Plan Review Details - Permit 22060558
Plan Review Stops For Permit 22060558
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 18:24 Rev Time 0.00
Received By shill Date 2022-08-15 Time 18:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2022-08-15 Time 18:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 12:56 Rev Time 0.00
Received By shill Date 2022-08-02 Time 12:56 Sent To  
Notes
2022-08-02 12:58:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST, COMMENT NOT ADDRESSED:
  
 1. SUPERSIM 90 WAS PROPOSED AND PASSED PREVIOUS REVIEW.
 NOW WHISPERMAT CS DATA SHEET WAS UPLOADED. WHICH
 PRODUCT IS PROPOSED?
  
 FBC B 1207, WE HAVE TEST REPORTS ON FILE FOR BOTH
 PRODUCTS.
  
 TO ENSURE THAT THERE IS NO MISUNDERSTANDING, REVISE THE
 FLOOR PLAN TO STATE THE UNDERLAYMENT PROPOSED.
  
 2. NEW COMMENT - THE FLOOR PLAN IS ILLEGIBLE AND DOES
 NOT INDICATE WHICH UNDERLAYMENT IS PROPOSED.
  
 IS THE PROPOSED UNDERLAYMENT SUPERSIM 90 OR WHISPERMAT
 CS? ONLY ONE SHOULD BE PROPOSED UNLESS EACH IS BEING
 INSTALLED IN DIFFERENT AREAS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By shill Date 2022-07-27 Time 09:49 Rev Time 0.00
Received By shill Date 2022-07-27 Time 09:49 Sent To  
Notes
2022-07-27 09:52:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SUPERSIM 90 WAS PROPOSED AND PASSED PREVIOUS REVIEW.
 NOW WHISPERMAT CS DATA SHEET WAS UPLOADED. WHICH
 PRODUCT IS PROPOSED?
  
 FBC B 1207, WE HAVE TEST REPORTS ON FILE FOR BOTH
 PRODUCTS.
  
 TO ENSURE THAT THERE IS NO MISUNDERSTANDING, REVISE THE
 FLOOR PLAN TO STATE THE UNDERLAYMENT PROPOSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:47 Rev Time 0.00
Received By shill Date 2022-07-23 Time 12:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-08-15 Time 12:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By pleduc Date 2022-08-01 Time   Rev Time 0.00
Received By pleduc Date 2022-08-01 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-07-27 Cont ID  
Sent By pleduc Date 2022-07-27 Time   Rev Time 0.00
Received By pleduc Date 2022-07-27 Time 13:06 Sent To  
Notes
2022-07-27 13:14:32EXCEPT FOR THE SUBMITTAL OF THE FLOOR PLAN, THE
 PREVIOUS COMMENTS FOR FIRE NOT BEEN ADDRESSED.
  
 IS THIS A REVISON OF A PREVIOUS PERMIT?
  
 WHAT IS THE TYPE OF TILE/FINISHED FLOOING? IF LAMINATE
 TYPE FLOORING PROVIDE THE PRODUCT NAME AND SPEC SHEET
 SHOWING THE FLAME RATING.
  
 IF CERAMIC, MARBLE, ETC, PLEASE INDICAATE IT ON THE
 FLOOR PALN, NO SPEC SHEET IS NEEDED.
  
 THE PREVIOUS FIRE COMMENTS ARE SUBMITTED BELOW WITH THE
 FLLOR PLAN COMMENT REMOVED.
  
 *******************************************************
 *************************************************
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF ON THE APPLICATION OF TILE
 CHANGE.
  
 THAT IS A VERY GENRAL DESCRIPTION WITH NO DETAILS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE A BETTER DECRIPTIVE OF THE PROPOSED
 SCOPE OF WORK,
  
  
  
 2) IN THE BACK UP DOCUMENTS THERE IS A SPEC SHEET FOR
 THE FLOOR UNDERLAYMENT WITH THE CITY OF WPBCH PERMIT #
 21120939, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE
 ACTUAL PROPOSED TILE FLOORING.
  
 TILE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 DIIFFERENT TYPES AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 IF THE PROPOSED TILE FLOORING IS PORCELAIN/CERAMIC
 TILE, NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC
 SHEETS WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 TILE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2A) IS THIS SUBMITTAL FOR A CHANGE OF FLOORING TYPE?
  
 IF SO, A REVISION APPLICATION IS REQUIRED WITH
 INDICATIONS AS NOTE ABOVE.
  
  
  
 3) PROVIDED
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By pleduc Date 2022-06-13 Time   Rev Time 0.00
Received By pleduc Date 2022-06-13 Time 10:38 Sent To  
Notes
2022-06-13 10:52:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF ON THE APPLICATION OF TILE
 CHANGE.
  
 THAT IS A VERY GENRAL DESCRIPTION WITH NO DETAILS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE A BETTER DECRIPTIVE OF THE PROPOSED
 SCOPE OF WORK,
  
  
  
 2) IN THE BACK UP DOCUMENTS THERE IS A SPEC SHEET FOR
 THE FLOOR UNDERLAYMENT WITH THE CITY OF WPBCH PERMIT #
 21120939, BUT NO SPEC SHEET NOR A PRODUCT NAME FOR THE
 ACTUAL PROPOSED TILE FLOORING.
  
 TILE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 DIIFFERENT TYPES AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 IF THE PROPOSED TILE FLOORING IS PORCELAIN/CERAMIC
 TILE, NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC
 SHEETS WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TILE
 FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED
 TILE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2A) IS THIS SUBMITTAL FOR A CHANGE OF FLOORING TYPE?
  
 IF SO, A REVISION APPLICATION IS REQUIRED WITH
 INDICATIONS AS NOTE ABOVE.
  
  
  
 3) THERE IS NO FLOOR PLAN SUBMITTED.
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE SUBMIT FLOOR PLANS THAT HAVE INDICATIONS WHERE
 THE REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL
 PLANS, ARE LOCATED.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-15 Cont ID  
Sent By shill Date 2022-08-15 Time 18:24 Rev Time 0.00
Received By shill Date 2022-08-12 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-02 Cont ID  
Sent By shill Date 2022-08-02 Time 12:58 Rev Time 0.00
Received By shill Date 2022-07-29 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-27 Cont ID  
Sent By aoliver Date 2022-07-27 Time 14:51 Rev Time 0.00
Received By aoliver Date 2022-07-26 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:47 Rev Time 0.00
Received By shill Date 2022-06-10 Time 11:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 12:47 Rev Time 0.00
Received By shill Date 2022-07-23 Time 12:47 Sent To  
Notes
***NONE***