Plan Review Details - Permit 22060835
Plan Review Stops For Permit 22060835
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-09-15 Cont ID  
Sent By cpuell Date 2022-09-15 Time 09:37 Rev Time 0.00
Received By cpuell Date 2022-09-15 Time 09:37 Sent To  
Notes
2022-09-15 09:38:16ADDRESS OF 2807 S DIXIE HWY ASSIGNED TO THIS SUITE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By cpuell Date 2022-07-21 Time 11:22 Rev Time 0.00
Received By cpuell Date 2022-07-21 Time 11:22 Sent To  
Notes
2022-07-21 11:28:01SUITE JR6 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 DUE TO THE COMPLEXITIES OF THIS PARCEL, PLEASE PROVIDE
 A SITE PLAN OR AERIAL PHOTO SHOWING THE EXACT LOCATION
 WHERE THE TENANT SPACE IS LOCATED. PLEASE EMAIL TO
 [email protected] FOR FURTHER QUESTIONS YOU CAN
 ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2022-11-07 Cont ID  
Sent By rmcdouga Date 2022-11-07 Time 09:59 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 09:59 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2022-10-26 Cont ID  
Sent By rmcdouga Date 2022-10-26 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-10-26 Time 17:14 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-10-12 Cont ID  
Sent By rmcdouga Date 2022-10-12 Time 16:02 Rev Time 0.00
Received By rmcdouga Date 2022-10-12 Time 16:02 Sent To  
Notes
2022-10-12 16:02:36PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 06:41 Rev Time 0.00
Received By rmcdouga Date 2022-08-19 Time 06:41 Sent To  
Notes
2022-08-19 06:54:11PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-11-07 Cont ID  
Sent By rmcdouga Date 2022-11-07 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-10-26 Cont ID  
Sent By rmcdouga Date 2022-10-26 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-10-26 Time 17:14 Sent To  
Notes
2022-10-26 17:19:19THE SECOND BUILDING REVIEW WAS ACCIDENTALLY LOCKED.
  
 PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) RESOLVED.
  
 3) [NOT RESOLVED. I NEED THE ACTUAL FLORIDA PRODUCT OR
 MIAMI-DADE NOA FOR THE LOUVERS. IT HAS TO BE CURRENT
 WITH THE 2020 FBC. NEITHER OF THESE HAVE BEEN
 SUBMITTED.]
 [THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 EXTERIOR LOUVERS (NOA NO. 17-1218.26) EXPIRED ON JULY
 28, 2021. THE DOCUMENTS THAT WERE SUBMITTED FOR THE
 STOREFRONT WINDOWS ARE NOT COMPLETE PRODUCT APPROVALS.
 NEITHER ONE OF THEM WAS REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.] SUBMIT PRODUCT APPROVALS FOR THE
 PROPOSED WINDOWS AND LOUVERS IN THE EXTERIOR WALL THAT
 MEET THE REQUIRED COMPONENT AND CLADDING PRESSURES. FBC
 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS
 WHICH ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA
 STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE
 COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS,
 WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR
 DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-12 Cont ID  
Sent By rmcdouga Date 2022-10-12 Time 16:08 Rev Time 0.00
Received By rmcdouga Date 2022-10-12 Time 16:08 Sent To  
Notes
2022-10-12 16:09:11THE SECOND BUILDING REVIEW WAS ACCIDENTALLY LOCKED.
  
 PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) RESOLVED.
  
 3) [NOT RESOLVED. THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE EXTERIOR LOUVERS (NOA NO. 17-1218.26)
 EXPIRED ON JULY 28, 2021. THE DOCUMENTS THAT WERE
 SUBMITTED FOR THE STOREFRONT WINDOWS ARE NOT COMPLETE
 PRODUCT APPROVALS. NEITHER ONE OF THEM WAS REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.] SUBMIT PRODUCT
 APPROVALS FOR THE PROPOSED WINDOWS AND LOUVERS IN THE
 EXTERIOR WALL THAT MEET THE REQUIRED COMPONENT AND
 CLADDING PRESSURES. FBC 107.3.4 - PROVIDE PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE COMPLETE PRODUCT APPROVALS WITH FL
 OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2022-08-19 Time 06:41 Sent To  
Notes
2022-08-19 11:29:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS APPEAR TO BE MISSING SOME OF THE REQUIRED
 (DIRECTIONAL) EXIT SIGNS. 1013.1 WHERE REQUIRED. EXITS
 AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED
 EXIT SIGN READILY VISIBLE FROM ANY DIRECTION OF EGRESS
 TRAVEL. THE PATH OF EGRESS TRAVEL TO EXITS AND WITHIN
 EXITS SHALL BE MARKED BY READILY VISIBLE EXIT SIGNS TO
 CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL IN
 CASES WHERE THE EXIT OR THE PATH OF EGRESS TRAVEL IS
 NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS. INTERVENING
 MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE MARKED BY
 EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS
 MORE THAN 100 FEET (30 480 MM) OR THE LISTED VIEWING
 DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE
 NEAREST VISIBLE EXIT SIGN.
  
 2) THE COMMON PATH OF EGRESS TRAVEL DISTANCE ON LIFE
 SAFETY SHEET A003 IS NOT SHOWN CORRECTLY. THE COMMON
 PATH OF EGRESS TRAVEL DISTANCE IS USED TO DETERMINE IF
 MORE THAN ONE EXIT IS REQUIRED. IT IS THE DISTANCE FROM
 THE MOST REMOTE POINT IN THE AREA TO AN EXIT OR TO
 WHERE THERE IS TWO SEPARATE AND DISTINCT PATHS OF
 TRAVEL TO SEPARATE EXITS. THE MAXIMUM COMMON PATH OF
 TRAVEL DISTANCE FOR A BUSINESS OCCUPANCY IN A FULLY
 SPRINKLERED BUILDING IS 100 FEET PER FBC TABLE
 1006.2.1. FBC 1006.2.1 EGRESS BASED ON OCCUPANT LOAD
 AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS OR
 EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED
 WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF
 EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1. THE CUMULATIVE OCCUPANT LOAD FROM
 ADJACENT ROOMS, AREAS OR SPACES SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1004.2. FBC 202 DEFINITIONS.
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS TRAVEL DISTANCE MEASURED FROM THE MOST REMOTE
 POINT OF EACH ROOM, AREA OR SPACE TO THAT POINT WHERE
 THE OCCUPANTS HAVE SEPARATE AND DISTINCT ACCESS TO TWO
 EXITS OR EXIT ACCESS DOORWAYS.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE PROPOSED WINDOWS
 AND LOUVERS IN THE EXTERIOR WALL THAT MEET THE REQUIRED
 COMPONENT AND CLADDING PRESSURES. FBC 107.3.4 - PROVIDE
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED.
  
 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-30 Cont ID  
Sent By fgiaquin Date 2022-09-30 Time 22:01 Rev Time 0.00
Received By fgiaquin Date 2022-09-29 Time 22:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-08-03 Cont ID  
Sent By fgiaquin Date 2022-08-03 Time 21:07 Rev Time 0.00
Received By fgiaquin Date 2022-08-03 Time 19:50 Sent To  
Notes
2022-08-03 21:07:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULE FOR HA IS INCORRECT. BOTH 45KVA
 TRANSFORMERS ARE NOT ON PANEL SCHEDULE AND NO
 OVERCURRENT PROTECTION FOR WIRE SIZE IS SHOWN FOR THEM.
 THE PANELS THEY FEED ARE AND THEIR 200AMP OVERCURRENT
 PROTECTION IS SHOWN AND WIRE SIZES ARE SHOWN.
  
 PROVIDE ACCURATE PANEL SCHEDULE SHOWING CODE COMPLIANT
 LOCATION FOR TRANSFORMERS. NEC 215.3A NEC 450.3B1, NEC
 240.4 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By   Date 2022-07-25 Time   Rev Time 0.00
Received By bdolan Date 2022-07-25 Time 12:20 Sent To  
Notes
2022-07-25 12:33:55THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION, WITH THE FOLLOWING
 COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 PERMITS FOR FIRE SPRINKLER AND ALARM SYSTEM MUST BE
 SUBMITTED PRIOR TO ANY WORK UNDER MASTER PERMIT.
  
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By rwbrown Date 2022-09-21 Time 07:34 Rev Time 0.00
Received By rwbrown Date 2022-09-21 Time 07:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By rwbrown Date 2022-07-25 Time 14:29 Rev Time 0.00
Received By rwbrown Date 2022-07-25 Time 14:18 Sent To  
Notes
2022-07-25 14:30:361ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FGC 304.1 - SHOW YOUR COMBUSTION AIR AND
 MAKE-UP AIR CALCULATIONS AND PROVIDE MAKE-UP AIR IF
 REQUIRED FOR THE GAS DRYERS AND WATER HEATERS.
  
 2. 2020 FGC 503.6 - PLEASE SHOW THE DETAILS OF THE
 WATER HEATER VENTING FOR REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-17 Cont ID  
Sent By aoliver Date 2022-11-17 Time 16:15 Rev Time 0.00
Received By aoliver Date 2022-10-31 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-26 Cont ID  
Sent By rmcdouga Date 2022-10-26 Time 17:19 Rev Time 0.00
Received By rmcdouga Date 2022-10-24 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-12 Cont ID  
Sent By rmcdouga Date 2022-10-12 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2022-09-20 Time 09:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2022-07-20 Time 09:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-11-21 Cont ID  
Sent By lmarchan Date 2022-11-21 Time 15:12 Rev Time 0.00
Received By lmarchan Date 2022-11-08 Time 09:21 Sent To  
Notes
2022-11-21 15:12:18NO IMPACT FEES DUE. LEM
2022-11-08 09:21:1711/8/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-08-19 Cont ID  
Sent By rmcdouga Date 2022-08-19 Time 06:41 Rev Time 0.00
Received By rmcdouga Date 2022-08-19 Time 06:41 Sent To  
Notes
2022-08-19 06:42:43PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 10:21 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-26 Cont ID  
Sent By medwards Date 2022-07-26 Time 11:42 Rev Time 0.00
Received By medwards Date 2022-07-26 Time 09:35 Sent To  
Notes
2022-07-26 11:43:291ST REVIEW FMC
 PERMIT: 22060835
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT NOT
 THE INSPECTION CHECKLIST FOUND ON SHEET M3.01. FBC
 101.5.1.1.2
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1
  
 3) PROVIDE DETAIL DRAWING OF THE MANICURE/PEDICURE
 STATIONS MEETING THE REQUIREMENTS OF FMC 502.20:
 MANICURE AND PEDICURE STATIONS SHALL BE PROVIDED WITH
 AN EXHAUST SYSTEM IN ACCORDANCE WITH TABLE 403.3.1.1,
 NOTE H. MANICURE TABLES AND PEDICURE STATIONS NOT
 PROVIDED WITH FACTORY-INSTALLED EXHAUST INLETS SHALL BE
 PROVIDED WITH EXHAUST INLETS LOCATED NOT MORE THAN 12
 INCHES (305 MM) HORIZONTALLY AND VERTICALLY FROM THE
 POINT OF CHEMICAL APPLICATION.
  
 4) SHEET M2.01: PROVIDE THE OUTDOOR AIR CALCULATIONS
 ACCORDING TO THE OCCUPANCY CLASSIFICATION FROM TABLE
 403.3.1.1. HALLS AND LOBBIES HAVE DIFFERENT
 CALCULATIONS.
  
 5) SHEET M1.02: EXPLAIN THE USE OF THE SUPPLY DUCT
 GOING INTO THE WATER HEATER CLOSET. FBC 107.2.1
  
 6) REMOVE THE RETURN AIR GRILLES FROM THE UTILITY ROOM.
 FMC 601.5
  
 7) M1.02: PROVIDE THE DRYER DUCT MATERIAL, SIZE AND
 MATERIAL. FMC 504.
  
 8) EF-4 A,B,C,D: MUST MEET FMC 504.5. PROVIDE THE
 SPECIFICATIONS FOR THESE EXHAUST FANS THAT SHOWS THE UL
 705 LISTING ALONG WITH THE INSTALLATION INSTRUCTIONS
 SHOWING THE APPROVED LENGTHS THE DUCT WORK; DRYER
 EXHAUST DUCT POWER VENTILATORS. DOMESTIC DRYER EXHAUST
 DUCT POWER VENTILATORS SHALL BE LISTED AND LABELED TO
 UL 705 FOR USE IN DRYER EXHAUST DUCT SYSTEMS. THE DRYER
 EXHAUST DUCT POWER VENTILATOR SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 9) THE GAS RISER DIAGRAM INDICATES ONLY 3 GAS DRYERS.
 SHEET M1.04 INDICATES 4 DRYER EXHAUST DUCTS. PLEASE
 EXPLAIN. FBC 107.2.1
  
 10) SHEET M1.04: EF-1 INDICATES PULLING EXHAUST FROM
 ABOVE THE CEILING? PLEASE EXPLAIN THE USE OF EF-1. FBC
 107.2.1
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By rwbrown Date 2022-09-21 Time 07:30 Rev Time 0.00
Received By rwbrown Date 2022-09-21 Time 07:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-07-25 Cont ID  
Sent By rwbrown Date 2022-07-25 Time 13:39 Rev Time 0.00
Received By rwbrown Date 2022-07-25 Time 13:15 Sent To  
Notes
2022-07-25 14:04:111ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5.
  
 2. 2020 FPC 607.1.2/419.5 - PLEASE SHOW COMPLIANCE FOR
 THE LIMITING DEVICE REQUIRED FOR PUBLIC HANDWASHING
 FACILITIES AND TEMPERED WATER. THE DEVICE SHOULD
 CONFORM TO ASSE 1070.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-07 Cont ID  
Sent By rmcdouga Date 2022-11-07 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2022-11-07 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By rwbrown Date 2022-09-21 Time 07:38 Rev Time 0.00
Received By rwbrown Date 2022-09-21 Time 07:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-25 Cont ID  
Sent By rwbrown Date 2022-07-25 Time 13:00 Rev Time 0.00
Received By rwbrown Date 2022-07-25 Time 13:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-11-17 Cont ID  
Sent By jroach Date 2022-11-17 Time 12:59 Rev Time 0.00
Received By jroach Date 2022-11-17 Time 12:59 Sent To  
Notes
2022-11-17 12:59:43THIS PERMIT REVIEW IS LIMITED TO THE INTERIOR BUILD-OUT
 ONLY!
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE SHOPS AT THE PRESS
 DEVELOPMENT OF SIGNIFICANT IMPACT (DSI) SHALL BE
 SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, ETC., AS
 OUTLINED IN RESOLUTION NO. 81-20, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-11 Cont ID  
Sent By jroach Date 2022-10-11 Time 09:07 Rev Time 0.00
Received By jroach Date 2022-10-11 Time 09:07 Sent To  
Notes
2022-10-11 09:08:58THIS PERMIT REVIEW IS LIMITED TO THE INTERIOR BUILD-OUT
 ONLY!
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. ALL DEVELOPMENT WITHIN THE SHOPS AT THE PRESS
 DEVELOPMENT OF SIGNIFICANT IMPACT (DSI) SHALL BE
 SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, ETC., AS
 OUTLINED IN RESOLUTION NO. 81-20, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 _______________________________________________________
 _____________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-18 Cont ID  
Sent By jroach Date 2022-08-18 Time 12:29 Rev Time 0.00
Received By jroach Date 2022-08-18 Time 12:28 Sent To  
Notes
2022-08-18 12:29:24ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.18.2022
 PERMIT NO.: 22060835
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AS MODIFICATIONS ARE BEING MADE TO THE SOUTH FA?ADE
 OF THE FORMER WAREHOUSE BUILDING, A MINOR AMENDMENT TO
 THE SHOPS AT THE PRESS DEVELOPMENT OF SIGNIFICANT
 IMPACT (DSI) SHALL BE SUBMITTED TO, AND APPROVED BY,
 THE DEVELOPMENT SERVICES DEPARTMENT ? PLANNING
 DIVISION, PRIOR TO ISSUANCE OF A PERMIT FOR SUCH
 EXTERIOR WORK.
  
 2. PLEASE CLARIFY THE VENEER INFILL THAT IS PROPOSED ON
 THE SOUTH ELEVATION.
  
 3. STAFF HAS SIGNIFICANT CONCERNS REGARDING THE
 PROPOSED BLOCKING OF THE LOWER PORTIONS OF THE
 STOREFRONTS FACING SOUTH DIXIE HIGHWAY (EAST FA?ADE).
 THESE STOREFRONTS WERE ADDED AS A PART OF THE FORMAL
 APPROVAL PROCESS FOR REDEVELOPMENT OF THE SITE AND
 SHOULD BE MAINTAINED WITH FULL TRANSPARENCY.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved