Plan Review Details - Permit 22060570
Plan Review Stops For Permit 22060570
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 12:20 Rev Time 0.00
Received By shill Date 2022-07-26 Time 12:20 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:23 Rev Time 0.00
Received By shill Date 2022-07-23 Time 12:23 Sent To  
Notes
2022-07-23 12:23:19PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:10 Rev Time 0.00
Received By shill Date 2022-08-20 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 12:23 Rev Time 0.00
Received By shill Date 2022-07-26 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:23 Rev Time 0.00
Received By shill Date 2022-07-23 Time 12:23 Sent To  
Notes
2022-07-23 12:27:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO STATE TYPE OF FLOORING PROPOSED, FBC
 107. THIS INFORMATION IS REQUIRED TO REVIEW THE
 UNDERLAYMENT PROPOSED.
  
 2. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED, UNLESS WE
 HVE THEM ON FILE - MANUFACTURER SPEC SHEETS ARE NOT
 ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-04 Cont ID  
Sent By fgiaquin Date 2022-08-04 Time 09:37 Rev Time 0.00
Received By fgiaquin Date 2022-08-04 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-07-01 Cont ID  
Sent By jleahy Date 2022-07-01 Time 13:57 Rev Time 0.00
Received By jleahy Date 2022-07-01 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-08-15 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-07-26 Cont ID  
Sent By pleduc Date 2022-07-26 Time   Rev Time 0.00
Received By pleduc Date 2022-07-26 Time 10:49 Sent To  
Notes
2022-07-26 11:06:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NOW AN INDICATION OF THE CARPETING BEING
 INSTALLED BUT NO SPEC SHEET FOR THE PROPOSED CARPET.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.2.2* INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7 UNDER ANY OF
 THE FOLLOWING CONDITIONS:
 (1) WHERE FLOOR FINISH REQUIREMENTS ARE SPECIFIED
 ELSEWHERE IN THE
 CODE
 (2) WHERE THE FIRE PERFORMANCE OF THE FLOOR FINISH
 CANNOT BE DEMONSTRATED TO BE EQUIVALENT TO FLOOR
 FINISHES WITH A CRITICAL RADIANT FLUX
 OF AT LEAST 0.1 W/CM2
  
 10.2.7.1* CARPET AND CARPET-LIKE INTERIOR FLOOR
 FINISHES SHALL COMPLY
 WITH ASTM D2859, STANDARD TEST METHOD FOR IGNITION
 CHARACTERISTICS
 OF FINISHED TEXTILE FLOOR COVERING MATERIALS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED CARPET
 INDICATING THE FIRE BEHAVIOR RATING IN COMPLIANCE WITH
 THE CODE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-10 Cont ID  
Sent By pleduc Date 2022-06-10 Time   Rev Time 0.00
Received By pleduc Date 2022-06-10 Time 10:48 Sent To  
Notes
2022-06-10 11:02:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION ON THE DEMO PLAN TITLE BLOCK
 OF THE ADDRESS: 2600 S OCEAN BLVD, PALM BEACH.
  
 THE APPLICATION AND FLOOR PLAN INDICATE 2800 N FLALGER
 DR, WPB
  
 ENSURE THAT THE SUBMITTED FLOOR PLAN IS CORRECT TO THE
 ADDRESS WITHIN THE CITY OF WPBCH
  
 PLEASE CORRECT.
  
  
  
  
 2) THERE ARE INDICATIONS OF NEW FLOORING; HOWEVER,
 THERE ARE FLOORING PRODUCT TYPE, UNDERLAYMENT NOR SPEC
 SHEETS THAT INDICATED THE REQUIRED FLAME RATING OF THE
 FINISH FLOORING
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 TYPE AND THE PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED
 FLOORING, INCLUDING THE CARPET, INDICATING THE FIRE
 BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS, (OTHER THAN CARPET,)
 PORCELAIN OR CERAMIC TILE, NATURAL STONE TILE, CONCRETE
 TILES, SPEC SHEETS WOULD NOT BE REQUIRED.
  
  
  
 3) THERE IS AN INDICATION OF A NEW SHOWER IN THE MASTER
 BATH.
  
 THAT PROPOSED WORK MAY INCLUDE REMOVING EXISTING SHOWER
 WALL TILE THAT MAY DAMAGE THE EXISTING FIRE RATED WALL
 BOARD.
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE PLAN
 SHEET.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-20 Cont ID  
Sent By shill Date 2022-08-20 Time 09:11 Rev Time 0.00
Received By shill Date 2022-08-14 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By fgiaquin Date 2022-08-04 Time 09:37 Rev Time 0.00
Received By fgiaquin Date 2022-07-25 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:27 Rev Time 0.00
Received By shill Date 2022-06-10 Time 05:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-06-22 Cont ID  
Sent By medwards Date 2022-06-22 Time 05:52 Rev Time 0.00
Received By medwards Date 2022-06-22 Time 05:52 Sent To  
Notes
2022-06-22 05:53:09NO MECHANICAL WORK SHOWN IN SCOPE OF WORK FOR THIS
 PROJECT.ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-17 Cont ID  
Sent By rwbrown Date 2022-06-17 Time 06:01 Rev Time 0.00
Received By rwbrown Date 2022-06-17 Time 06:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:27 Rev Time 0.00
Received By shill Date 2022-07-23 Time 12:27 Sent To  
Notes
***NONE***