Plan Review Details - Permit 22060227
Plan Review Stops For Permit 22060227
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By cwalker Date 2022-09-21 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-09-02 Cont ID  
Sent By cwalker Date 2022-09-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-09-02 12:25:20FIRE REVIEW COMMENTS:
  
 THE SUBMITTED PLAN WAS REVIEWED AND FAILED WITH THE
 FOLLOWING:
  
 (1) ALL SYSTEMS SHALL HAVE BOTH AUTOMATIC AND MANUAL
 METHODS OF ACTIVATION. NFPA 17A 5.2
  
 (2) PROVIDE THE DISTANCE BETWEEN THE HOOD AND THE
 MANUAL ACTIVATION, PATH OF EGRESS, AND THE MOUNTING
 HEIGHT OF THE MANUAL ACTIVATION. NFPA 96 10.5
  
 (3) PROVIDE INFORMATION ON FUSIBLE LINKS TO BE
 UTILIZED. NFPA 17A 4.4.1
  
 (4) PROVIDE THE DISTANCE OF THE COOKING APPLIANCES IN
 REGARDS TO THE HOOD PERIMETER. NFPA 17A 5.1.2
  
 (5) AN AUDIBLE OR VISUAL INDICATOR SHALL BE PROVIDED TO
 SHOW THAT THE SYSTEM HAS OPERATED. NFPA 17A 5.2.1.8
  
 (6) PROVIDE THE DISTANCE OF THE NOZZLES TO THE COOKING
 SURFACE. NFPA 17A 5.5
  
 (7) PROVIDE THE DISTANCE FROM THE COOKING SURFACE TO
 THE PORTABLE CLASS K FIRE EXTINGUISHER LOCATION. NFPA
 96.10.5.1.1
  
 WHEN RESUBMITTING, CORRECTIONS AND/OR ADDITIONS TO THE
 ORIGINAL PLAN SET SHALL BE CLOUDED OR IN A NARRATIVE
 EXPLANATION NOTE..
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 11:05 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 14:29 Rev Time 0.00
Received By medwards Date 2022-09-01 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 11:04 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 14:27 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 14:27 Sent To  
Notes
2022-09-06 14:28:52PROVIDE A DRAWING OF THE KITCHEN HOOD ANSUL SYSTEM
 INSTALLATION SHOWING THE COMPLETE DESIGN. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-06 Cont ID  
Sent By medwards Date 2022-09-06 Time 14:29 Rev Time 0.00
Received By medwards Date 2022-09-06 Time 14:29 Sent To  
Notes
***NONE***