Plan Review Details - Permit 22060998
Plan Review Stops For Permit 22060998
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-15 Cont ID  
Sent By jbrooks Date 2022-07-15 Time 11:05 Rev Time 0.00
Received By jbrooks Date 2022-07-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By jbrooks Date 2022-06-23 Time 11:06 Rev Time 0.00
Received By jbrooks Date 2022-06-23 Time 08:15 Sent To  
Notes
2022-06-23 11:06:30JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. SUBMITTED PRODUCT APPROVAL FL1654-R28 HAS BEEN
 REVISED TO FL1654-R29. PLEASE PROVIDE THE FOLLOWING:
 INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL27499-R4 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL27499.1-R4 COVERS MULTIPLE INSTALLATION
 OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT INSTALLATION OPTION FROM PAGE #2 OF THE
 EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 4. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 21-0602.14 SELECT INSTALLATION PROCEDURE SYSTEM TYPE
 E(1), E(2) OR E(3) IT DO NOT ALLOW FOR DIRECT-TO-DECK
 INSTALLATION. THE CITY OF WEST PALM BEACH WILL NOT
 ACCEPT THIS METHOD OF INSTALLATION WITHOUT ITS EXPLICIT
 MEANS OF INSTALLATION INDICATED IN THE NOA.
 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-15 Cont ID  
Sent By jbrooks Date 2022-07-15 Time 11:05 Rev Time 0.00
Received By jbrooks Date 2022-06-29 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-23 Cont ID  
Sent By jbrooks Date 2022-06-23 Time 11:06 Rev Time 0.00
Received By jbrooks Date 2022-06-22 Time 07:25 Sent To  
Notes
***NONE***