| 2022-07-27 13:14:32 | EXCEPT FOR THE SUBMITTAL OF THE FLOOR PLAN, THE |
| | PREVIOUS COMMENTS FOR FIRE NOT BEEN ADDRESSED. |
| | |
| | IS THIS A REVISON OF A PREVIOUS PERMIT? |
| | |
| | WHAT IS THE TYPE OF TILE/FINISHED FLOOING? IF LAMINATE |
| | TYPE FLOORING PROVIDE THE PRODUCT NAME AND SPEC SHEET |
| | SHOWING THE FLAME RATING. |
| | |
| | IF CERAMIC, MARBLE, ETC, PLEASE INDICAATE IT ON THE |
| | FLOOR PALN, NO SPEC SHEET IS NEEDED. |
| | |
| | THE PREVIOUS FIRE COMMENTS ARE SUBMITTED BELOW WITH THE |
| | FLLOR PLAN COMMENT REMOVED. |
| | |
| | ******************************************************* |
| | ************************************************* |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF ON THE APPLICATION OF TILE |
| | CHANGE. |
| | |
| | THAT IS A VERY GENRAL DESCRIPTION WITH NO DETAILS. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE A BETTER DECRIPTIVE OF THE PROPOSED |
| | SCOPE OF WORK, |
| | |
| | |
| | |
| | 2) IN THE BACK UP DOCUMENTS THERE IS A SPEC SHEET FOR |
| | THE FLOOR UNDERLAYMENT WITH THE CITY OF WPBCH PERMIT # |
| | 21120939, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE |
| | ACTUAL PROPOSED TILE FLOORING. |
| | |
| | TILE FLOORING IS MANUFACTURED AROUND THE WORLD AND |
| | DIIFFERENT TYPES AND NOT ALL ARE TESTED AND MEETING |
| | LISTED AND NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | IF THE PROPOSED TILE FLOORING IS PORCELAIN/CERAMIC |
| | TILE, NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC |
| | SHEETS WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE |
| | FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED FINISHED |
| | TILE FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | |
| | 2A) IS THIS SUBMITTAL FOR A CHANGE OF FLOORING TYPE? |
| | |
| | IF SO, A REVISION APPLICATION IS REQUIRED WITH |
| | INDICATIONS AS NOTE ABOVE. |
| | |
| | |
| | |
| | 3) PROVIDED |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |