Plan Review Details - Permit 22060772
Plan Review Stops For Permit 22060772
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-07-13 Time   Rev Time 0.00
Received By aoliver Date 2022-07-12 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-07-08 Time   Rev Time 0.00
Received By aoliver Date 2022-07-07 Time 07:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-06-23 Time   Rev Time 0.00
Received By aoliver Date 2022-06-15 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-07-13 Cont ID  
Sent By ccole Date 2022-07-13 Time 14:05 Rev Time 0.00
Received By ccole Date 2022-07-13 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-07-08 Cont ID  
Sent By ccole Date 2022-07-08 Time 10:16 Rev Time 0.00
Received By ccole Date 2022-07-08 Time 09:18 Sent To  
Notes
2022-07-08 10:17:252ND REVIEW FBC-2020 PLUMBING
 PERMIT-22060772
 7/8/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS WERE NOT CORRECTED AND ARE NO LONGER
 COMPLETELY LEGIBLE APPARENTLY BECAUSE OF BEING COPIED
 AND SCANNED TOO MANY TIMES. SOME OF THE PRINT IS NO
 LONGER LEGIBLE- SEC. 107.2.1 WPB.
 THE CONTRACTOR?S RESPONSE NARRATIVE INDICATES ?THE
 2-INCH PIPE BACKS INTO A 3-INCH PIPE IN THE CEILING AND
 IT CONNECTS TO A 4-INCH STACK PIPE UNDER THE SLAB?.
 PLEASE SUBMIT CORRECTED, LEGIBLE AND SIGNED PLUMBING
 PLANS THAT REFLECT THESE CODE COMPLIANT PIPING
 CONDITIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-23 Cont ID  
Sent By ccole Date 2022-06-23 Time 07:21 Rev Time 0.00
Received By ccole Date 2022-06-22 Time 16:11 Sent To  
Notes
2022-06-23 07:22:331ST REVIEW FBC-2020 PLUMBING
 PERMIT-22060772
 6/22/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO TABLE 710.2(2) FBC P: THE EXISTING 2-INCH
 STACK IS LIMITED TO 24 DFUS FOR STACKS GREATER THAN 3
 BRANCH INTERVALS. TWO CITY PLAZA IS A 20-STORY BUILDING
 WITH MULTIPLE INTERVALS AND FIXTURE DRAINS CONNECTING
 TO THE 2-INCH STACK SO IT APPEARS THE STACK MAY BE NOT
 SIZED LARGE ENOUGH TO ACCEPT ANY ADDITIONAL DFU?S
 UNLESS THE STACK INCREASES IN SIZE BELOW THE FLOOR.
 PROVIDE MORE INFORMATION.
  
 2) PLEASE EXPLAIN WHY A BACKWATER VALVE IS TO BE
 INSTALLED IN THE HUB DRAIN LINE- SEC. 714.1 FBC P.
 PROVIDE MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE STEAM OVEN DRAINAGE SYSTEM- SEC.
 107.2.1 WPB. PLEASE NOTE A TRAP PRIMER MAY BE REQUIRED-
 SEC. 1002.4.1.
  
 3) INSTALLATION OF THE HUB DRAIN AND DRAIN PIPES WILL
 REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 4) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 5) THE PLUMBING PLANS SHALL BEAR THE SIGNATURE OF THE
 CONTACTOR OR QUALIFIER WHO PREPARED THE DRAWINGS- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-23 Cont ID  
Sent By ccole Date 2022-06-23 Time 07:23 Rev Time 0.00
Received By ccole Date 2022-06-22 Time 16:11 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved