 CONDENSATE DRAIN IS TO BE PVC. PROVIDE A PLENUM RATED
 MATERIAL FOR THE CONDENSATE DRAIN PIPE. FMC 602.2.1
  
 3) PROVIDE GUARD PROTECTION FOR THE SERVICING OF THE
 CONDENSING UNIT LOCATED CLOSER THAN 10 FOOT FROM THE
 ROOFS EDGE. FMC 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 09:40 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By jesmith Date 2022-07-19 Time 11:42 Rev Time 0.00
Received By jesmith Date 2022-07-12 Time 09:38 Sent To  
Notes
2022-07-19 11:32:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22061065 879 W EXECUTIVE CENTER DR
  
 1ST REVIEW
  
  
 PLUMBING COMMENTS: DENIED
  
 1. THE BACKFLOW PERMIT AND INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
 2. PLAN SHEET A1B/ WATER CLOSET REAR WALL VIEW DETAIL:
 TO SHOW COMPLIANCE WITH FBC ACC604.5.2, REMOVE 6 INCH
 MEASUREMENT FROM SIDE WALL TO GRAB BAR AS IT CONFLICTS
 WITH 17 INCH MEASUREMENT FROM SIDEWALL TO CENTERLINE OF
 THE WATER CLOSET
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE PER FBC ACC 604.5.2
  
 3. PLAN SHEET A1B/ WALL HUNG SINK WITH MIRROR DETAIL:
 PER FBC ACC 603.3, MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT THE MAXIMUM
 40 INCH DIMENSION IS TO THE REFLECTING SURFACE OF THE
 MIRROR AS THE FRAME IS NOT DIMENSIONED..
  
 4. PER WPB FBC 107.2.1 AND 107.3.4, MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE FOLLOWING
 SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) MOP SINK FAUCET
 ***E) ACO TRENCH DRAIN
 ***F) OIL/WATER SEPARATOR
 ***G) RECLAIM TANKS
 ***H) HEAVY DUTY TRAFFIC LIDS FOR THE INTERCEPTOR AND
 RECLAIM TANKS
 ***I) WASH EQUIPMENT LISTED IN PINK BIRD 2 CAR WASH
 EXPRESS INSTALLATION 2-24-22-02
 ALL SUBMITTALS SHALL BE APPROVED AND STAMPED BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PER WPB FBC
 107.2.1 AND 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH WPB FBC 107.3.4.1. DEFERRED SUBMITTALS
 SHALL BE LISTED ON THE PLANS.
  
 5. OIL/WATER SEPARATOR: A SEPARATE PERMIT IS REQUIRED
 HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN PERMIT IS
 ALSO REQUIRED. PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 ***A) PROVIDE AN ENLARGED PIPING DIAGRAM SHOWING THE
 LOCATIONS OF CLEANOUTS AND VENTS AS REQUIRED BY THE
 MANUFACTURER AND FBC PL 1003.9.
 ***B) PROVIDE AN EQUIPMENT SCHEDULE FOR THE INTERCEPTOR
 ON THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 (INCLUDING STRUCTURAL) THAT INDICATE THE LISTING AND
 LABELING OF THE UNIT- FBC PL 1003.4.2
 ***C) PROVIDE SIZING CALCULATIONS PER THE MANUFACTURER
 IN ACCORDANCE WITH FBC PL 1003.4.2.2- NOT LESS THAN 6
 CU. FT. FOR THE FIRST 100 SQ. FT. OF AREA TO BE DRAINED
 PLUS 1 CU. FT. FOR EACH ADDITIONAL 100 SQ. FT.
 ***D) PROVIDE A SITE SPECIFIC, DIMENSIONED INSTALLATION
 DIAGRAM (PLAN AND RISER) SHOWING THE BURIAL DEPTH AND
 INLET AND OUTLET LOCATIONS, CLEAN OUT AND SAMPLING PORT
 LOCATIONS AND SIZES. PLEASE NOTE A SAMPLING PORT
 CONSISTING OF A 4-INCH TWO-WAY CLEANOUT TO BE USED AS A
 SAMPLING PORT MAY BE REQUIRED. PLEASE CONTACT THE CITY
 OF WEST PALM BEACH UTILITIES DEPT. FOR ADDITIONAL
 REQUIRED INSPECTION AND TEST SAMPLING INFORMATION AND
 GUIDELINES: FOG COMPLIANCE SPECIALISTS AT 561-822-2065
 OR 561-822-2274 OR EMAIL [email protected].
 ***E) HEAVY DUTY TRAFFIC LIDS ARE REQUIRED FOR TANK
 ACCESS OPENINGS- FBC PL 305.7 & 1003.10. PLEASE SUBMIT
 SPECS FOR THE LIDS. F) ALL SUBMITTALS SHALL BE APPROVED
 AND STAMP BY THE DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE- SECTION 107.2.1, 107.3.4. WPB. SUBMITTALS MAY
 BE DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
  
 6. RECLAIMED WATER SYSTEM- PER WPB FBC 107.2.1 WPB AND
 FBC PL 1301.1 & 1304.3 FBC PL, PROVIDE THE FOLLOWING:
 ***A) PROVIDE A COMPLETE PIPING DIAGRAM (PLAN AND
 RISER) THAT SHOWS THE PIPE RUNS FROM THE TANKS TO THE
 EQUIPMENT ROOM AND TO THE CONVEYOR. INCLUDE THE
 LOCATIONS OF TANK CLEANOUTS, VENTS AND OTHER
 APPURTENANCES WHERE REQUIRED BY MANUFACTURER'S
 SPECIFICATIONS.
 ***B) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 TANKS, AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKS (INCLUDING STRUCTURAL), THE RECLAIM UNIT, AND THE
 PIPING- FBC PL 1301.9.2, 1304.3 AND 1304.1.3.
 ***C) INDICATE HOW THE TANKS WERE SIZED AND PROVIDE
 CALCULATIONS.
 ***D) PROVIDE SITE SPECIFIC, DIMENSIONED TANK AND TANK
 INSTALLATION DIAGRAMS SHOWING ALL COMPONENTS IF THE
 TANKS AND BURIAL DEPTHS, WATER INLET AND OUTLET
 LOCATIONS ETC.- FBC PL 1309.3, 1309.7.
 ***E) HEAVY DUTY TRAFFIC LIDS ARE REQUIRED FOR TANK
 ACCESS OPENINGS- FBC PL 305.7 & 1309.6. PLEASE SUBMIT
 SPECS FOR THE LIDS.
 ***F) ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1 & 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH WPB FBC 107.3.4.1.
  
 7. CAR WASH SYSTEM: PER WPB FBC 107.2.1 AND 107.3.4,
 SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUALS FOR ALL WASH EQUIPMENT LISTED IN PINK BIRD 2
 CAR WASH EXPRESS INSTALLATION 2-24-22-02 FOR THE
 EQUIPMENT ROOM AND TUNNEL. PLEASE SUBMIT SHOP DRAWINGS
 FOR THE TUNNEL EQUIPMENT INSTALLATIONS. SUBMITTALS MAY
 BE DEFERRED IN ACCORDANCE WITH WPB FBC 107.3.4.1.
 ***A) PER SECTION 107.2.1 & 107.3.5.1.3 WPB PROVIDE A
 COMPLETE WATER PIPING DIAGRAM OR RISER DRAWING FOR THE
 EQUIPMENT ROOM AND WASH TUNNEL. SHOW LOCATIONS OF
 POTABLE WATER CONNECTIONS, BACKFLOW PREVENTERS, VALVES,
 AND SHUTOFFS FOR WASH EQUIPMENT.
  
 8. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 AND SHALL COMPLY WITH THE REQUIREMENTS OF FBC PL 605.3,
 TABLE 605.3, 605.4, TABLE 605.4, 605.5, TABLE 605.5,
 605.7 AND TABLE 605.7. PER WPB FBC 107.2.1, PROVIDE
 NOTE ON PLANS STATING THE SAME.
  
 9. P5/RPZ AT THE DOMESTIC WATER ENTRY: ALTHOUGH THE
 MANUFACTURER'S SPECIFICATIONS/INSTALLATION MANUALS DO
 NOT CLEARLY STATE IT, THE LF-009 RPZ IS MEANT TO BE
 INSTALLED ONLY IN THE HORIZONTAL POSITION. THIS IS
 REINFORCED BY THE FACT THAT THE MANUFACTURER?S
 SPECIFICATIONS/INSTALLATION MANUALS FOR THE LF-009 RPZ
 NOTES THAT THE UNIT MAY BE INSTALLED IN EITHER A
 VERTICAL OR HORIZONTAL POSITION DUE TO THE LOCATION OF
 THE RELIEF VALVE IN RELATION TO THE NUMBER 1 CHECK
 VALVE. PER WPB FBC 107.2.1, REVISE P5/DOMESTIC WATER
 ENTRY TO SHOW THE SPECIFIED LF-009 RPZ IN A HORIZONTAL
 POSITION; INCLUDE THE RELIEF VALVE DISCHARGE WITH AIR
 GAP AND SUPPORT DETAILS. IN LIEU OF THE HORIZONTAL
 POSITION, SPECIFY A PRV SUITED FOR VERTICAL
 INSTALLATION AND PROVIDE DETAIL; INCLUDE THE RELIEF
 VALVE DISCHARGE WITH AIR GAP AND SUPPORT DETAILS. IT
 SHOULD BE NOTED THAT CIVIL DRAWING C5 PROVIDES A RPPA
 BACKFLOW PREVENTION DEVICE IN THE WATER SERVICE AT THE
 METER LOCATION TO THE BUILDING.
  
 10. THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING, FROM THE SOURCE OF HOT WATER TO THE FIXTURES
 THAT REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50
 FEET (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER PER FBC PL 607.2.
 IT APPEARS THE HOT WATER PIPING FROM THE WATER HEATER
 TO THE LAVATORY EXCEEDS 50 FEET. PER WPB FBC 107.2.1,
 SHOW COMPLIANCE WITH FBC PL 607.2.
 REFER TO TABLE C404.5.1 FBC EC- THE 1/2 -INCH HOT WATER
 PIPE TO THE LAVATORY SHALL NOT EXCEED 2 FEET FROM THE
 HOT WATER SOURCE.
 ***A) IF RECIRCULATED OR HEAT TRACE SYSTEM IS APPLIED,
 A DETAIL AND SPECIFICATION IS REQUIRED FOR THE
 RECIRCULATING PUMP SHOWING PIPING, VALVES AND
 APPURTENANCES AS WELL AS INTEGRATION WITH THE WATER
 HEATER PIPING OR THE HEAT TRACE SYSTEM, WHICHEVER IS
 APPLICABLE.
  
 11. P4/GENERAL NOTE 3: PER FBC PL 605.2.1, NOTE SHALL
 STATE "LEAD FREE SOLDERED JOINTS", NOT "95/5 SOLDERED
 JOINTS".
  
 12. P2: THERE ARE NUMBERED WINDOW SYMBOLS ON THE PLAN
 THAT SHOULD BE SUPPORTED WITH KEY NOTES, BUT THERE ARE
 NO CORRESPONDING KEY NOTES. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 13. P2: PER WPB FBC 107.2.1, CLARIFY THE PURPOSE OF THE
 1-1/2 INCH VALVED AND CAPPED COLD WATER LINE LINE
 (WINDOW SYMBOL 4). PLEASE NOTE THAT PER FBC PL 608.1
 AND 1301.9.4, A BACKFLOW PREVENTER IS REQUIRED AT THE
 CONNECTION POINT FOR THE WASH EQUIPMENT. PROVIDE A
 BACKFLOW PREVENTER ASSEMBLY AT THIS LOCATION AND
 INDICATE THE TYPE PER FBC PL 608.3. THE EQUIPMENT
 SYSTEM SHALL BE COMPLETELY ISOLATED FROM THE POTABLE
 WATER SYSTEM. PLEASE SEE COMMENT 6.
  
 14. P4/SANITARY RISER; PER WPB CODE OF ORDINANCE
 CHAPTER 90, ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE
 (INTERPRET THIS AS ANY CONDENSATION FROM EVAPORATOR
 COILS) SHALL NOT DISCHARGE TO THE CITY UTILITIES
 SANITARY SEWAGE INFRASTRUCTURE WITHOUT PERMISSION FROM
 THE UTILITIES DEPARTMENT. YOU MAY CONTACT MR. RICK
 ROSSANO IN ENGINEERING AT 561-494-1098 FOR ADDITIONAL
 INFORMATION. MOVING FORWARD, REMOVE THE DRAIN FOR THE
 A/C CONDENSATE FROM THE SANITARY AND DISCHARGE THE
 CONDENSATE TO AN EXTERIOR DRYWELL; PER WPB FBC 107.2.1,
 PROVIDE ROUTING AND DRYWELL DETAIL.
  
 15.PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY
 WITH FBC EC TABLE C404.2
  
 16. SEE P4/GENERAL NOTE 3: INSULATION SPECIFICATION FOR
 HOT WATER INSULATION SHALL COMPLY WITH FBC EC C404.4
 (A-E) AND TABLE C403.2.10. PER WPB FBC 107.2.1
 THE FOLLOWING PIPING SHALL BE INSULATED TO LEVELS SHOWN
 IN TABLE C403.2.10:A.RECIRCULATING SYSTEM PIPING,
 INCLUDING THE SUPPLY AND RETURN PIPING OF A CIRCULATING
 TANK TYPE WATER HEATER.
 ***A) THE FIRST 8 FEET OF OUTLET PIPING FOR A
 CONSTANT-TEMPERATURE NONRECIRCULATING STORAGE SYSTEM.
 ***B) THE FIRST 8 FEET OF BRANCH PIPING CONNECTING TO
 RECIRCULATED, HEAT-TRACED, OR IMPEDANCE HEATED PIPING.
 ***C) THE INLET PIPING BETWEEN THE STORAGE TANK AND A
 HEAT TRAP IN A NONRECIRCULATING STORAGE SYSTEM.
 ***D) PIPING THAT IS EXTERNALLY HEATED (SUCH AS HEAT
 TRACE OR IMPEDANCE HEATING).
  
 17. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR SUPPORT BRACKET AND ANCHORS FOR WALL
 MOUNTED WATER HEATER.
  
 18. P2/ROOF DRAINAGE: NOTE IN ROOF DRAIN CALCULATIONS
 (SEE P2/ROOF DRAINAGE) STATES DISCHARGES TO SITE STORM
 SEWER; P1 INDICATES TWO (2) STORM BUILDING DRAINS WITH
 NOTE "CONNECT TO CIVIL". CIVIL (SEE C4) DOES NOT
 INDICATE STORM BUILDING SEWER, ONLY PAVEMENT DRAINAGE
 WITH EXFILTRATION TRENCH AND NO PROVISION FOR BUILDING
 STORM DISCHARGE. PER WPB FBC 107.2.1, PROVIDE CLEAR
 PLANS WITH CLEAR INSTRUCTION FOR TERMINATION OF
 BUILDING STORM DISCHARGE
  
 19. A3 ROOF PLAN/OVERFLOW SCUPPER DETAIL: THE SCUPPER
 DETAIL DOES NOT APPEAR IN COMPLIANCE WITH SECTION
 1503.4.2.1 FBC B WHICH INDICATES THE SCUPPERS SHALL BE
 PLACED IN THE PARAPET WALLS NOT LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE ROOF COVERING. PER WPB FBC
 107.2.1, REVISE NOTE TO REFLECT THE REQUIREMENT.
  
 20. PER WPB FBC 107.2.1, PROVIDE STORM RISER DIAGRAM.
  
 21. P1/SANITARY DRAINAGE AND SIZING CHART: TRENCH DRAIN
 IS NOTED WITH 4 INCH TRAP WITH A DFU VALUE OF 2; PER
 FBC PL TABLE 709.1, FOOTNOTE A), THE VALUE FOR A 4 INCH
 TRAP SHALL BE 6.
  
 22. P4/WATER HEATER SCHEDULE AND DETAIL:
 ***A) DETAIL SHOWS RELIEF LINE DISCHARGING TO A FLOOR
 DRAIN. NO FLOOR DRAIN IS SHOWN. PER WPB FBC 107.2.1,
 PROVIDE TERMINATION FOR THE RELIEF VALVE DISCHARGE ON
 THE DETAIL.
 ***B) PER WPB FBC 107.2.1, PROVIDE T&P DISCHARGE PIPE
 SIZE AND MATERIAL
 ***C) PER WPB FBC 107.2.1, PROVIDE PAN DRAIN MATERIAL.
 PER FBC PL 504.7.1, PIPING MATERIAL FOR PAN DRAIN SHALL
 COMPLY WITH FBC PL TABLE 605.4.
 ***D) PER WPB FBC 107.2.1, PROVIDE THE TEMPERATURE OF
 THE HOT WATER SUPPLY TO THE FIXTURES.
  
 23. PINK BIRD 2 CAR WASH EXPRESS INSTALLATION
 2-24-22-02: EQUIPMENT OVERVIEW/LISTED EQUIPMENT
 INDICATES A COMPRESSED AIR SYSTEM. PER WPB FBC 107.2.1,
 PROVIDE PLAN VIEW AND RISER DIAGRAM SHOWING AND
 IDENTIFYING ALL COMPONENTS; PROVIDE MATERIAL
 SPECIFICATION.
  
 24. PINK BIRD 2 CAR WASH EXPRESS INSTALLATION
 2-24-22-02: PER WPB FBC 107.2.1 AND 107.2.1.2, PROVIDE
 PLAN VIEW/OVERVIEW AND SCHEMATIC/P&ID FOR ALL
 NON-POTABLE/PROCESS SYSTEMS; INCLUDE AND IDENTIFY ALL
 EQUIPMENT. RECONCILE WITH PINK BIRD 2 CAR WASH EXPRESS
 INSTALLATION 2-24-22-P1.
  
 25. PER WPB FBC 107.2.1, RECONCILE P1 SANITARY PLAN AND
 PINK BIRD 2 CAR WASH EXPRESS INSTALLATION 2-24-22-C1
 TRENCH PLAN AND ELEVATION SLEEVE/PIPING.
  
 26. AS1, AS2 AND ES1 INDICATE A VACUUM SYSTEM; NOTHING
 IS INDICATED ON THE PLUMBING OR MECHANICAL PLANS. PER
 WPB FBC 107.2.1, CLARIFY. PER WPB FBC 105.1, A PERMIT
 IS REQUIRED. PER WPB FBC 107.2.1 AND 107.3.4, PROVIDE
 PLANS AND SPECIFICATIONS FOR THE SYSTEM INCLUDING ALL
 PIPING.
  
 27. PER FBC PL 1301.3 & 1301.9.9, NON-POTABLE WATER
 SIGNAGE IS REQUIRED IN THE EQUIPMENT ROOM, OUTLETS AND
 AT ALL COMPONENTS OF THE RECLAIMED WATER SYSTEM. PER
 WPB FBC 107.2.1, PLEASE SHOW SIGN LOCATIONS AND PROVIDE
 SIGNAGE DETAILS.
  
 28. PLEASE NOTE THAT IF THE BUILDING PLANS EXAMINER
 DETERMINES THAT THE PROPOSED BUILDING IS A FLOOD ZONE
 AREA, PROVISION SHALL BE MADE IN ACCORDANCE WITH FBC PL
 309.2, 1301.9.3.1 AND FBC 1612.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 2 Status N Date 2022-10-21 Cont ID  
Sent By rwbrown Date 2022-10-21 Time 09:41 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-21 09:42:01IRRIGATION REQUIRED TO BE ON SEPARATE PERMIT
  

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By jesmith Date 2022-07-19 Time 16:31 Rev Time 0.00
Received By jesmith Date 2022-07-19 Time 11:44 Sent To  
Notes
2022-07-19 16:31:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22061065 879 W EXECUTIVE CENTER DR
  
 1ST REVIEW
 DENIED
  
 A SEPARATE PERMIT MAY BE REQUIRED FOR THE WELL IF NOT
 EXISTING
 A SEPARATE ELECTRICAL PERMIT MAY BE REQUIRED FOR THE
 PUMP IF NOT EXISTING
 A SEPARATE PLUMBING PERMIT IS REQUIRED FOR THE
 INSTALLATION.
  
 PER WPB FBC 107.2.1, THE FOLLOWING ITEMS ARE REQUIRED.
 1.PROVIDE SYMBOL LEGEND/EQUIPMENT SCHEDULE FOR
 IRRIGATION WELL & PUMP (NEW OR EXISTING?), CONTROLLER,
 RAIN SENSOR, SPRINKLER HEADS, CONTROL VALVES, ETC.
 INDICATE THE MAKES AND MODELS OF THE CONTROLLER, RAIN
 SENSOR, SPRINKLER HEADS, CONTROL VALVES ETC.- SECTION
 107.2.1 WPB. PROVIDE MOUNTING DETAILS FOR THE PUMP
  
 2.CLEARLY SHOW LOCATIONS OF IRRIGATION WELL & PUMP (NEW
 OR EXISTING?), CONTROLLER, RAIN SENSOR, SPRINKLER
 HEADS, CONTROL VALVES, ETC. (SPRINKLER HEADS DO SEEM TO
 BE SHOWN)
  
 3. PROVIDE BASIC INSTALLATION DETAILS- DEPTH OF COVER
 FOR THE PIPING, CLEARANCE OF PIPING FROM OTHER
 UNDERGOUND UTILITIES, SPACING OF SPRINKLER HEADS,
 CLEARANCE DISTANCES OF HEADS TO BUILDINGS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-10-31 Cont ID  
Sent By rmcphers Date 2022-10-31 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2022-10-31 Time 08:21 Sent To  
Notes
2022-10-31 08:21:48ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-08-05 Cont ID  
Sent By rmcphers Date 2022-08-05 Time 10:55 Rev Time 0.00
Received By rmcphers Date 2022-08-05 Time 10:55 Sent To  
Notes
2022-08-05 10:55:21SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-03 Cont ID  
Sent By rmcphers Date 2023-01-03 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2023-01-03 Time 09:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-10-31 Cont ID  
Sent By rmcphers Date 2022-10-31 Time 08:22 Rev Time 0.00
Received By rmcphers Date 2022-10-31 Time 08:22 Sent To  
Notes
2022-10-31 08:23:18SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) SOIL REPORT PROVIDED DOES NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-28 Cont ID  
Sent By mpeterso Date 2022-07-28 Time 16:29 Rev Time 0.00
Received By mpeterso Date 2022-07-28 Time 16:29 Sent To  
Notes
2022-07-28 16:29:53ALL SIGNATURES PASSED . MP
2022-07-14 06:56:27DIGITAL MECHANICAL SIGNATURE APPROVED ME
2022-07-12 09:52:43SIGNATURES FOR PLUMBING AND IRRIGATION ARE VALID. JS

Review Stop Z ZONING
Rev No 4 Status P Date 2023-02-03 Cont ID  
Sent By eschneid Date 2023-02-03 Time 16:35 Rev Time 0.25
Received By eschneid Date 2023-02-03 Time 16:35 Sent To  
Notes
2023-02-03 16:35:30PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE CAR WASH BUILDING THE PROPERTY OWNER MUST:
  
 A. RECORD A PUBLIC ACCESS EASEMENT, ACCEPTABLE TO THE
 CITY ATTORNEY'S OFFICE, FOR THE PLAZA ALONG WEST
 EXECUTIVE CENTER DRIVE. THE EASEMENT MAY OCCUR ON THE
 PLAT.
 B. GRANT THE REDEDICATED DRAINAGE EASEMENT TO THE CITY
 FOR THE EXISTING DRAINAGE PIPE ALONG THE SOUTH PROPERTY
 LINE.
 C. PLAT THE PROPETY.
  
 SEPARATE PERMITS, WITH PLANS ARE REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE.
 B. VACUUM ENCLOSURES AND VACUUM EQUIPMENT.
 C. FLAG POLE, BOLLARDS, BICYCLE RACKS, BENCHES AND
 OTHER ABOVE GROUND FIXTURES.
 D. SITE LIGHTING - THE SITE LIGHTING PERMIT SHALL
 INCLUDE THE LIGHT POLE SPECIFICATIONS, INCLUDING POLE
 AND FIXTURE HEIGHTS, TO ENSURE NO CONFLICTS WITH THE
 PROPOSED GUMBO LIMBO TREE CANOPIES.
 E. LANDSCAPE.
 F. IRRIGATION.
 G. HARDSCAPE.
 H. PARKING LOT STRIPING.
 I. SIGNAGE.
 J. PAY STATION.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-01-03 Cont ID  
Sent By eschneid Date 2023-01-03 Time 12:13 Rev Time 0.75
Received By eschneid Date 2023-01-03 Time 08:37 Sent To  
Notes
2023-01-03 12:19:20*** AN UPDATED PALM BEACH COUNTY TPS LETTER EXTENDING
 THE BUILDING OUT DATE IS REQUIRED PRIOR TO ZONING
 APPROVAL OF THIS PERMIT ***
  
 *** A TREE ALTERATION PERMIT MUST BE SUBMITTED TO AND
 APPROVED BY THE PLANNING DIVISION PRIOR TO ZONING
 APPROVAL OF THIS PERMIT ***
  
 BUILDING COMPLIES WITH APPROVED DEVELOPMENT PLANS.
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE CAR WASH BUILDING THE PROPERTY OWNER MUST:
  
 A. RECORD A PUBLIC ACCESS EASEMENT, ACCEPTABLE TO THE
 CITY ATTORNEY'S OFFICE, FOR THE PLAZA ALONG WEST
 EXECUTIVE CENTER DRIVE. THE EASEMENT MAY OCCUR ON THE
 PLAT.
 B. GRANT THE REDEDICATED DRAINAGE EASEMENT TO THE CITY
 FOR THE EXISTING DRAINAGE PIPE ALONG THE SOUTH PROPERTY
 LINE.
 C. PLAT THE PROPETY.
  
 SEPARATE PERMITS, WITH PLANS ARE REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE.
 B. VACUUM ENCLOSURES AND VACUUM EQUIPMENT.
 C. FLAG POLE, BOLLARDS, BICYCLE RACKS, BENCHES AND
 OTHER ABOVE GROUND FIXTURES.
 D. SITE LIGHTING - THE SITE LIGHTING PERMIT SHALL
 INCLUDE THE LIGHT POLE SPECIFICATIONS, INCLUDING POLE
 AND FIXTURE HEIGHTS, TO ENSURE NO CONFLICTS WITH THE
 PROPOSED GUMBO LIMBO TREE CANOPIES.
 E. LANDSCAPE.
 F. IRRIGATION.
 G. HARDSCAPE.
 H. PARKING LOT STRIPING.
 I. SIGNAGE.
 J. PAY STATION.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By eschneid Date 2022-12-01 Time 13:41 Rev Time 1.00
Received By eschneid Date 2022-12-01 Time 10:09 Sent To  
Notes
2022-12-01 13:30:03FAILED
  
 1) REPEAT COMMENT: A SURVEY IS REQUIRED.
  
 2) REPEAT COMMENT: A PLAN WHICH INCLUDES THE BUILDING
 SETBACKS TO THE PROPERTY LINES IS REQUIRED.
  
 3) ZONING WILL NOT ISSUE THE BUILDING PERMIT UNTIL THE
 REQUIRED TREE ALTERATION PERMIT HAS BY ISSUED BY THE
 PLANNING DIVISION. NOTE: NO TREES MAY BE
 REMOVED/RELOCATED PRIOR TO THE ISSUANCE OF THE TREE
 ALTERATION PERMIT. **** NO TREE ALTERATION PERMIT HAS
 BEEN SUBMITTED. ****
  
 4) NO NEW PLANS WERE SUBMITTED TO ADDRESS THE ZONING
 COMMENTS MADE ON AUGUST 4, 2022.
  
 5) REPEAT COMMENT: THE ARCHITECTURAL AND CIVIL SITE
 PLANS MUST MATCH THE LAYOUT ON THE PLANS SUBMITTED FOR
 THE PENDING MINOR PLANNED DEVELOPMENT AMENDMENT
 APPROVAL. ALL SUBMITTALS NEED TO INCLUDE CONSISTENT,
 CODE COMPLIANT PLANS.
  
 6) THE FLOOR PLAN THAT IS INCLUDED WITH THE BUILDING
 PERMIT MATCHES THE FLOOR PLAN SUBMITTED WITH THE LATEST
 MINOR AMENDMENT SUBMITTAL; HOWEVER, THE SITE LAYOUT
 SURROUNDING THE BUILDING DOES NOT MATCH THE MINOR
 AMENDMENT SITE, LANDSCAPE, CIVIL AND ARCHITECTURAL PLAN
 LAYOUTS AND MUST BE CORRECTED WITH THIS BUILDING
 PERMIT. **** SUBMIT THE SAME PLAN LAYOUT SHOWN ON THE
 MINOR AMENDMENT FLOOR PLAN TO ADDRESS THIS COMMENT.
 ****
  
 7) REPEAT COMMENT: THE ELEVATIONS DO NOT MATCH THE
 ELEVATIONS APPROVED AS PART OF THE ORIGINAL DEVELOPMENT
 ORDER OR THE PENDING MINOR PLANNED DEVELOPMENT
 AMENDMENT APPROVAL. ALL SUBMITTALS NEED TO INCLUDE
 CONSISTENT, CODE COMPLIANT PLANS. **** THE HIGH POINT
 OF THE FIN ELEMENT IS LISTED AS 26 FEET 8 INCHES ON THE
 MINOR AMENDMENT SUBMITTED ELEVATIONS AND 28 FEET ON THE
 PERMIT ELEVATIONS (EAST AND SOUTH). ****
  
 8) THE TOTAL BUILDING AREA SHOWN ON SHEET T2 (3,856 SF)
 IS LESS SQUARE FOOTAGE THAN SHOWN ON THE ARCHITECTURAL
 SITE PLAN SUBMITTED TO THE PLANNING DIVISION AS PART OF
 THE MOST RECENT MINOR AMENDMENT RESUBMITTAL AS WELL AS
 THE ARCHITECTURAL SITE PLAN SHEET AS1 SUBMITTED WITH
 THE PERMIT (3,898 SF). THE PLANS AND INFORMATION SHALL
 MATCH.
  
 9) REPEAT COMMENT: THE SIGNS REQUIRE SEPARATE
 PERMITTING AND SHALL BE REMOVED FROM THE ELEVATION
 DRAWINGS SUBMITTED WITH THIS PERMIT. PLEASE NOTE THAT
 THE BUILDING CONTAINS MORE SIGNAGE THAN IS PERMITTED BY
 THE CITY SIGN REGULATIONS. **** THE LATEST MINOR
 AMENDMENT PLANS ADDRESS THIS COMMENT ****
  
 10) REPEAT COMMENT: PROVIDE VERIFICATION THAT THE
 PROPOSED ROOFTOP MECHANICAL EQUIPMENT, INCLUDING ANY
 RACK OR CURB, IS SCREENED FOR ITS FULL HEIGHT BY THE
 PROPOSED PARAPET WALL. **** THE LATEST MINOR AMENDMENT
 PLANS GRAPHICALLY SHOW THE MECHANICAL EQUIPMENT
 SCREENED; HOWEVER, FOR THE PERMIT, THE EQUIPEMENT
 HEIGHT (INCLUDING CURB), MUST BE INCLUDED TO VERIFY
 THAT THE PARAPETS PROVIDE SCREENING.
  
 11) REPEAT COMMENT: PROVIDE VERIFICATION THAT THE TINT
 ON THE WINDOWS ALONG WEST EXECUTIVE CENTER DRIVE IS NOT
 SO DARK/REFLECTIVE THAT IT OBSTRUCTS THE VIEW INTO THE
 CAR WASH.
  
 12) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE CAR WASH BUILDING THE PROPERTY OWNER MUST:
  
 A. RECORD A PUBLIC ACCESS EASEMENT, ACCEPTABLE TO THE
 CITY ATTORNEY'S OFFICE, FOR THE PLAZA ALONG WEST
 EXECUTIVE CENTER DRIVE. THE EASEMENT MAY OCCUR ON THE
 PLAT, WHICH IS ALSO REQUIRED PRIOR TO CO.
 B. GRANT THE REDEDICATED DRAINAGE EASEMENT TO THE CITY
 FOR THE EXISTING DRAINAGE PIPE ALONG THE SOUTH PROPERTY
 LINE. BY THIS RESOLUTION, THE CITY COMMISSION
 AUTHORIZES THE MAYOR TO EXECUTE ANY REQUIRED AGREEMENTS
 RELATED TO THE DRAINAGE EASEMENT TERMINATION AND
 REDEDICATION WITH THE PROPERTY OWNER.
  
 13) SEPARATE PERMITS REQUIRED (SOME HAVE ALREADY BEEN
 APPLIED FOR):
  
 A. LANDSCAPE
 B. SIGNAGE
 C. PARKING LOT STRIPING
 D. HARDSCAPE, INCLUDING THE BICYCLE RACK, BENCHES, ETC.
 PLEASE REMEMBER THAT THE SEATING ALONG WEST EXECUTIVE
 CENTER DRIVE MUST MEET CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) STANDARDS.
 E. SITE LIGHTING NOTE: LIGHT POLES ARE SHOWN IN
 DIFFERENT LOCATIONS AND CONFLICTS ON THE SITE/LANDSCAPE
 PLANS, THE ARCHITECTURAL PLANS AND THE ELECTRICAL SITE
 PLAN. THE LIGHT POLE LOCATIONS ARE REQUIRED TO BE
 COORDINATED AMONG THE PLANS AS PART OF THE MINOR
 PLANNED DEVELOPMENT. THESE PLANS CAN THEN BE USED FOR
 THE SITE LIGHTING PERMIT.
 F. PAY STATIONS AND CANOPY
 G. DUMPSTER ENCLOSURE
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-04 Cont ID  
Sent By eschneid Date 2022-08-04 Time 11:39 Rev Time 1.00
Received By eschneid Date 2022-08-04 Time 09:22 Sent To  
Notes
2022-08-04 11:40:18FAILED
  
 1) A SURVEY IS REQUIRED.
  
 2) A PLAN WHICH INCLUDES THE BUILDING SETBACKS TO THE
 PROPERTY LINE IS REQUIRED.
  
 3) ZONING WILL NOT ISSUE THE BUILDING PERMIT UNTIL THE
 REQUIRED TREE ALTERATION PERMIT HAS BY ISSUED BY THE
 PLANNING DIVISION. NOTE: NO TREES MAY BE
 REMOVED/RELOCATED PRIOR TO THE ISSUANCE OF THE TREE
 ALTERATION PERMIT.
  
 4) THE ARCHITECTURAL AND CIVIL SITE PLANS DO NOT MATCH
 THE SITE PLAN APPROVED AS PART OF THE ORIGINAL
 DEVELOPMENT ORDER OR THE PENDING MINOR PLANNED
 DEVELOPMENT AMENDMENT APPROVAL. ALL SUBMITTALS NEED TO
 INCLUDE CONSISTENT, CODE COMPLIANT PLANS.
  
 5) THE FLOOR PLAN DOES NOT MATCH THE FLOOR PLAN
 APPROVED AS PART OF THE ORIGINAL DEVELOPMENT ORDER OR
 THE PENDING MINOR PLANNED DEVELOPMENT AMENDMENT
 APPROVAL. ALL SUBMITTALS NEED TO INCLUDE CONSISTENT,
 CODE COMPLIANT PLANS.
  
 6) THE ELEVATIONS DO NOT MATCH THE ELEVATIONS APPROVED
 AS PART OF THE ORIGINAL DEVELOPMENT ORDER OR THE
 PENDING MINOR PLANNED DEVELOPMENT AMENDMENT APPROVAL.
 ALL SUBMITTALS NEED TO INCLUDE CONSISTENT, CODE
 COMPLIANT PLANS.
  
 7) THE SIGNS REQUIRE SEPARATE PERMITTING AND SHALL BE
 REMOVED FROM THE ELEVATION DRAWINGS SUBMITTED WITH THIS
 PERMIT. PLEASE NOTE THAT THE BUILDING CONTAINS MORE
 SIGNAGE THAN IS PERMITTED BY THE CITY SIGN REGULATIONS.
  
 8) PROVIDE VERIFICATION THAT THE PROPOSED ROOFTOP
 MECHANICAL EQUIPMENT, INCLUDING ANY RACK OR CURB, IS
 SCREENED FOR ITS FULL HEIGHT BY THE PROPOSED PARAPET
 WALL.
  
 9) PROVIDE VERIFICATION THAT THE TINT ON THE WINDOWS
 ALONG WEST EXECUTIVE CENTER DRIVE IS NOT SO
 DARK/REFLECTIVE THAT IT OBSTRUCTS THE VIEW INTO THE CAR
 WASH.
  
 10) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE CAR WASH BUILDING THE PROPERTY OWNER MUST:
  
 A. RECORD A PUBLIC ACCESS EASEMENT, ACCEPTABLE TO THE
 CITY ATTORNEY?S OFFICE, FOR THE PLAZA ALONG WEST
 EXECUTIVE CENTER DRIVE. THE EASEMENT MAY OCCUR ON THE
 PLAT.
 B. GRANT THE REDEDICATED DRAINAGE EASEMENT TO THE CITY
 FOR THE EXISTING DRAINAGE PIPE ALONG THE SOUTH PROPERTY
 LINE. BY THIS RESOLUTION, THE CITY COMMISSION
 AUTHORIZES THE MAYOR TO EXECUTE ANY REQUIRED AGREEMENTS
 RELATED TO THE DRAINAGE EASEMENT TERMINATION AND
 REDEDICATION WITH THE PROPERTY OWNER.
  
 11) SEPARATE PERMITS REQUIRED:
  
 A. LANDSCAPE
 B. SIGNAGE
 C. PARKING LOT STRIPING
 D. HARDSCAPE, INCLUDING THE BICYCLE RACK, BENCHES, ETC.
 PLEASE REMEMBER THAT THE SEATING ALONG WEST EXECUTIVE
 CENTER DRIVE MUST MEET CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED) STANDARDS.
 E. SITE LIGHTING
 F. PAY STATIONS AND CANOPY
 G. DUMPSTER ENCLOSURE
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  