| 2022-11-23 08:08:19 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO. |
| | 17-1003.04 SYSTEM TYPE E (14) MAXIMUM DESIGN PRESSURE |
| | -90 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE |
| | REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C AREAS. |
| | GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED TO IN |
| | THIS NOA. THE MAXIMUM DESIGNED PRESSURE LIMITATION |
| | LISTED SHALL BE APPLICABLE TO ALL ROOF PRESSURE ZONES |
| | (I.E. FIELD, PERIMETERS, AND CORNERS). NEITHER RATIONAL |
| | ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR |
| | ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E. |
| | PERIMETERS, EXTENDED CORNERS AND CORNERS). THIS SYSTEM |
| | CAN???T BE USED. PROVIDE SYSTEM THAT MEETS OR EXCEEDS |
| | THESE REQUIREMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |