Plan Review Details - Permit 22060036
Plan Review Stops For Permit 22060036
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 15:08 Rev Time 0.00
Received By shill Date 2022-07-19 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-25 Cont ID  
Sent By pleduc Date 2022-07-25 Time   Rev Time 0.00
Received By pleduc Date 2022-07-25 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-06 Cont ID  
Sent By pleduc Date 2022-06-06 Time   Rev Time 0.00
Received By pleduc Date 2022-06-06 Time 13:17 Sent To  
Notes
2022-06-06 14:33:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED LAMINATE FLOORING.
  
 LAMINATE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE IS NO FLOOR PLAN SHOWING THE LOCATIONS OF THE
 BEDROOMS.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATIONS OF THE BEDROOMS AND PROPOSED
 FLOORING REPLACEMENT..
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 09:52 Rev Time 0.00
Received By shill Date 2022-07-22 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 15:08 Rev Time 0.00
Received By shill Date 2022-06-03 Time 11:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 15:08 Rev Time 0.00
Received By shill Date 2022-07-19 Time 15:08 Sent To  
Notes
***NONE***