| Plan Review Stops For Permit 22060351 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-30 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-25 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-07-25 16:21:25 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 2.) PLEASE CLARIFY HOW THE ROOF SECTION IS TO BE | | | COMPLETED. IF ROOF MEMBRANES ARE REQUIRED PROVIDE THE | | | METHOD. IF THIS SYSTEM IS DESIGNED FOR NO ROOFING | | | MATERIAL, PLEASE CLARIFY THE SEALANTS THAT WILL BE | | | REQUIRED AT JOINTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-08 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-08 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2022-07-08 13:19:53 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 1609.3 & WPB AMENDMENTS, PROVIDE, ON PLANS, | | | SHOP DRAWINGS, & ON CALCULATIONS PACKAGE THE WIND | | | LOADS/ULTIMATE WIND SPEED OF 170 MPH. | | | 2.) FBC B 107.2.1, PROVIDE ROOFING DETAILS & PRODUCT | | | APPROVALS FOR NON MEMBRANE SEALANTS IF APPLICABLE AND | | | ALL OTHER ROOFING MATERIALS IF APPLICABLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-10-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-20 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-20 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-07-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-07-18 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-06-16 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-06-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2022-06-16 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2022-06-16 10:43:50 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-11 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-15 |
Time |
06:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-08 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-13 |
Time |
05:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-25 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-08 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-08 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2022-07-08 10:17:32 | SIGNATURE REVIEW DENIED: | | | | | | THE CALCULATION PACKAGE, (14) SHEETS AND SHOP DRAWINGS | | | (3) SHEETS NEED TO HAVE 3RD PARTY VERIFIED SIGNATURES | | | AND SEALS BY THE ENGINEER (CHANDLER P. NANGIA P.E.). | | | THE DESIGNER OF RECORD FOR THIS PROJECT MUST HAVE THEIR | | | REVIEW STAMP APPROVAL ON THIS CALCULATIONS PACKAGE. | | | NOTE: THE WINDLOADS INDICATED ON THIS CALCULATIONS | | | PACKAGE MUST CONFORM TO THE FLORIDA BUILDING CODE | | | REQUIREMENTS OF 170 MPH ULTIMATE DESIGN WIND SPEED. | | | | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-07-25 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-07-25 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-17 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-06-17 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-06-17 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2022-06-17 08:50:27 | 06/17/22 FAILED - PLEASE SHOW THE PROPOSED IMPROVEMENTS | | | ON A SURVEY SO I CAN DETERMINE IF THE PROPOSED CANOPY | | | MEETS SETBACKS. | | | | | | ALEXANDER FOWLKES | | | 5618221431 | | | [email protected] |
|
|