| 2022-06-23 07:22:33 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-22060772 |
| | 6/22/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) REFER TO TABLE 710.2(2) FBC P: THE EXISTING 2-INCH |
| | STACK IS LIMITED TO 24 DFUS FOR STACKS GREATER THAN 3 |
| | BRANCH INTERVALS. TWO CITY PLAZA IS A 20-STORY BUILDING |
| | WITH MULTIPLE INTERVALS AND FIXTURE DRAINS CONNECTING |
| | TO THE 2-INCH STACK SO IT APPEARS THE STACK MAY BE NOT |
| | SIZED LARGE ENOUGH TO ACCEPT ANY ADDITIONAL DFU?S |
| | UNLESS THE STACK INCREASES IN SIZE BELOW THE FLOOR. |
| | PROVIDE MORE INFORMATION. |
| | |
| | 2) PLEASE EXPLAIN WHY A BACKWATER VALVE IS TO BE |
| | INSTALLED IN THE HUB DRAIN LINE- SEC. 714.1 FBC P. |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | GUIDELINES FOR THE STEAM OVEN DRAINAGE SYSTEM- SEC. |
| | 107.2.1 WPB. PLEASE NOTE A TRAP PRIMER MAY BE REQUIRED- |
| | SEC. 1002.4.1. |
| | |
| | 3) INSTALLATION OF THE HUB DRAIN AND DRAIN PIPES WILL |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 4) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 5) THE PLUMBING PLANS SHALL BEAR THE SIGNATURE OF THE |
| | CONTACTOR OR QUALIFIER WHO PREPARED THE DRAWINGS- SEC. |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |