| Plan Review Stops For Permit 22060754 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-07 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-07 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2022-07-07 10:34:56 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-01 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-01 |
Time |
08:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-12-05 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-12-05 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2022-12-05 09:48:21 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE | | | REVIEW. | | | | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: THE LATEST VERSIONS OF PLAN PAGES A-6 & M-2 ARE | | | NOT SIGNED/SEALED BY DESIGN PROFESSIONAL. | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND | | | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | | VALID DIGITAL SIGNATURE. | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C. | | | | | | 2. SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. | | | 481, F.S. & 61G1. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-09-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-20 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-20 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-01 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-01 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-08-01 13:43:37 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, ON PLAN SHEET A-5, DESIGN CRITERIA, | | | THE BUILDING TYPE FOR COMPONENT & CLADDING IS LABELED | | | AS OPEN. IT APPEARS THAT THIS SHOULD BE ENCLOSED. | | | PLEASE CLARIFY OR CHANGE TO ENCLOSED. | | | | | | 2.) FBC B 107.2.1, THERE ARE NO DETAILS FOR THE TIE-IN | | | OF NEW TO EXISTING BUILDINGS. PLEASE PROVIDE DETAILS | | | FOR THE CONNECTION OF NEW TO EXISTING BUILDING AND | | | INCLUDE THE METHOD OF WATER PROOFING JOINTS OF THE VOID | | | BETWEEN BUILDING SECTIONS. | | | | | | 3.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVALS FOR | | | FOAM SPRAY INSULATION. | | | | | | 4.) FBC R 806.5, PROVIDE DETAILS INCLUDING THE AIR | | | IMPERMIABILITY OF INSULATION AS PER THIS SECTION OF | | | CODE AS PLAN SHEET A-6 INDICATES NO VENTS WITH FOAMED | | | ROOF. | | | | | | 5.) FBC R 1003.18, FBC R 1006, & FBC B 107.2.1, ON PLAN | | | SHEETS: 000 COVER SHEET & A-4 THERE ARE INDICATORS OF A | | | CHIMNEY. HOWEVER THERE ARE NO INDICATIONS ON OTHER | | | PAGES OF CHIMNEY. PLEASE CLARIFY AND PROVIDE DETAILS | | | AND INCLUDE REQUIRED MODIFICATIONS OF WALL FRAMING AND | | | FLOOR/ROOF TRUSSES FOR REQUIRED CLEARANCE SEPERATION. | | | | | | 6.) FBC R 314.3 & FBC R 315.1, PROVIDE, ON PLANS, THE | | | SMOKE & CARBON MONOXIDE DETECTOR LOCATIONS. | | | | | | 7.) FBC EC (R) 103.1.1.2 THE ENERGY CALCULATIONS (FORM | | | R405) MUST BE COMPLETED AND SIGNED BY OWNER/OWNER'S | | | REPRESENTATIVE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-02-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2023-02-24 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2023-02-24 |
Time |
15:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-19 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-19 |
Time |
08:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-14 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-14 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-14 |
Time |
17:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-09-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-02 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-02 |
Time |
07:29 |
Sent To |
|
|
| Notes |
| 2022-09-02 07:52:34 | GAS IS UNDER SEPARATE PERMIT 22071210. NO REVIEW UNDER | | | THIS PERMIT. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
5 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-21 |
Time |
00:09 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-21 |
Time |
00:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-10 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-10 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2023-03-10 10:28:13 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PLEASE VERIFY THAT ALL WINDOWS WILL HAVE CLEAR GLASS, | | | WHITE FRAMES AND OGEE MUNTINS. PLEASE ALSO INDICATE | | | WHERE LOW E COATING WILL BE APPLIED (ONLY PERMITTED ON | | | SIDE AND REAR ELEVATIONS) | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-11-17 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-17 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2022-11-17 14:50:43 | WAITING ON HPB APPROVAL | | | SCHEDULED FOR 12/21/22 HPB MEETING |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-09-13 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-09-13 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2022-09-13 16:03:02 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | SCHEDULED FOR 9/27 HISTORIC PRESERVATION BOARD MEETING | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-07-28 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-07-28 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2022-07-28 16:22:56 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | ADDITIONS REQUIRE HISTORIC PRESERVATION BOARD APPROVAL, | | | PLEASE REACH OUT FOR COA FORM AND INFORMATION ON THE | | | APPLICATION PROCESS. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-03-13 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-02-22 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-12-05 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-10-31 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-20 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-01 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-01 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-01 |
Time |
11:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-03-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-26 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-22 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2023-03-24 07:50:44 | RECEIPT MU-2023-012466 - $459.33 PAID | | 2023-03-22 11:29:40 | 3/22/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-01 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-01 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-08-01 10:25:27 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-23 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-23 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-08 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-08 |
Time |
11:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-02 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-02 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2022-09-02 07:52:52 | 1) PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM FOR THE | | | EXISTING HOUSE MECHANICAL UNIT CHANGE OUT. FBC 107.3.5 | | | | | | 2) THIS REVIEWER CANNOT SEE HOW THE SUPPLY AND RETURN | | | FROM THE FIRST FLOOR IS COMING FROM THE MECHANICAL | | | SYSTEM IN THE ATTIC.PLEASE SHOW DETAIL. FBC 107.3.5 | | | | | | 3) WITH THE MECHANICAL SYSTEM IN THE ATTIC I DO NOT SEE | | | HOW THE RETURN IN THE 2ND FLOOR NEW BEDROOM NORTH WOULD | | | BE THE CENTRAL RETURN FOR THE SYSTEM AS THERE IS NO | | | DUCTWORK SHOWN IN THE HALL FROM THAT RETURN. THE RETURN | | | SHOWN IN THE HALL DOES NOT SHOW IT TIED TO THE | | | MECHANICAL SYSTEM IN THE ATTIC. FBC 107.3.5 | | | | | | 4) I DO NOT SEE A CHASE ON THE 2ND FLOOR SHOWING THE | | | RETURN AND SUPPLY TO THE MECHANICAL SYSTEM IN THE | | | ATTIC. PROVIDE A DETAIL SHOWING HOW THIS WILL BE | | | COMPLETED. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-06 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-06 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2022-07-06 07:03:24 | 1ST REVIEW FMC | | | PERMIT: 22060754 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE ENERGY CALCULATIONS. FEC 101.5.2.1.1 | | | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | 3) IT IS UNCLEAR AS TO THE LOCATION OF THE GROUND FLOOR | | | AHU. PLEASE PROVIDE A MECHANICAL DRAWING INDICATING THE | | | LOCATION OF THIS UNIT. FBC 107.2.1 | | | | | | 4) THE APPLICATION IS FOR A NEW ADDITION TO AN EXISTING | | | HOUSE. THE AHU?S PAGE IS LABELED NEW AIR HANDLER FOR | | | OLD HOUSE. THE CONDENSER IS LABELED NEW CONDENSER OLD | | | HOUSE. PROVIDE A COMPLETE SCOPE OF WORK FOR THE | | | MECHANICAL SYSTEMS FOR THIS PROJECT. IS THE AHU?S IN | | | THE EXISTING HOUSE BEING CHANGED OUT? FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2023-02-23 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2023-02-23 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-02 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-02 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2023-02-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-06 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-06 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2022-07-06 12:07:37 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22060754 | | | 7/6/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-1: SHOW THE SOURCE OF THE HOT WATER FOR THE | | | NEW BATH FIXTURES- SEC. P2801.1 FBC RES. FOR A NEW | | | WATER HEATER INSTALLATION PLEASE SHOW THE LOCATION ON | | | THE PLAN PROVIDE AN EQUIPMENT SCHEDULE- SEC. P2801.4 | | | FBC RES. THE EQUIPMENT SCHEDULE SHALL INDICATE THE MAKE | | | AND MODEL, TYPE- TANK OR TANKLESS, GALLON SIZE, | | | EFFICIENCY RATING, AND ELECTRICAL CIRCUITRY. A) PAN AND | | | PAN DRAIN DETAILS REQUIRED FOR STORAGE TANK | | | INSTALLATIONS- SEC. P2801.6 FBC RES. | | | | | | 2) SHEET P-1: BECAUSE THIS IS A MULTI-FAMILY DWELLING | | | AN RPZ BACKFLOW PREVENTER IS REQUIRED FOR THE POTABLE | | | WATER SERVICE- SEC. D WPB UTILITIES CROSS-CONNECTION | | | MANUAL. PLEASE PLACE A NOTE ON THE PLANS VERIFYING | | | THERE IS AN EXISTING RPZ BACKFLOW PREVENTER FOR THE | | | WATER SERVICE, OR NOTE THAT A NEW RPZ WILL BE INSTALLED | | | UNDER A SEPARATE PERMIT- SECS. C, D, & E WPB UTILITIES | | | CROSS-CONNECTION MANUAL & SECS. 105.1 & 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-08-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-01 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-01 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-08-01 16:38:08 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ANY | | | ROOF WORK. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-03-01 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-03-01 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2023-02-23 15:38:31 | MECHANICAL DIGITAL SIGNATURES APPROVED ME | | 2023-02-23 09:56:27 | PLUMBING (P) PLANS SIGS APPROVED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-12-05 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-12-05 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2022-12-05 09:51:48 | SIGNATURE REVIEW DENIED: | | | | | | THE LATEST SUBMITTED VERSIONS OF PLAN SHEETS A-6 & M-2 | | | NEED TO BE SIGNED/SEALED BY THE DESIGN PROFESSIONAL. | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-09-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-20 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-20 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2022-09-19 08:44:34 | ELECTRICAL PAGES ARE APPROVED JLEAHY | | 2022-09-02 07:53:40 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-06 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-06 |
Time |
12:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-21 |
Time |
00:06 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-21 |
Time |
00:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2023-03-10 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-10 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-10 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2023-03-10 10:10:02 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | **PREVIOUS COMMENTS NOT ADDRESSED SEE BELOW** | | | | | | THE VALUE OF THE CONSTRUCTION ($324,270) EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE ($509,807) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. SUBMIT A SEPARATE LANDSCAPE | | | PERMIT WITH PLANS SHOWING MATERIAL EXISTING ON SITE OR | | | ANY ADDITION OF TREES OR SHRUBS TO BRING THE SITE INTO | | | CONFORMITY. | | | | | | REASON: | | | FOR THE MAJORITY OF PROPERTIES, THE EXISTING LANDSCAPE | | | IS NON-CONFORMING. THE MINIMAL CHARGE FOR A PERMIT | | | VALUE OF LESS THAN $2500.00 IS $125.00. THIS ALLOWS FOR | | | STAFF TO REVIEW THE EXISTING MATERIAL ON SITE TO VERIFY | | | THE REQUIREMENTS ARE MET AND ALSO ALLOWS FOR AN | | | INSPECTION TO CONFIRM THE SITE IS IN COMPLIANCE AT THE | | | CONCLUSION OF THE PROJECT. | | | | | | NEW SINGLE FAMILY AND ALL OTHER NEW STRUCTURES REQUIRE | | | A LANDSCAPE PERMIT BE SUBMITTED OR USE THE CONDITIONAL | | | APPROVAL FORM. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-11-17 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-17 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2022-11-17 14:50:08 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | **PREVIOUS COMMENTS NOT ADDRESSED SEE BELOW** | | | | | | THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE | | | IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A | | | SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE | | | SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD | | | | | | SEC 94-441 (B) | | | | | | HPB APPROVAL ALSO REQUIRED FOR PROJECT | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-09-13 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-09-13 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-09-13 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2022-09-13 16:05:52 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE | | | IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A | | | SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE | | | SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD | | | | | | SEC 94-441 (B) | | | | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-28 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-07-28 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-07-28 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2022-07-28 16:23:16 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | SEE HISTORIC COMMENT | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|