Plan Review Details - Permit 22060204
Plan Review Stops For Permit 22060204
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By jleahy Date 2022-09-21 Time 15:19 Rev Time 0.00
Received By jleahy Date 2022-09-21 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By jleahy Date 2022-06-30 Time 09:45 Rev Time 0.00
Received By jleahy Date 2022-06-30 Time 09:43 Sent To  
Notes
2022-06-30 09:45:32FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 GROUNDING ELECTRODE SYSTEM TO BE INSTALLED PER
 250.32(A) AT EACH BUILDING.
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE. BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING
 ELECTRODE OR GROUNDING ELECTRODE SYSTEM INSTALLED IN
 ACCORDANCE WITH PART III OF ARTICLE 250. THE GROUNDING
 ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE,
 THE GROUNDING ELECTRODE(S) REQUIRED IN 250.50 SHALL BE
 INSTALLED.
  
 HAND DRYERS TO BE GFCI PROTECTED PER 210.8(B) WITHIN 6'
 OF A SINK.
  
 RECEPTACLE. A CONTACT DEVICE INSTALLED AT THE OUTLET
 FOR THE CONNECTION OF AN ATTACHMENT PLUG, OR FOR THE
 DIRECT CONNECTION
 OF ELECTRICAL UTILIZATION EQUIPMENT DESIGNED TO MATE
 WITH THE CORRESPONDING CONTACT DEVICE. A SINGLE
 RECEPTACLE IS A SINGLE
 CONTACT DEVICE WITH NO OTHER CONTACT DEVICE ON THE SAME
 YOKE A MULTIPLE RECEPTACLE IS TWO OR MORE CONTACT
 DEVICES ON THE
 SAME YOKE. (CMP-18)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By jleahy Date 2022-09-21 Time 15:20 Rev Time 0.00
Received By jleahy Date 2022-08-21 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-30 Cont ID  
Sent By jleahy Date 2022-06-30 Time 09:47 Rev Time 0.00
Received By jleahy Date 2022-06-07 Time 13:07 Sent To  
Notes
***NONE***

Review Stop REV REVISIONS
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By lmarchan Date 2022-06-07 Time 13:07 Rev Time 0.00
Received By lmarchan Date 2022-06-07 Time 13:07 Sent To  
Notes
2022-06-07 13:07:43OK TO PASS STOP AFTER FEES HAVE BEEN PAID TO ISSUE. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-21 Cont ID  
Sent By jleahy Date 2022-09-21 Time 15:20 Rev Time 0.00
Received By jleahy Date 2022-09-21 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By jleahy Date 2022-06-30 Time 09:45 Rev Time 0.00
Received By jleahy Date 2022-06-30 Time 09:45 Sent To  
Notes
2022-06-30 09:47:28FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGES SEEM TO BE COPIES OF THE ORIGINALS.
  
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE. WPB
 FBC 107.1; FS 471/481
  