Plan Review Details - Permit 22060780
Plan Review Stops For Permit 22060780
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-07-19 Cont ID  
Sent By cpuell Date 2022-07-19 Time 10:17 Rev Time 0.00
Received By cpuell Date 2022-07-19 Time 10:17 Sent To  
Notes
2022-07-19 10:17:53NORTHERN UNIT GIVEN THE ADDRESS OF 4616 S DIXIE HWY,
 MIDDLE UNIT GIVEN THE ADDRESS OF 4618 S DIXIE HWY AND
 THE SOUTHERN UNIT GIVEN THE ADDRESS OF 4622 S DIXIE
 HWY, UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-06-27 Cont ID  
Sent By cpuell Date 2022-06-27 Time 10:59 Rev Time 0.00
Received By cpuell Date 2022-06-27 Time 10:59 Sent To  
Notes
2022-06-27 11:01:30PLANS INDICATE THAT THE BUILDING IS TO BE SUB DIVED
 INTO THREE SPACES, THREE UNIQUE ADDRESSES WILL NEED TO
 BE ESTABLISHED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO HAVE
 ADDRESSES ASSIGNED TO THE THREE SPACES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-07-27 Cont ID  
Sent By rmcphers Date 2022-07-27 Time 16:55 Rev Time 0.00
Received By rmcphers Date 2022-07-27 Time 16:55 Sent To  
Notes
2022-07-27 16:55:42DEMO WAS UNDER A SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-11-04 Cont ID  
Sent By rmcphers Date 2022-11-04 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2022-11-04 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-10-18 Cont ID  
Sent By rmcphers Date 2022-10-18 Time 08:01 Rev Time 0.00
Received By rmcphers Date 2022-10-18 Time 07:55 Sent To  
Notes
2022-10-18 08:00:56OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE ROLL IN SHOWER - (BR4) I DO NOT SEE A
 SEAT THEREFORE THE SIDE GRAB BAR SHOULD EXTEND FULL
 LENGTH OF ALL 3 WALLS PER FBC A 608.3.2 STANDARD
 ROLL-IN TYPE SHOWER COMPARTMENTS. WHERE A SEAT IS NOT
 PROVIDED IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS,
 GRAB BARS SHALL BE PROVIDED ON THREE WALLS. GRAB BARS
 SHALL BE INSTALLED 6 INCHES (150 MM) MAXIMUM FROM
 ADJACENT WALLS.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-08 Cont ID  
Sent By rmcphers Date 2022-09-08 Time 11:17 Rev Time 0.00
Received By rmcphers Date 2022-09-08 Time 11:17 Sent To  
Notes
2022-09-08 11:34:42OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) CONSTRUCTION SHOWN IS TYPE II - PLEASE REMOVE THE
 WOOD FRAMING WALLS FROM DRAWING A500 FBC 603.1
  
 2) PLEASE SHOW THE RESTROOM WALLS, SHOWER WALLS AND
 WALL SURROUNDING THE SERVICE SINK TO COMPLY WITH FBC
 1210 - (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  
 3) ACCESSIBLE ROLL IN SHOWER - I DO NOT SEE A SEAT
 THEREFORE THE SIDE GRAB BAR SHOULD EXTEND FULL LENGTH
 OF THE WALL PER FBC A FIGURE 608.5.3
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2022-07-27 Time 16:11 Sent To  
Notes
2022-07-28 09:09:56OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE DESCRIBE THE "USE" (WHAT TYPE OF BUSINESS)
 FBC 302.2 USE DESIGNATION.
 OCCUPANCY GROUPS CONTAIN SUBORDINATE USES HAVING
 SIMILAR HAZARDS AND RISKS TO BUILDING OCCUPANTS. USES
 INCLUDE, BUT ARE NOT LIMITED TO, THOSE FUNCTIONAL
 DESIGNATIONS LISTED WITHIN THE OCCUPANCY GROUP
 DESCRIPTIONS IN SECTION 302.1. CERTAIN USES REQUIRE
 SPECIFIC LIMITATIONS AND CONTROLS IN ACCORDANCE WITH
 THE PROVISIONS OF CHAPTER 4 AND ELSEWHERE IN THIS CODE.
  
 2) PLEASE SHOW THE ACCESSIBLE RESTROOM IF REQUIRED FOR
 UNIT "A" - FBC A 213.1 GENERAL.
 WHERE TOILET FACILITIES AND BATHING FACILITIES ARE
 PROVIDED, THEY SHALL COMPLY WITH 213.
  
 3) UNIT "A" DOOR NUMBER 13 SHOULD HAVE A CLEAR OPENING
 OF 32" DEPENDING ON THE "USE" - FBC A 404.2.3 CLEAR
 WIDTH.
 DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 4) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC
 602.1 GENERAL.
 BUILDINGS AND STRUCTURES ERECTED OR TO BE ERECTED,
 ALTERED OR EXTENDED IN HEIGHT OR AREA SHALL BE
 CLASSIFIED IN ONE OF THE FIVE CONSTRUCTION TYPES
 DEFINED IN SECTIONS 602.2 THROUGH 602.5.
  
 5) PLEASE SHOW GLASS WALLS TO BE SAFETY GLASS - FBC
 2406.4
  
 6) ACCESSIBLE RESTROOMS = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERRING TO THE MIRROR
 DIMENSION FROM THE FLOOR - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 11:36 Rev Time 0.00
Received By jleahy Date 2022-09-19 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-08 Cont ID  
Sent By jleahy Date 2022-07-08 Time 07:33 Rev Time 0.00
Received By jleahy Date 2022-07-07 Time 18:34 Sent To  
Notes
2022-07-08 07:33:27FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 (1) OUTLET SPACING AND FLOOR OUTLETS MISING IN BOTH
 CONFERENCE ROOMS PER 210.71
  
 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER
 OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE
 LESS THAN AS DETERMINED IN (1) AND (2). THESE
 RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE
 NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH
 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE
  
 (2) AIC CALCULATION FOR THE SERVICE AND PANELS. 110.10
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE
 INCLUDING INFORMATION FROM THE POWER COMPANY STATING
 WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE
 SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE
 EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10;
  
 (3) ALL KITCHEN OUTLETS TO BE GFCI PROTECTED PER
 210.8(B)
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREEPHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 100
 AMPERES OR LESS INSTALLED IN THE FOLLOWING LOCATIONS
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL.
  
 (4) VALUE OF PERMIT SEEMS LOW FOR THE AMOUNT OF WORK
 SHOWN ON PLANS.(18K)
  
 PLEASE SUBMIT A COST BREAKDOWN OR IF YOU WANT YOU CAN
 SUBMIT A SIGNED CONTRACT WITH THE OWNER.

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-08 Cont ID  
Sent By jleahy Date 2022-07-08 Time 07:35 Rev Time 0.00
Received By jleahy Date 2022-07-08 Time 07:35 Sent To  
Notes
2022-07-08 07:36:41VOICE AND DATA AS PER PLAN UNITS A AND C ONLY. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-21 Cont ID  
Sent By   Date 2022-06-21 Time   Rev Time 0.00
Received By bdolan Date 2022-06-21 Time 08:46 Sent To  
Notes
2022-06-21 08:50:08PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-04 Cont ID  
Sent By rmcphers Date 2022-11-04 Time 11:33 Rev Time 0.00
Received By rmcphers Date 2022-10-27 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-18 Cont ID  
Sent By rmcphers Date 2022-10-18 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2022-10-05 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-19 Cont ID  
Sent By jleahy Date 2022-09-19 Time 11:37 Rev Time 0.00
Received By jleahy Date 2022-08-31 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-28 Cont ID  
Sent By rmcphers Date 2022-07-28 Time 09:11 Rev Time 0.00
Received By rmcphers Date 2022-06-16 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 06:45 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 06:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 15:48 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 15:45 Sent To  
Notes
2022-06-24 15:48:50THIS APPEARS TO BE A CHANGE OF USE FROM RETAIL TO
 BUSINESS (OFFICE SPACE). PROVIDE THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS. ALSO PROVIDE THE OUTDOOR
 AIR CALCULATIONS BASED ON EACH USE OF SPACE I.E.
 OFFICE, CONFERENCE ROOM, CORRIDORS, COPYING ROOMS. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-10-07 Cont ID  
Sent By rwbrown Date 2022-10-07 Time 10:57 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-09-07 Cont ID  
Sent By ccole Date 2022-09-07 Time 17:57 Rev Time 0.00
Received By ccole Date 2022-09-07 Time 16:40 Sent To  
Notes
2022-09-07 17:57:572ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22060780
 9/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A601 & P3: THE NEW ACCESSIBLE ROLL-IN SHOWER
 IS NOT DESIGNED IN COMPLIANCE WITH SEC. AND FIGURE
 608.2.2. FBC ACC. A MINIMUM 60-INCH WIDE OPENING IS
 REQUIRED ON THE FACE OF THE COMPARTMENT, A MINIMUM
 30-INCHES WIDE X 60 INCHES LONG CLEAR FLOOR SPACE SHALL
 BE PROVIDED ADJACENT TO THE OPEN FACE OF THE SHOWER
 WHICH CANNOT BE OBSTRUCTED BY THE WATER CLOSET- SEC.
 2.2.1 FBC ACC. UNDER THE EXCEPTION A LAVATORY COMPLYING
 WITH SEC. 606 SHALL BE PERMITTED ON ONE 30-INCH WIDE
 MINIMUM SIDE OF THE CLEARANCE PROVIDED IT IS NOT ON THE
 SIDE OF THE CLEARANCE ADJACENT TO THE CONTROLS- SEC.
 606.2.2.1 FBC ACC.
  
 2) A600 & A601: PROVIDE ACCESSIBLE GRAB BAR AND CONTROL
 DETAILS FOR THE NEW ROLL-IN SHOWER IN ACCORDANCE WITH
 SEC. & FIGURE 608.3.2, AND SEC. AND FIGURE 608.5.2 FBC
 ACC.
  
 3) A100: THE DRINKING FOUNTAINS IN UNIT B ARE
 PROTRUDING INTO THE CIRCULATION PATH GREATER THAN THE
 MAXIMUM 4-INCHES ALLOWABLE PER SEC. 307.2 FBC ACC.
 PLEASE NOTE THAT DRINKING FOUNTAINS WITH CANE APRONS
 ARE ALLOWED HOWEVER THE FOUNTAINS WERE NOT INCLUDED IN
 THE FIXTURE SCHEDULE ON SHEET P-1.
  
 4) P-1: THE WATER RISER SHOWS THE IWH-1 WATER HEATERS
 SUPPLYING LAVATORIES IN UNIT A AND UNIT C WHICH ARE
 REQUIRED TO DELIVER TEMPERED WATER, NOT HOT WATER- SEC.
 419.5 FBC P. PLEASE PROVIDE ASSE 1070 APPROVED MIXING
 VALVES AT THE LOCATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-27 Cont ID  
Sent By ccole Date 2022-06-27 Time 11:09 Rev Time 0.00
Received By ccole Date 2022-06-27 Time 11:09 Sent To  
Notes
2022-06-27 11:15:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22060780
 6/27/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A100: THE FIXTURE CALCULATIONS SHALL BE
 CALCULATED FOR EACH OCCUPANCY SEPARATELY- SEC. AND
 TABLE 403.1 FBC P. BASED ON TABLE 403.1 FOOTNOTE(E),
 AND SEC. 410.2 SERVICE SINKS AND DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES FOR UNITS A & B. PLEASE REVISE THE
 PLANS TO SHOW THE FIXTURE LOCATIONS AND PLUMBING PIPING
 DETAILS- SEC. 107.2.1 WPB.
  
 A) CONCERNING THE REQUIRED DRINKING FOUNTAINS, A
 MINIMUM OF TWO ARE REQUIRED PER SEC. 211.2 FBC ACC- ONE
 HI AND ONE LO FOR EACH UNIT. REFER TO SECTIONS 306,
 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 2) A100 & P3: PLEASE IDENTIFY THE BATHROOMS AS EITHER
 MALE, FEMALE, OR UNISEX- SECS. 403.2 & 403.4 FBC P.
  
 3) A100 & A600: THE GENERIC ACCESSIBLE STALL DETAILS ON
 A600 DO NOT REFLECT THE ACTUAL BATHROOM LAYOUTS PLANS
 FOR THE ACCESSIBLE BATHROOMS IN EACH UNIT. PROVIDE
 ENLARGED SITE-SPECIFIC ACCESSIBLE TOILET ROOM DRAWINGS
 FOR EACH UNIT SHOWING THE FOLLOWING LIST OF FBC ACC
 COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC.
 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 4) A100 & A600: THE SHOWERS SHOWN IN BR2 & BR5 SHALL BE
 ACCESSIBLE IN ACCORDANCE WITH SEC. 213.3.6 FBC ACC.
 REVISE THE DRAWINGS TO PROVIDE THE FOLLOWING LIST OF
 FBC ACC COMPLIANCES:
 A) DIMENSIONS OF THE SHOWER- SEC. 608.2.1
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.1
 C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3 AND 608.3.1
 D) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SEC. 608.5.1.
 E) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6.
 F) LOCATION OF ACCESSIBLE SHOWER SEAT- SECS. 610.3 &
 610.3.2.
  
 5) A100 & A600: THE KITCHEN SINKS AND APPLIANCES SHOWN
 IN UNITS A & C SHALL BE ACCESSIBLE IN ACCORDANCE WITH
 SECS. 212.1 & 212.2 FBC ACC. PROVIDE ENLARGED DRAWINGS
 SHOWING THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE SINKS AND APPLIANCES- SEC. 606.2 & 804.1.
  
 6) P-1: IWH-2 SHALL PROVIDE HOT WATER, NOT TEMPERED
 WATER TO THE KITCHEN SINKS AND DISHWASHERS- SEC. 607.1
 FBC P.
  
 7) P-1: PROVIDE A MEANS OF LIMITING THE HOT WATER
 DELIVERY TEMPERATURE FROM THE KITCHEN SINKS AND
 DISHWASHERS- SEC. 607.1.1 FBC P.
  
 8) P-1 & P-3: THE 1/2-INCH HW PIPES SUPPLYING THE
 LAVATORIES HAVE EXCEEDED THEIR MAXIMUM ALLOWABLE 2FT.
 LENGTHS FROM THE IWH-1 SOURCES- TABLE C404.5.1 FBC EC.
  
 9) P1: PROVIDE THE TYPE OF BACKFLOW PREVENTER TO BE
 INSTALLED- SEC. 608.3 FBC P AND SECS. C, D, & E WPB
 CROSS CONNECTION MANUAL. PLEASE NOTE A SEPARATE PERMIT
 IS REQUIRED FOR INSTALLATION OF THE DEVICE- SECS. 105.1
 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-11-04 Cont ID  
Sent By rmcphers Date 2022-11-04 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2022-11-04 Time 11:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-10-07 Cont ID  
Sent By rwbrown Date 2022-10-07 Time 11:00 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-07 10:57:46PLUMBING PAGES OKAY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-08 Cont ID  
Sent By rmcphers Date 2022-09-08 Time 11:38 Rev Time 0.00
Received By rmcphers Date 2022-09-08 Time 11:38 Sent To  
Notes
2022-09-06 06:46:17MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-25 Cont ID  
Sent By rwbrown Date 2022-06-25 Time 06:46 Rev Time 0.00
Received By rwbrown Date 2022-06-25 Time 06:46 Sent To  
Notes
***NONE***