| 2023-01-25 08:04:13 | 2ND BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE |
| | BELOW: |
| | |
| | 1. FBC R 301, PROVIDE A STRUCTURAL PLAN FOR THE |
| | PROPOSED SHED. |
| | |
| | A PLAN IS AVAILABLE ON THE INTERNET: |
| | |
| | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/SHED%2011 |
| | .PDF |
| | |
| | 2. FBC107, THE SITE PLAN APPEARS TO SHOW THE PROPOSED |
| | SHED ATTACHED TO THE STRUCTURE. IF IT IS ATTACHED, A |
| | STRUCTURAL DETAIL IS REQUIRED. |
| | |
| | 3. FBC107, IF THE PROPOSED SHED IS LESS THAN 5' FROM |
| | THE EISTING HOUSE, PROVIDE A PLAN TO SHOW WHAT WINDOWS |
| | AND DOORS IN THE EXISTING HOUSE ARE AFFECTED BY HAVING |
| | THE SHED IN SUCH CLOSE PROXIMITY. NOTE THE ROOM |
| | DESIGNATION THE ROOM(S) ADJACENT TO THE PROPOSED SHED |
| | (FOR EXAMPLE LIVING ROOM, BEDROOM, KITCHEN). |
| | |
| | NEW COMMENTS: |
| | |
| | 4. THE LOCATION OF THE SHED ON THE SURVEY APPEARS TO BE |
| | IN THE SAME LOCATION AS THE MASTER BATH. PLEASE |
| | CLARIFY? |
| | PROVIDE A SITE PLAN.... |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE |
| | AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | 5. PROVIDE THE FOLLOWING PLANS |
| | |
| | A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON |
| | GRADE/REINFORCING/TIE DOWNS |
| | B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS |
| | C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION |
| | CONNECTION DETAIL |
| | D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION |
| | DETAIL |
| | E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL |
| | CONNECTION DETAIL |
| | F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH |
| | OPENINGS AND DESIGN WIND LOADS IF APPLICABLE. |
| | G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS, |
| | DOORS AND TIE DOWNS. |
| | |
| | 6. PROVIDE CURRENT PRODUCT APPROVALS OR NOA FOR |
| | PROPOSED EXTERIOR DOOR AND WINDOW. |
| | PRODUCT APPROVALS INCLUDE THE COVER SHEET, EVALUATION |
| | REPORT AND INSTALLATION INSTRUCTIONS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |