Plan Review Details - Permit 22060744
Plan Review Stops For Permit 22060744
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2022-10-13 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2022-09-16 Cont ID  
Sent By rmcdouga Date 2022-09-16 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2022-09-16 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:13 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 16:13 Sent To  
Notes
2022-08-18 16:14:47SEE COMMENTS FOR GARAGE TYPE 1 (EAST).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 09:18 Sent To  
Notes
2022-07-28 09:20:10PLAN REVIEW COMMENTS
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE COMPLETE PRODUCT APPROVALS AND/OR
 EVALUATION REPORTS FOR THE FLOOD VENT MODEL 1540-530
 AND TRIM AND SLEEVE KIT 1540-531-12.
  
 2) SUBMIT A SIGNED AND SEALED FINAL SURVEY. NOTE: THE
 BOOK AND PAGE NUMBER IN SECTION A3 OF THE ELEVATION
 CERTIFICATE DID NOT MATCH THE ONE ON THE PREVIOUS
 SURVEY DRAWINGS THAT WERE SUBMITTED. OUR RECORDS SHOW
 THAT THE PLATS ARE RECORDED IN BOOK 130, PAGE 178.
 PLEASE CORRECT. FBC 107.2.1
  
 3) THE BUILDING DIAGRAM NUMBER IN SECTION A7 OF THE
 ELEVATION CERTIFICATE SHOULD BE 1A FOR THE GARAGES.
 THEY ARE NOT RAISED SLAB ON GRADE PER NFIP ELEVATION
 CERTIFICATE INSTRUCTIONS PAGE 7 OF 9.
  
 4) THE INFORMATION THAT IS ENTERED IN SECTION A9 OF THE
 ELEVATION CERTIFICATE SHOULD BE ENTERED IN SECTION A8.
 THIS IS A DETACHED GARAGE AND SECTION A9 IS FOR GARAGES
 THAT ARE ATTACHED TO ANOTHER BUILDING. IN SECTION A4 IT
 SHOULD BE NOTED THAT THIS IS A DETACHED GARAGE.
  
 5) VERIFY THAT THE SQUARE FOOTAGE OF THE GARAGE IS THE
 MEASUREMENTS TO THE OUTSIDE WALLS AND THAT THEY
 CORRESPOND TO THE SURVEY. NFIP ELEVATION CERTIFICATE
 INSTRUCTIONS ITEM A8.A.
  
 6) THE TOP OF BOTTOM FLOOR ENTERED IN SECTION C2. A) IS
 15.02 FEET. MAKE SURE THAT THE ELEVATION ON THE FINAL
 SURVEY MATCHES THE ELEVATION CERTIFICATE. PLEASE VERIFY
 AND MAKE NECESSARY CORRECTIONS. FBC 107.2.1
  
 7) SUBMIT PHOTOGRAPHS OF THE EXTERIOR SIDES OF THE
 GARAGE THAT SHOWS THE FLOOD VENTS. FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2022-09-21 Time 06:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-19 Cont ID  
Sent By rmcdouga Date 2022-09-19 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2022-08-23 Time 06:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2022-08-15 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2022-07-12 Time 05:28 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 17:48 Rev Time 0.00
Received By rmcdouga Date 2022-10-13 Time 17:48 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By rmcdouga Date 2022-09-19 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2022-09-16 Time 15:22 Sent To  
Notes
2022-09-16 15:21:44PLAN REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE COMPLETE PRODUCT APPROVALS AND/OR
 EVALUATION REPORTS FOR THE FLOOD VENT MODEL 1540-530
 AND TRIM AND SLEEVE KIT 1540-531-12. FBC 107.2.1
  
 2) THE ALL PHASES S & S PDF IS NOT DIGITALLY SIGNED.
 FBC 107.2.1
  
 3) THE INFORMATION THAT IS ENTERED IN THE COMMENT AREA
 OF SECTION D SPECIFIES ITEM A9 WHICH SHOULD BE CHANGED
 TO ITEM A8. ALL OF THE INFORMATION WAS MOVED FROM A9 TO
 A8.
  
 4) [THE SQUARE FOOT AREA OF GARAGE 3 IS 2083 SQFT.
 BASED ON THE SURVEY. PLEASE REVISE ITEM A8 A). ] VERIFY
 THAT THE SQUARE FOOTAGE OF THE GARAGE IS THE
 MEASUREMENTS TO THE OUTSIDE WALLS AND THAT THEY
 CORRESPOND TO THE SURVEY. NFIP ELEVATION CERTIFICATE
 INSTRUCTIONS ITEM A8.A. FBC 107.2.1
  
 5) IN THE CAPTIONS FOR PHOTOS 7 AND 8, SPECIFTY THE
 RIGHT OR LEFT SIDE OF THE BUILDING FOR THE LOCATION OF
 THE FLOOD VENTS. FBC 107.2.1
  
 6) SUBMIT PHOTOGRAPHS OF THE EXTERIOR SIDES OF THE
 GARAGE THAT SHOWS THE FLOOD VENTS. FBC 107.2.1
  
 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:15 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 16:15 Sent To  
Notes
2022-08-18 16:16:35SEE BUILDING COMMENTS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 10:08 Sent To  
Notes
2022-07-28 10:10:26SEE BUILDING REVIEW. NOT RESULTED PENDING PEER REVIEW.
 PEER REVIEW BY ROGER MCPHERSON FOUND NO OTHER ISSUES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-13 Cont ID  
Sent By rmcdouga Date 2022-10-13 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2022-10-13 Time 17:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-09-16 Cont ID  
Sent By rmcdouga Date 2022-09-16 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2022-09-16 Time 15:22 Sent To  
Notes
2022-09-16 15:23:22A DIGITALLY SIGNED FINAL SURVEY IS REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-18 Cont ID  
Sent By rmcdouga Date 2022-08-18 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2022-08-18 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-28 Cont ID  
Sent By rmcdouga Date 2022-07-28 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2022-07-28 Time 09:15 Sent To  
Notes
***NONE***