Plan Review Details - Permit 22060778
Plan Review Stops For Permit 22060778
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2022-09-30 Time 13:57 Sent To  
Notes
2022-09-30 13:58:37NO STRUCTURAL WORK SHOWN. SEPARATE PERMIT OR SUB-PERMIT
 REQUIRED FOR STRUCTURAL WORK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-13 Cont ID  
Sent By mpeterso Date 2022-10-13 Time 08:10 Rev Time 0.00
Received By mpeterso Date 2022-10-13 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-09-14 Cont ID  
Sent By mpeterso Date 2022-09-14 Time 09:24 Rev Time 0.00
Received By mpeterso Date 2022-09-14 Time 09:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By pleduc Date 2022-10-06 Time   Rev Time 0.00
Received By pleduc Date 2022-10-06 Time 10:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-07-05 Cont ID  
Sent By clfranci Date 2022-07-05 Time   Rev Time 0.00
Received By clfranci Date 2022-07-05 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-17 Cont ID  
Sent By aoliver Date 2022-10-17 Time 08:40 Rev Time 0.00
Received By aoliver Date 2022-10-05 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 11:56 Rev Time 0.00
Received By medwards Date 2022-10-03 Time 16:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2022-08-23 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-11 Cont ID  
Sent By medwards Date 2022-07-11 Time 10:52 Rev Time 0.00
Received By medwards Date 2022-07-01 Time 12:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-10-11 Cont ID  
Sent By medwards Date 2022-10-11 Time 15:05 Rev Time 0.00
Received By medwards Date 2022-10-11 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 11:50 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 11:50 Sent To  
Notes
2022-10-04 11:54:40PLEASE ADDRESS 1ST CYCLE REVIEW COMMENTS BELOW:
  
 1ST REVIEW FMC
 PERMIT: 22060778
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE SEVERAL ISSUES WITH THE SUBMITTED DRAWING
 FOR THE GREASE DUCT TERMINATION. THE DRAWING DOES NOT
 GIVE ANY DETAILS FOR THE STRUCTURE THAT IS BEING
 INSTALLED AROUND THE KEF-1, PROVIDE DETAILS AND
 DRAWINGS FOR THIS STRUCTURE INCLUDING THE ACCESS DOORS
 FOR THE SERVICE AND CLEANING OF THE EQUIPMENT AND
 GREASE DUCT. THE DRAWING DOES NOT SHOW THE VEGETATION
 IN THE AREA IN QUESTION. PROVIDE A DETAIL SHOWING THE
 ACCESS DOORS ABOVE THIS AREA. SHEET H-7 INDICATES THIS
 STRUCTURE IS SITTING ON THE CONCRETE SLAB AND THE
 MEASUREMENT FROM THE SLAB TO THE BOTTOM OF THE LOUVER
 IS A MINIMUM OF 10 FEET. THIS MEASUREMENT SHOULD BE
 FROM THE WALKING PAVERS AND NOT FROM THE CONCRETE SLAB
 AS WE HAVE NO WAY OF KNOWING HOW HIGH FROM THE SLAB THE
 PAVERS ARE RAISED. WE DO KNOW THAT THE LOUVER SHOULD BE
 AT LEAST 10 FEET FROM ADJOINING GRADE. FMC 506.3.13.3.
 FBC 107.3.5
  
 2) HOW IS THIS STRUCTURE THAT IS SUPPORTING THE EXHAUST
 LOUVER SECURED? FBC 107.3.5
  
 3) PROVIDE A DETAIL FOR THE SLEEVE WHERE THE GREASE
 DUCT PENETRATES THE ROOF, HOW IS THIS CAPPED? FBC
 107.3.5
  
 4) PROVIDE A DETAIL SHOWING THE CLEARANCE FROM THE
 BUILDING TO THE EXHAUST FAN AND THE GREASE EXHAUST
 DUCTWORK. FBC 107.3.5
  
 5) SHOW THE DEPTH OF THE STRUCTURE FROM THE BUILDING.
  
 FMC 503.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE
 NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT
 BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE
 OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST
 OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By medwards Date 2022-08-29 Time 11:49 Rev Time 0.00
Received By medwards Date 2022-08-29 Time 11:49 Sent To  
Notes
2022-08-29 11:49:531ST REVIEW FMC
 PERMIT: 22060778
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE SEVERAL ISSUES WITH THE SUBMITTED DRAWING
 FOR THE GREASE DUCT TERMINATION. THE DRAWING DOES NOT
 GIVE ANY DETAILS FOR THE STRUCTURE THAT IS BEING
 INSTALLED AROUND THE KEF-1, PROVIDE DETAILS AND
 DRAWINGS FOR THIS STRUCTURE INCLUDING THE ACCESS DOORS
 FOR THE SERVICE AND CLEANING OF THE EQUIPMENT AND
 GREASE DUCT. THE DRAWING DOES NOT SHOW THE VEGETATION
 IN THE AREA IN QUESTION. PROVIDE A DETAIL SHOWING THE
 ACCESS DOORS ABOVE THIS AREA. SHEET H-7 INDICATES THIS
 STRUCTURE IS SITTING ON THE CONCRETE SLAB AND THE
 MEASUREMENT FROM THE SLAB TO THE BOTTOM OF THE LOUVER
 IS A MINIMUM OF 10 FEET. THIS MEASUREMENT SHOULD BE
 FROM THE WALKING PAVERS AND NOT FROM THE CONCRETE SLAB
 AS WE HAVE NO WAY OF KNOWING HOW HIGH FROM THE SLAB THE
 PAVERS ARE RAISED. WE DO KNOW THAT THE LOUVER SHOULD BE
 AT LEAST 10 FEET FROM ADJOINING GRADE. FMC 506.3.13.3.
 FBC 107.3.5
  
