| Plan Review Stops For Permit 22060301 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-12-20 |
Time |
19:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-12-20 |
Time |
19:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-12-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-12-06 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-12-06 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2022-12-06 07:40:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | NOT CLEAR HOW THIS WAS ADDRESED. DIGITALLY SIGNED PLANS | | | NOT UPLOADED. | | | | | | 1. FS 471, FAC61G15-23 - NOTE THAT DIGITAL OR | | | ELECTRONIC SIGNATURE IS PERMITTED. REVIEW REFERS TO | | | DIGITAL SIGNATURE SINCE THIS IS THE MOST COMMON | | | SIGNATURE. | | | | | | 003 S0.00, S004 S1.00 - GORDON D. BATTISTO, PE, NOT | | | DIGITALLY SIGNED. | | | 005 THROUGH 009, MECHANICAL AND ELECTRICAL PLANS, | | | DIGITALLY SIGNED BY BEAU CHANT GALLO, PE ARE DIGITALLY | | | SIGNED BUT ARE SELF CERTIFIED. FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS REQUIRES THAT THE DIGITAL | | | SIGNATURE BE ISSUED BY A CERTIFICATE AUTHORITY | | | (COMMONLY REFERRED TO AS A 3RD PARTY DIGITAL | | | SIGNATURE). THIS ALSO APPLIES TO 22.08.29 (ENERGY | | | GAGE), AIR SYSTEM SIZING IN THE SUPPORTING DOCS FOLDER. | | | | | | PLEASE EITHER UPLOAD DOCUMENTS THAT ARE DIGITALLY | | | SIGNED IN ACCORDANCE WITH FPBE RULES (DIGITAL SIGNATURE | | | ISSUED BY A CERTIFICATE AUTHORITY, NOT SELF CERTIFIED), | | | OR CONTACT ME VIA EMAIL TO DISCUSS OPTIONS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-10-12 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-10-12 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-10-12 10:17:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FS 471, FAC61G15-23 - NOTE THAT DIGITAL OR | | | ELECTRONIC SIGNATURE IS PERMITTED. REVIEW REFERS TO | | | DIGITAL SIGNATURE SINCE THIS IS THE MOST COMMON | | | SIGNATURE. | | | | | | 003 S0.00, S004 S1.00 - GORDON D. BATTISTO, PE, NOT | | | DIGITALLY SIGNED. | | | 005 THROUGH 009, MECHANICAL AND ELECTRICAL PLANS, | | | DIGITALLY SIGNED BY BEAU CHANT GALLO, PE ARE DIGITALLY | | | SIGNED BUT ARE SELF CERTIFIED. FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS REQUIRES THAT THE DIGITAL | | | SIGNATURE BE ISSUED BY A CERTIFICATE AUTHORITY | | | (COMMONLY REFERRED TO AS A 3RD PARTY DIGITAL | | | SIGNATURE). THIS ALSO APPLIES TO 22.08.29 (ENERGY | | | GAGE), AIR SYSTEM SIZING IN THE SUPPORTING DOCS FOLDER. | | | | | | PLEASE EITHER UPLOAD DOCUMENTS THAT ARE DIGITALLY | | | SIGNED IN ACCORDANCE WITH FPBE RULES (DIGITAL SIGNATURE | | | ISSUED BY A CERTIFICATE AUTHORITY, NOT SELF CERTIFIED), | | | OR CONTACT ME VIA EMAIL TO DISCUSS OPTIONS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-23 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-23 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2022-07-23 12:55:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FS 471, THE ENGINEERING PREPARED BY BOWDOIN G. | | | HUTCHINSON, PE IS NOT DIGITALLY SIGNED. UPLOAD A | | | DIGITALLY SIGNED DOCUMENT OR HAVE HIM CONTACT ME TO | | | DISCUSS OPTIONS. | | | | | | 2. PROVIDE A PLAN SHOWING PROPOSED LOCATION, DISTANCE | | | FROM ROOF EDGE. IF LESS THAN 10' SHOW REQUIRED GUARDS, | | | FBC B 1015.7. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-09 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-09 |
Time |
17:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-18 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-18 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2022-10-18 15:18:32 | DIGITAL SIGNATURE IS NOT VERIFIABLE. JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-01 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-01 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-12-29 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-12-29 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-09 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-11-30 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-18 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-27 |
Time |
07:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-23 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-17 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-20 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-20 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-01 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-01 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2022-12-13 08:55:33 | 1) SHEET M.0: THE OUTDOOR AIR SUMMARY TABLE SPECIFIES | | | 1160 CFMS OF OUTDOOR AIR IS REQUIRED. THE EXISTING | | | ROOFTOP SCHEDULE SPECIFIES THAT EACH OF THE 3 RTUS WILL | | | SUPPLY 290 CFMS, WHICH IS ONLY 870 CFMS. PROVIDE THE | | | REQUIRED OUTDOOR AIR FOR THE SPACE. FMC TABLE 403.3.1.1 | | | | | | 2) I DO NOT SEE THE SPECIFICATIONS ASKED FOR IN COMMENT | | | 3 OF 2ND REVIEW CYCLE. PROVIDE DOCUMENTATION THAT SHOWS | | | THE FABRIC DUCT IS LISTED AND LABELED IN COMPLIANCE | | | WITH UL 2518. FMC 603.17 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-30 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-30 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2022-09-30 06:28:45 | 1ST