Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:24 Rev Time 0.00
Received By shill Date 2022-08-20 Time 09:24 Sent To  
Notes
2022-08-20 09:27:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 SEE PREVIOUS LIST FOR CODE REFERENCES
  
 2. THE FBC REQUIREMENT FOR FLAME SPREAD IS FOR THE
 UNDERLAYMENT. APPLICANT UPLOADED A SPEC SHEET FOR
 "KAHRS TECHNICAL DATA" WHICH APPEARS TO BE THE
 FLOORING. IT STATES THAT THE ASTM E-84 FLAME SPREAD FOR
 THIS PRODUCT IS 145. PLEASE SUBMIT THE ACTUAL TEST
 REPORT AND I'LL TAKE THIS TO THE BUILDING OFFICIAL TO
 SEE IF WE CAN ACCEPT THE TEST FOR THE FLOORING RATHER
 THAN THE UNDERLAYMENT PER FBC 104.11 ALTERNATIVE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 09:12 Rev Time 0.00
Received By shill Date 2022-07-27 Time 09:12 Sent To  
Notes
2022-07-27 09:14:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PROVIDE A PLAN SHOWING PROPOSED AREA OF
 WORK.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FLAME
 SPREAD TEST. THE TESTS WE HAVE ON FILE ARE FOR TILE,
 WOOD FLOOR IS PROPOSED.
  
 2ND REVIEW, THE FLAME SPREAD TEST SUBMITTED WAS TESTED
 WITH TILE. THIS NEEDS TO BE DONE WITH EITHER
 UNDERLAYMENT ALONE OR A WOOD OR SIMILAR COMBUSTIBLE
 FLOOR.
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 18:44 Rev Time 0.00
Received By shill Date 2022-07-23 Time 18:44 Sent To  
Notes
2022-07-23 18:47:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PROVIDE A PLAN SHOWING PROPOSED AREA OF
 WORK.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FLAME
 SPREAD TEST. THE TESTS WE HAVE ON FILE ARE FOR TILE,
 WOOD FLOOR IS PROPOSED.
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-08-15 Time 12:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By pleduc Date 2022-07-27 Time   Rev Time 0.00
Received By pleduc Date 2022-07-27 Time 13:00 Sent To  
Notes
2022-07-27 13:02:17THE PREVIOUS FAILED FIRE COMMENTS WERE NOT ADDRESSED.
  
 PLEASE PROVIDE A FLOOR PLAN, THE TYPE OF WOOD FLOORING
 & PRODUCT NAME, A A RADIANT FLUX FLAME RATING FOR THE
 WOOD FLOORING.
  
 THE PREVIOUS COMMENTS ARE RESUBMITTED BELOW:
  
 *******************************************************
 ******************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATIONS WITHIN THE UNIT WHERE THE FLOORING WILL BE
 INSTALLED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION OF THE FLOORING INSTALL.
  
  
 2) THERE IS AN INDICATION OF WOOD FLOORING BUT NO
 MANUFACTURER SPEC SHEET NOR PRODUCT NAME FOR THE ACTUAL
 PROPOSED FINISHED FLOORING.
  
 WOOD FLOORING IS A GENRAL TERM AND THE ACTUAL PRODUCT
 COULD HAVE DIFFERENT MATERIALS AND CAN BE
 VINYL/LAMINATE, PLASTIC ETC AND CAN BE MANUFACTURED
 FROM AROUND THE WORLD AND NOT ALL ARE TESTED AND
 MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 WOOD FLOORING NAME AND PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By pleduc Date 2022-06-23 Time   Rev Time 0.00
Received By pleduc Date 2022-06-23 Time 11:06 Sent To  
Notes
2022-06-23 11:16:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATIONS WITHIN THE UNIT WHERE THE FLOORING WILL BE
 INSTALLED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION OF THE FLOORING INSTALL.
  
  
 2) THERE IS AN INDICATION OF WOOD FLOORING BUT NO
 MANUFACTURER SPEC SHEET NOR PRODUCT NAME FOR THE ACTUAL
 PROPOSED FINISHED FLOORING.
  
 WOOD FLOORING IS A GENRAL TERM AND THE ACTUAL PRODUCT
 COULD HAVE DIFFERENT MATERIALS AND CAN BE
 VINYL/LAMINATE, PLASTIC ETC AND CAN BE MANUFACTURED
 FROM AROUND THE WORLD AND NOT ALL ARE TESTED AND
 MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 WOOD FLOORING NAME AND PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:28 Rev Time 0.00
Received By shill Date 2022-08-14 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-27 Cont ID  
Sent By aoliver Date 2022-07-27 Time 14:41 Rev Time 0.00
Received By aoliver Date 2022-07-26 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 18:48 Rev Time 0.00
Received By shill Date 2022-06-22 Time 11:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 18:47 Rev Time 0.00
Received By shill Date 2022-07-23 Time 18:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved