Plan Review Details - Permit 22060302
Plan Review Stops For Permit 22060302
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-10-04 Cont ID  
Sent By jleahy Date 2022-10-04 Time 16:07 Rev Time 0.00
Received By jleahy Date 2022-10-04 Time 16:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-30 Cont ID  
Sent By jleahy Date 2022-08-30 Time 07:52 Rev Time 0.00
Received By jleahy Date 2022-08-30 Time 07:16 Sent To  
Notes
2022-08-30 07:53:33SPECS FOR SLAB DO NOT COVER 24KW GENERATOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 16:57 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 16:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 08:17 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 08:17 Sent To  
Notes
2022-07-17 08:17:59FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO DETAIL FOR PAD SUBMITTED, PLEASE SUBMIT A SIGNED PAD
 DETAIL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 16:57 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 08:16 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 08:10 Sent To  
Notes
2022-07-17 08:17:01FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-04 Cont ID  
Sent By jleahy Date 2022-10-04 Time 16:07 Rev Time 0.00
Received By jleahy Date 2022-09-06 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-30 Cont ID  
Sent By jleahy Date 2022-08-30 Time 07:53 Rev Time 0.00
Received By jleahy Date 2022-08-02 Time 12:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-30 Cont ID  
Sent By jleahy Date 2022-07-30 Time 14:50 Rev Time 0.00
Received By jleahy Date 2022-07-22 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 08:18 Rev Time 0.00
Received By jleahy Date 2022-07-01 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-04 Cont ID  
Sent By jleahy Date 2022-10-04 Time 16:07 Rev Time 0.00
Received By jleahy Date 2022-10-04 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-08-30 Cont ID  
Sent By jleahy Date 2022-08-30 Time 07:52 Rev Time 0.00
Received By jleahy Date 2022-08-30 Time 07:16 Sent To  
Notes
2022-08-30 07:52:31FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SPECS FOR GENERATOR PAD DO NOT COVER 24KW GENERATOR.
  
 AGAIN SIGNATURE IS NOT VERIFIABLE.
  
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-07-29 Cont ID  
Sent By jleahy Date 2022-07-29 Time 16:58 Rev Time 0.00
Received By jleahy Date 2022-07-29 Time 16:58 Sent To  
Notes
2022-07-30 14:47:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SLAB SPECS ARE COPIES DIGITAL PLANS REQUIRE A DIGITAL
 SIGNATURE AND VERIFIABLE BY A THIRD PARTY.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481I
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 08:14 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 08:10 Sent To  
Notes
2022-07-17 08:16:25FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A PHOTOCOPIED OR PRINTED
 SIGNATURE IS NOT ACCEPTABLE. PER FAC 61G15-23.003, (1)
 THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEES SIGNATURE ON EACH PAGE REQUIRED TO BE SEALED.
 A SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEES SIGNATURE SHALL NOT BE USED. (2) THE
 LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY CREATED
 SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING
 THE LICENSEES SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481 (NOT ADDRESSED, SAME PLAN SUBMITTED FOR
 SECOND REVIEW.)

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-11 Cont ID  
Sent By afowlkes Date 2022-07-11 Time 09:55 Rev Time 0.00
Received By afowlkes Date 2022-07-11 Time 09:55 Sent To  
Notes
***NONE***