 2) HOW IS THIS STRUCTURE THAT IS SUPPORTING THE EXHAUST
 LOUVER SECURED? FBC 107.3.5
  
 3) PROVIDE A DETAIL FOR THE SLEEVE WHERE THE GREASE
 DUCT PENETRATES THE ROOF, HOW IS THIS CAPPED? FBC
 107.3.5
  
 4) PROVIDE A DETAIL SHOWING THE CLEARANCE FROM THE
 BUILDING TO THE EXHAUST FAN AND THE GREASE EXHAUST
 DUCTWORK. FBC 107.3.5
  
 5) SHOW THE DEPTH OF THE STRUCTURE FROM THE BUILDING.
  
 FMC 503.13.3 EXCEPTION: EXHAUST OUTLETS SHALL TERMINATE
 NOT LESS THAN 5 FEET (1524 MM) HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDING, AN ADJACENT
 BUILDING, ADJACENT PROPERTY LINE AND AIR INTAKE
 OPENINGS INTO A BUILDING WHERE AIR FROM THE EXHAUST
 OUTLET DISCHARGES AWAY FROM SUCH LOCATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By medwards Date 2022-07-11 Time 10:44 Rev Time 0.00
Received By medwards Date 2022-07-11 Time 10:44 Sent To  
Notes
2022-07-11 10:49:19SHEET H-6 SHOWS THE KEF-1 EXHAUST TERMINATION
 APPROXIMATELY 6 FT. 3.75 INCHES FROM THE PARKING GARAGE
 WALL AND 1 FT 8.75 INCHES FROM THE WALKING AREA OF THE
 GREEN SPACE. THIS DOES NOT MEET FMC 506.3.13.3. THE
 GREEN SPACE IS AN AREA ON THE ROOF THAT THE EMPLOYEES
 CAN SIT AND ENJOY THE OUTDOORS. THIS WOULD BE
 CONSIDERED GRADE LEVEL. PLEASE REVISE THE DRAWING SO
 THAT IT REFLECTS FMC 506.3.13.3
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-11 Cont ID  
Sent By medwards Date 2022-10-11 Time 15:06 Rev Time 0.00
Received By medwards Date 2022-10-11 Time 15:06 Sent To  
Notes
2022-10-05 16:29:20DIGITALLY SIGNED FILE IN SIGNATURES FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-10-04 Cont ID  
Sent By medwards Date 2022-10-04 Time 11:55 Rev Time 0.00
Received By medwards Date 2022-10-04 Time 11:55 Sent To  
Notes
2022-10-04 11:55:44PLEASE ADDRESS 1ST CYCLE COMMENTS BELOW:
  
 SEE ORIGINAL COMMENT BELOW:
  
 THE DRAWINGS ARE MISSING THE DIGITAL SIGNATURE OF THE
 DESIGNERS. FBC 107.2.1 FS 471/481
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By medwards Date 2022-08-29 Time 12:00 Rev Time 0.00
Received By medwards Date 2022-08-29 Time 12:00 Sent To  
Notes
2022-08-29 12:01:27SEE ORIGINAL COMMENT BELOW:
  
 THE DRAWINGS ARE MISSING THE DIGITAL SIGNATURE OF THE
 DESIGNERS. FBC 107.2.1 FS 471/481
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-11 Cont ID  
Sent By medwards Date 2022-07-11 Time 10:51 Rev Time 0.00
Received By medwards Date 2022-07-11 Time 10:51 Sent To  
Notes
2022-07-11 10:52:08THE DRAWINGS ARE MISSING THE DIGITAL SIGNATURE OF THE
 DESIGNERS. FBC 107.2.1 FS 471/481
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-10-13 Cont ID  
Sent By aaponte Date 2022-10-13 Time 17:39 Rev Time 0.00
Received By aaponte Date 2022-10-13 Time 17:38 Sent To  
Notes
2022-10-13 17:40:00PROVISO: ANY NEW MECHANICAL EQUIPMENT ON ROOF SHALL BE
 SCREENES FROM VIEW WITH A SCREEN AS TALL AS THE
 EQUIPMENT.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-09-22 Cont ID  
Sent By ckimmerl Date 2022-09-22 Time 11:22 Rev Time 0.00
Received By ckimmerl Date 2022-09-22 Time 11:22 Sent To  
Notes
2022-09-22 11:22:38PROVISO: ALL NEW MECHANICAL OR ROOFTOP EQUIPMENT SHALL
 BE ENCLOSED OR SCREENED FROM VIEW WITH A SCREEN EQUAL
 TO THE HEIGHT OF THE EQUIPMENT.