Plan Review Details - Permit 22060665
Plan Review Stops For Permit 22060665
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-18 Cont ID  
Sent By dbattles Date 2022-08-18 Time 11:20 Rev Time 0.00
Received By dbattles Date 2022-08-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 13:01 Rev Time 0.00
Received By shill Date 2022-08-02 Time 13:01 Sent To  
Notes
2022-08-02 13:17:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 WOOD FLOORS ARE PROPOSED OVER AN UNDERLAYMENT WHICH IS
 NOT CLEAR.
  
 STC TEST FOR PROFLEX MSC 90 WAS SUBMITTED (QUARRY TILE,
 8" SLAB) - NOT OK
 IIC TEST FOR PROFLEX SUPERSIM 90 (TILE, 6" SLAB) - TEST
 OK
 STC TEST FOR PROFLEX SUPERSIM 90 PARTIAL TEST SUBMITTED
 - TEST OK (WE CAN PROVIDE COMPLETE TEST)
 NO FLAME SPREAD SUBMITTED
  
 IT IS SUGGESTED THAT YOU EITHER CONTACT PROFLEX TO SEE
 IF THEY HAVE A FLAME SPREAD TEST FOR SUPERSIM90 WITH A
 COMBUSTIBLE FLOOR, OR CONSIDER PROFLEX LV200 AS PROFLEX
 HAS RECOMMENDED THIS PRODUCT IN THE PAST AND WE HAVE
 THE THREE TEST REPORTS ON FILE. IF YOU ELECT TO TAKE
 THIS OPTION, PLEASE NOTE THAT I DO NOT TAKE INTO
 ACCOUNT QUALITY, SUITABILITY, PRICE, ETC., SIMPLY CODE
 COMPLIANCE AND AVAILABILITY OF THE TEST REPORTS.
  
 SEE PREVIOUS REVIEW FOR CODE REFERENCES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 13:29 Rev Time 0.00
Received By shill Date 2022-07-23 Time 13:29 Sent To  
Notes
2022-07-23 13:32:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 WOOD FLOORS ARE PROPOSED. THE TEST REPORT SUBMITTED IS
 FOR QUARRY TILE OVER 8" SLAB.
  
 1. EITHER PROVIDE TEST REPORTS FOR STC/IIC WHICH WERE
 TESTED WITH A 6" SLAB OR PROVIDE INFORMATION TO SHOW
 HOW YOU HAVE DETERMINED THAT THE SLAB IS 8", SEE CODE
 REFERENCES BELOW.
  
 2. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT (STC, IIC, FLAME SPREAD). FLAME SPREAD
 SHOULD BE TESTED WITH EITHER WOOD FLOOR OR A SIMILAR
 COMBUSTIBLE MATERIAL.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-15 Cont ID  
Sent By pleduc Date 2022-06-15 Time   Rev Time 0.00
Received By pleduc Date 2022-06-15 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-18 Cont ID  
Sent By dbattles Date 2022-08-18 Time 11:20 Rev Time 0.00
Received By dbattles Date 2022-08-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 13:17 Rev Time 0.00
Received By shill Date 2022-07-29 Time 08:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 13:33 Rev Time 0.00
Received By shill Date 2022-06-14 Time 10:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 13:33 Rev Time 0.00
Received By shill Date 2022-07-23 Time 13:33 Sent To  
Notes
***NONE***