Plan Review Details - Permit 22060129
Plan Review Stops For Permit 22060129
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-21 Cont ID  
Sent By jbrooks Date 2022-07-20 Time 14:02 Rev Time 0.00
Received By jbrooks Date 2022-07-20 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-06 Cont ID  
Sent By jbrooks Date 2022-07-06 Time 14:38 Rev Time 0.00
Received By jbrooks Date 2022-07-06 Time 13:06 Sent To  
Notes
2022-07-06 14:39:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5680-R35 SYSTEM NO. W-57 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-14 Cont ID  
Sent By jbrooks Date 2022-06-14 Time 08:23 Rev Time 0.00
Received By jbrooks Date 2022-06-14 Time 07:33 Sent To  
Notes
2022-06-14 08:24:13JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL
 SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH
 NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS.
 PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT
 INDICATE ON ROOF DRAWING/SKETCH).
 2. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-20 Cont ID  
Sent By jbrooks Date 2022-07-20 Time 14:02 Rev Time 0.00
Received By jbrooks Date 2022-07-07 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-06 Cont ID  
Sent By jbrooks Date 2022-07-06 Time 14:39 Rev Time 0.00
Received By jbrooks Date 2022-06-23 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-14 Cont ID  
Sent By jbrooks Date 2022-06-14 Time 08:24 Rev Time 0.00
Received By jbrooks Date 2022-06-13 Time 08:20 Sent To  
Notes
***NONE***