Plan Review Details - Permit 22060410
Plan Review Stops For Permit 22060410
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 17:11 Rev Time 0.00
Received By rmcdouga Date 2022-08-31 Time 17:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2022-07-22 Time 13:52 Sent To  
Notes
2022-07-22 14:22:08PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
 FOR THE PURPOSE OF THIS SECTION, THE EXHAUST FROM
 DWELLING UNIT TOILET ROOMS, BATHROOMS AND KITCHENS
 SHALL NOT BE CONSIDERED AS HAZARDOUS OR NOXIOUS.
  
 2) THE GENERATOR PAD ENGINEERING IS NOT DIGITALLY
 SIGNED BY THE ENGINEER. SEE SIGNATURE REVIEW.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 16:53 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 16:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 17:12 Rev Time 0.00
Received By rmcdouga Date 2022-08-05 Time 06:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 13:53 Rev Time 0.00
Received By rmcdouga Date 2022-06-10 Time 05:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-31 Cont ID  
Sent By rmcdouga Date 2022-08-31 Time 17:11 Rev Time 0.00
Received By rmcdouga Date 2022-08-31 Time 17:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2022-07-22 Time 13:50 Sent To  
Notes
2022-07-22 13:52:45THE GENERATOR PAD DRAWING IS REQUIRED TO HAVE THE
 ENGINEER'S DIGITAL SIGNATURE AND SEAL. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
2022-06-10 16:53:47ELECTRICAL SIGNATURE APPROVED JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-11 Cont ID  
Sent By asangele Date 2022-08-11 Time 14:02 Rev Time 0.00
Received By asangele Date 2022-08-11 Time 14:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-10 Cont ID  
Sent By asangele Date 2022-06-10 Time 14:10 Rev Time 0.00
Received By asangele Date 2022-06-10 Time 14:10 Sent To  
Notes
***NONE***