Plan Review Details - Permit 22060860
Plan Review Stops For Permit 22060860
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 12:21 Rev Time 0.00
Received By shill Date 2022-09-06 Time 12:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 08:26 Rev Time 0.00
Received By shill Date 2022-08-29 Time 08:26 Sent To  
Notes
2022-08-29 08:29:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 SEE PREVIOUS LISTS FOR CODE REFERENCES
  
 MSC90 SPEC SHEET WAS UPLOADED. TEST REPORTS FOR
 SUPERSIM 90 WERE UPLOADED BUT THEY WERE NAMED "MSC90".
 IF MSC90 IS PROPOSED, PROVIDE TEST REPORTS FOR MSC90.
 IF SUPERSIM90 IS PROPOSED, EMAIL
 [email protected] AND REQUEST THAT ALL OTHER
 FILES BE DELETED, UPLOAD THE SPEC SHEET FOR SUPERSIM90.
 NORMALLY I'D DELETE THE UNNECESSARY FILES AND PASS THE
 REVIEW BUT DUE TO THE WAY THE FILES WERE NAMED, THE
 PRODUCT PROPOSED IS NOT CLEAR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 13:51 Rev Time 0.00
Received By shill Date 2022-08-03 Time 13:51 Sent To  
Notes
2022-08-03 13:51:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 2ND REVIEW - THE STC AND IIC TEST REPORTS WERE DONE
 WITH A DROPPED CEILING AND AN 8" SLAB. OUR RECORDS SHOW
 THAT THS BUILDING HAS A 5.5" SLAB, SO YOU NEED A
 PRODUCT THAT HAS BEEN TESTED TO A 6" OR THINNER SLAB.
  
 PROFLEX MSC 90 IS PROPOSED. WE DO NOT HAVE TEST REPORTS
 ON FILE, PLEASE PROVIDE.
  
 PROFLEX SUPERSIM 90 FLAME SPREAD TEST WAS UPLOADED. IF
 YOU WISH TO USE THAT PRODUCT, PLEASE ADVISE, WE HAVE
 TEST REPORTS ON FILE. WHEN RESUBMITTING PLEASE SUBMIT A
 RESPONSE LETTER MAKING THIS REQUEST. IF NOT, PLEASE
 PROVIDE THE STC AND ICC TESTS AS NOTED ABOVE.
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 16:07 Rev Time 0.00
Received By shill Date 2022-07-26 Time 16:07 Sent To  
Notes
2022-07-26 16:08:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 PROFLEX MSC 90 IS PROPOSED. WE DO NOT HAVE TEST REPORTS
 ON FILE, PLEASE PROVIDE.
  
 1. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By   Date 2022-07-06 Time   Rev Time 0.00
Received By bdolan Date 2022-07-06 Time 10:30 Sent To  
Notes
2022-07-06 10:33:22PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 12:21 Rev Time 0.00
Received By shill Date 2022-08-31 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 08:29 Rev Time 0.00
Received By shill Date 2022-08-16 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By shill Date 2022-08-03 Time 13:51 Rev Time 0.00
Received By shill Date 2022-07-30 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 16:08 Rev Time 0.00
Received By shill Date 2022-07-05 Time 05:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 16:08 Rev Time 0.00
Received By shill Date 2022-07-26 Time 16:08 Sent To  
Notes
***NONE***