REVIEW FMC | | | PERMIT: 22060301 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) 2ND ATTEMPT: PLEASE PROVIDE THE OUTDOOR AIR | | | CALCULATIONS FOR THE OCCUPANCY FOR THESE 2 NEW RTU???S. | | | FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | 2) SHEET M-1 SHOWS THE DUCT SMOKE DETECTOR LOCATION AS | | | BEING IN THE RETURN DUCT. PLEASE SHOW THE DUCT SMOKE | | | DETECTORS AS BEING LOCATED IN THE SUPPLY DUCT. FMC | | | 606.2.1 | | | | | | 606.2.1 TO PREVENT THE RECIRCULATION OF DANGEROUS | | | QUANTITIES OF SMOKE, A DETECTOR APPROVED FOR AIR DUCT | | | USE SHALL BE INSTALLED ON THE SUPPLY SIDE OF | | | AIR-HANDLING SYSTEMS AS REQUIRED BY NFPA 90A, STANDARD | | | FOR THE INSTALLATION OF AIR CONDITIONING AND | | | VENTILATING SYSTEMS. SMOKE DETECTORS LISTED FOR USE IN | | | AIR DISTRIBUTION SYSTEMS SHALL BE | | | LOCATED DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY | | | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING THE | | | CAPACITY GREATER THAN 2000 CUBIC FEET PER MINUTE. | | | | | | 3) PROVIDE SPECS ON THE FABRIC DUCT. INCLUDE | | | DOCUMENTATION THAT THIS PRODUCT IS LISTED AND LABELED | | | IN COMPLIANCE WITH UL 2518. FMC 603.17 | | | | | | 4) THE DESIGNER OF THE MECHANICAL SYSTEM, BEAU CHANT C. | | | GALLO MUST SHOW THAT THEIR DIGITAL SIGNATURE HAS BEEN | | | 3RD PARTY VERIFIED. FS 471/481 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-06-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-22 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-22 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2022-06-22 08:43:00 | WHAT IS THE OCCUPANCY CLASSIFICATION OF THE TENANT | | | SPACE? | | | THE CONTRACT STAES THIS IS 2 NEW UNITS THAT WILL BE CUT | | | INTO THE ROOF, NOT LIKE FOR LIKE CHANGE OUTS. PROVIDE A | | | ROOF DRAWING SHOWING THE LOCATION OF THESE NEW RTU'S | | | ALONG WITH A MECHANICAL DRAWING SHOWING THE DUCTWORK IN | | | THE TENANT SPACE. | | | PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THESE 2 NEW | | | RTU'S. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-12-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-20 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-20 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-12-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-12-09 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-12-09 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2022-12-01 15:25:07 | MECHANICAL DIGITAL SIGNATURE APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-18 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-18 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2022-10-18 15:16:34 | DIGITAL SIGNATURE IS NOT VERIFIABLE PLEASE SUBMIT ONE | | | THAT IS VERIFIABLE. JLEAHY | | 2022-09-30 06:33:43 | THE DESIGNER OF THE MECHANICAL SYSTEM MUST BE 3RD PARTY | | | VERIFIED.ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-21 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-21 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2022-06-21 10:43:07 | SIGNATURE REVIEW FAILED | | | 1) SUBMITTED PAPER DOCUMENTS LABELED WIND LOAD | | | CERTIFICATION APPEARS TO BE A COPY OF AN ELECTRINICALLY | | | SIGNED DOCUMENT, AIR SYSTEM SIZING SUMMARY APPEARS TO | | | BE A COPY OF A WET SIGNED AND SEALED DOCUMENT AND | | | DOCUMENT E6.1 DOES NOT APPEAR TO BE SIGNED AS REQUIRED. | | | PLEASE CORRECT THESE ISSUES AS OUTLINED BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | | | | UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN TO THE | | | SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF APPLICABLE) | | | AND COMPLETE THE UPLOAD TASK IN PROJECTDOX.. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] WITH ANY QUESTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2022-12-29 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-12-29 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-12-29 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-12-02 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-12-02 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-12-02 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2022-12-02 11:27:17 | FAILED | | | 12/2/2022 | | | | | | | | | PLEASE PROVIDE WHERE ON THE ROOF THE EQUIPMENT WILL ME | | | BE LOCATED WITH A FULL SURVEY OF THE ROOF AND SETBACKS | | | OF THE EQUIPMENT. | | | | | | | | | MECHANICAL EQUIPMENT MUST BE PROPERLY SCEENED IF IT IS | | | VISIBLE FROM THE PUBLIC RIGHT WAY | | | | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-10-11 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-10-11 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-10-11 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2022-10-11 08:55:16 | 10/11/2022 | | | FAILED | | | | | | PLEASE PROVIDE A FULL SURVEY OF THE ROOF TOP | | | | | | MECHANICAL EQUIPMENT MUST BE PROPERLY SCEENED IF IT IS | | | VISIBLE FROM THE PUBLIC RIGHT WAY | | | | | | | | | | | | | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-07-05 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-07-05 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2022-07-05 14:30:47 | 7/5/2022 | | | FAIL | | | PLEASE PROVIDE A SURVEY WITH LABELED SETBACKS. | | | | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|