Plan Review Details - Permit 22060388
Plan Review Stops For Permit 22060388
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 16:22 Sent To  
Notes
2023-06-29 17:39:55PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [REPEAT COMMENT.] THE ENGINEERED ANCHORING DRAWING
 THAT WAS SUBMITTED IS A COPY OF THE DIGITALLY SIGNED
 COPY. SUBMIT AN ORIGINAL DIGITALLY SIGNED ELECTRONIC
 DOCUMENT. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. NO PHOTOCOPIES OR OTHER FACSIMILES
 OF THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR
 FS 471 & FAC 61G15

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-15 Cont ID  
Sent By rmcdouga Date 2023-05-15 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2023-05-15 Time 16:47 Sent To  
Notes
2023-05-15 16:53:26PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEERED ANCHORING DRAWING THAT WAS SUBMITTED
 IS A RATHER POOR COPY OF THE DIGITALLY SIGNED COPY.
 SUBMIT AN ORIGINAL DIGITALLY SIGNED ELECTRONIC
 DOCUMENT. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. NO PHOTOCOPIES OR OTHER FACSIMILES
 OF THE SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR
 FS 471 & FAC 61G15

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2022-07-22 Time 15:39 Sent To  
Notes
2022-07-22 15:46:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I HAVE UPLOADED THE SET OF THE APPROVED PLANS FOR
 THIS SHED FROM THE DBPR MANUFACTURED BUILDING PROGRAM.
 THIS SHED WAS APPROVED UNDER THE 2017 FBC AND 32989 IS
 THE ID NUMBER.
  
 2) THE DBPR APPROVED PLANS DO NOT HAVE A FOUNDATION OR
 ANCHORING PLAN. YOU WILL NEED TO SUBMIT A FOUNDATION
 AND ANCHORING PLAN THAT HAS BEEN SIGNED AND SEALED BY A
 FLORIDA LICENSED ENGINEER. FBC 107.2.1 ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-10 Cont ID  
Sent By asangele Date 2023-07-10 Time 15:52 Rev Time 0.00
Received By asangele Date 2023-07-10 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-19 Cont ID  
Sent By vbroglia Date 2023-05-19 Time 16:01 Rev Time 0.00
Received By vbroglia Date 2023-05-12 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2022-06-07 Time 13:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2023-06-29 Cont ID  
Sent By rmcdouga Date 2023-06-29 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2023-06-29 Time 16:22 Sent To  
Notes
2023-06-29 17:29:57THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 ANCHORING PLAN. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-15 Cont ID  
Sent By rmcdouga Date 2023-05-15 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2023-05-15 Time 16:46 Sent To  
Notes
2023-05-15 16:54:38THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE
 ANCHORING PLAN. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. FS 481 & FAC 61G1 OR FS 471 & FAC
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2022-07-22 Time 15:56 Sent To  
Notes
2022-07-22 15:58:41A SIGNED AND SEALED FOUNDATION AND ANCHORING PLAN FROM
 A FL LICENSED ENGINEER IS REQUIRED. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-10 Cont ID  
Sent By asangele Date 2023-07-10 Time 15:52 Rev Time 0.00
Received By asangele Date 2023-07-10 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-05-19 Cont ID  
Sent By vbroglia Date 2023-05-19 Time 16:01 Rev Time 0.00
Received By vbroglia Date 2023-05-19 Time 16:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By afowlkes Date 2022-06-13 Time 12:10 Rev Time 0.00
Received By afowlkes Date 2022-06-13 Time 12:10 Sent To  
Notes
2022-06-13 12:14:5106/13/22 FAILED - THE NEW SHED DOES NOT MEET THE CORNER
 AND REAR SETBACK REQUIREMENT. ACCESSORY STRUCTURES NEED
 TO BE SET BACK AT LEAST 12.5 FT FROM THE CORNER
 PROPERTY LINE AND 5 FT FROM THE REAR PROPERTY LINE IN
 THE SF7 ZONING DISTRICT.
  
 ALEXANDER FOWLKES
 [email protected]
 5618221431
  
  