| Plan Review Stops For Permit 22060388 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-29 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-29 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-06-29 17:39:55 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) [REPEAT COMMENT.] THE ENGINEERED ANCHORING DRAWING | | | THAT WAS SUBMITTED IS A COPY OF THE DIGITALLY SIGNED | | | COPY. SUBMIT AN ORIGINAL DIGITALLY SIGNED ELECTRONIC | | | DOCUMENT. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. NO PHOTOCOPIES OR OTHER FACSIMILES | | | OF THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR | | | FS 471 & FAC 61G15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-05-15 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-05-15 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2023-05-15 16:53:26 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEERED ANCHORING DRAWING THAT WAS SUBMITTED | | | IS A RATHER POOR COPY OF THE DIGITALLY SIGNED COPY. | | | SUBMIT AN ORIGINAL DIGITALLY SIGNED ELECTRONIC | | | DOCUMENT. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. NO PHOTOCOPIES OR OTHER FACSIMILES | | | OF THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR | | | FS 471 & FAC 61G15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-22 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-22 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2022-07-22 15:46:26 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) I HAVE UPLOADED THE SET OF THE APPROVED PLANS FOR | | | THIS SHED FROM THE DBPR MANUFACTURED BUILDING PROGRAM. | | | THIS SHED WAS APPROVED UNDER THE 2017 FBC AND 32989 IS | | | THE ID NUMBER. | | | | | | 2) THE DBPR APPROVED PLANS DO NOT HAVE A FOUNDATION OR | | | ANCHORING PLAN. YOU WILL NEED TO SUBMIT A FOUNDATION | | | AND ANCHORING PLAN THAT HAS BEEN SIGNED AND SEALED BY A | | | FLORIDA LICENSED ENGINEER. FBC 107.2.1 ELECTRONICALLY | | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER | | | VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE | | | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-10 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-10 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-10 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-19 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-19 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-12 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-22 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-06-07 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2023-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-06-29 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-06-29 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2023-06-29 17:29:57 | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | ANCHORING PLAN. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC | | | 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-05-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2023-05-15 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2023-05-15 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2023-05-15 16:54:38 | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | ANCHORING PLAN. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | | REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC | | | 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-22 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-22 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2022-07-22 15:58:41 | A SIGNED AND SEALED FOUNDATION AND ANCHORING PLAN FROM | | | A FL LICENSED ENGINEER IS REQUIRED. ELECTRONICALLY | | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT | | | OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE | | | THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER | | | VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE | | | BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-07-10 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-07-10 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-05-19 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-05-19 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-06-13 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-06-13 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2022-06-13 12:14:51 | 06/13/22 FAILED - THE NEW SHED DOES NOT MEET THE CORNER | | | AND REAR SETBACK REQUIREMENT. ACCESSORY STRUCTURES NEED | | | TO BE SET BACK AT LEAST 12.5 FT FROM THE CORNER | | | PROPERTY LINE AND 5 FT FROM THE REAR PROPERTY LINE IN | | | THE SF7 ZONING DISTRICT. | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 | | | | | | |
|
|